BEKA BA678C Скачать руководство пользователя страница 11

 

6.2.6  Sensor fault analogue indication   ‘FAuLt’

The sensor fault analogue indication function
appears in the menu when the transmitter is
configured for a resistance thermometer or a
thermocouple input.

When a fault is detected the transmitter’s 4/20mA
output current is set to the specified under or over
range fault value and the transmitter’s digital display
flashes as shown below. One of three fault currents
may be selected, or the fault indication may be
turned off.

Irrespective of how the function is set

the transmitter display will flash when a sensor fault
is detected.
 

Selected

Output

Transmitter

             

fault current

current

display

    

‘oFF’ 

No fault indication

Flashes

‘dn3.6’

  3.6mA 

*

Flashes

‘dn3.8’

3.8mA

Flashes

‘uP 21’

21.0mA

Flashes

     *

 Not recommended when HART

 

 communication is used.

The ‘FAuLt’ function may be selected from within the
configuration