BEKA BA678C Скачать руководство пользователя страница 19

Step 6

Configuration of 4/20mA output

See: Fig 6 and section 6.2.7
The BA678C transmitter digital display
at which the transmitter output current is
4mA and 20mA is defined by the ‘CAL’
function

which

contains

two

sub-

functions.  
Using the

or

button select ‘CAL’

from the configuration menu and press

P

which will show the ‘ZEro’ sub-function

prompt. Press

P

again to enter this sub-

function, which will reveal the existing
digital display at which the transmitter
output current is 4mA.

Adjust the

display to the required –0010.0 using
the

or

button to adjust the flashing

digit and the

P

button to move control to

the next digit.

A negative display is

achieved

by

scrolling

the

most

significant digit below zero using the

button. When set press

E

to enter the

new value and return to the ‘ZEro’ sub-
function prompt from which the ‘SPAn’
sub-function, which defines the display
at which the output is 20mA, may be
selected using the

or

button.

Press

P

to enter this sub-function, which

will reveal the existing digital display at
which the transmitter output current is
20mA.

Adjust the display to 0250.0

using the

or

button to adjust the

flashing digit and the

P

button to move

control to the next digit.   
Finally press

E

twice, first to enter the

selection and return to the ‘SPAn’ sub-
function prompt, and again to return to
the ‘CAL’ function prompt in the
configuration menu. 

Step 7

Configuration of bargraph display

See: Fig 6 and section 6.2.8
This

function

contains

three

sub-

functions that justify the bargraph
display and define the transmitter digital
display at which the bargraph starts and
finishes. 

Using the

or

button select ‘bAr’

from the configuration menu and press

P

which will show the ‘b.tYPE’ sub-

function prompt. Press

P

again to enter

this sub-function, which will reveal the
existing bargraph justification. Using the

or

button scroll through the options

and select ‘LEFt’ which will start the
bargraph on the left hand side of the
display. Press

E

to enter the selection

and return to the ‘b.tYPE’ sub-function
prompt from which, using the

or

button, the ‘bArLo’ sub-function may be
selected. Press

P

to enter the ‘bArLo’

sub-function

which

will

reveal

the

existing digital display at which the
bargraph starts.

Set the display to

0100.0 using the

or

button to

adjust the flashing digit and the

P

button

to move control to the next digit. When
set, press

E

to enter the new value and

return to the ‘bArLo’ sub-function prompt
from which the ‘bArHi’ sub-function may
be selected.

Press

P

to enter the

‘bArHi’ sub-function which will reveal the
existing digital display at which the
bargraph finishes.

Set the display to

0200.0 using the

or

button to

adjust the flashing digit and the

P

button

to move control to the next digit.
Finally press

E

twice, first to enter the

selection and return to the ‘bArHi’ sub-
function prompt, and again to return to
the

‘bAr’

function

prompt

in

the

configuration menu.

Step 8

Enter

the

configuration

menu access code.

See Fig 6 and section 6.2.9
This function defines the four digit code
that must be entered to obtain access to
the BA678C transmitter’s configuration
menu.  
Using the

or

button select the

‘CodE’ prompt from the configuration
menu and press

P

which, for a new

instrument, will show the default code
‘0000’ with the first digit flashing. Using
the

or

button to adjust the flashing

digit and the

P

button to transfer control

to the next digit, set the display to 1209.
Press

E

twice to enter the new access

code and return the BA678C to the
display mode via the ‘CodE prompt.    

This

completes

the

instrument

configuration. The BA678C transmitter
will now function as specified at the
beginning of this example. Access to
the configuration is protected by code
1209 which must be entered each time a
change is made.  

19

Содержание BA678C

Страница 1: ...Issue 9 4th July 2019 BA678C Panel mounting indicating temperature transmitter Issue 9...

Страница 2: ...BLANK PAGE 2...

Страница 3: ...ermometer type r tYPE 6 1 13 Decimal point position dP 6 1 14 Lower input display in Lo 6 1 15 Higher input display in Hi 6 3 Configuration defaults 7 Configuration example 8 Maintenance 8 1 Fault fin...

Страница 4: ...diagram of the BA678C Indicating Temperature Transmitter The input which may be from a resistance thermometer thermocouple or a dc voltage or resistance is digitised and transferred to the instrument...

Страница 5: ...the sum of the voltage drops caused by the transmitter load and the cable resistance is less than the minimum supply voltage For the transmitter loop shown in Fig 2 Minimum operating voltage of BA678...

Страница 6: ...at an ambient temperature between 20 C and 70 C Please consult BEKA associates if high vibration is anticipated Fig 3 shows the overall dimensions of the BA678C and the panel cut out To achieve an IP6...

Страница 7: ...tion and custom linearisation to be performed Details of the HART communication are contained in the BA47X 67X Indicating Temperature Transmitter HART Interface Guide which may be downloaded from www...

Страница 8: ...smitter input Selects one of the following inputs Thermocouple tHC 3 wire RTD 3rtd 4 wire RTD 4rtd Differential RTD d_rtd Voltage Volt 3 wire resistance 3rES 4 wire resistance 4rES See section 6 2 1 T...

Страница 9: ...Access code for configuration menu Enters four digit configuration menu access code Default code 0000 disables this function See section 6 2 9 For Voltage and Resistance Inputs see Fig 7 Transmitter...

Страница 10: ...e has been selected press E to enter the selection and return to the t tYPE prompt in the configuration menu 6 2 3 Units of digital display dEG The transmitter digital display may be in one of four un...

Страница 11: ...play the ZEro function in the sub menu pressing P again will reveal the existing transmitter input at which the transmitter output current is 4mA Input is shown in units which depend upon how the tran...

Страница 12: ...will return control to one of the digits 6 2 9 Access code for configuration menu CodE Access to the configuration menu may be protected by a four digit security code which must be entered to gain ac...

Страница 13: ...d using either the or button Pressing the P button again will return control to one of the digits 6 2 13 Higher input display in Hi This function which only appears in the menu when the transmitter is...

Страница 14: ...14...

Страница 15: ...15...

Страница 16: ...16...

Страница 17: ...site Function Factory default Transmitter input InPut 3 wire RTD Sensor type t tYPE Pt100 Units of digital display dEG C Display resolution rESn Low Sensor fault FAuLt Off 4 20mA output CAL 0 0 to 10...

Страница 18: ...to enter the selection and return to the InPut prompt in the configuration menu Step 2 Select resistance thermometer type See Fig 6 and section 6 2 10 Using the or button select the r tYPE prompt fro...

Страница 19: ...eveal the existing bargraph justification Using the or button scroll through the options and select LEFt which will start the bargraph on the left hand side of the display Press E to enter the selecti...

Страница 20: ...e digital display Bargraph is over or under range with scale flashing bargraph displaying all or just one segment Input is outside specified range for bargraph Reconfigure bargraph display Digital dis...

Страница 21: ...e fitted with a blank escutcheon around the liquid crystal display If specified when the instrument is ordered this can be supplied printed with units of measurement and a scale for the horizontal bar...

Страница 22: ...ing Temperature Transmitter HART Interface Guide which may be downloaded from www beka co uk manuals for details Alternatively configuration may be performed using the configuration menu which is acce...

Страница 23: ...high or low function See section 9 3 6 no nC Normally open or normally closed output Determines whether the single pole alarm output is open or closed in the non alarm condition See section 9 3 7 HSt...

Страница 24: ...24...

Страница 25: ...al the current setting The function may be changed by pressing the or button pressing the E button will enter the setting and return the display to the Hi Lo prompt in the alarm menu 9 3 7 Alarm outpu...

Страница 26: ...ed 9 3 11 Access Setpoint ACSP This function controls a separate menu that provides direct access to the alarm setpoints when the BA678C transmitter is in the operational mode The function enables an...

Страница 27: ...be displayed Pressing the or button will toggle between the two alarm setpoint prompts SP1 and SP2 If an incorrect security code is entered or a button is not pressed within ten seconds the transmitt...

Отзывы: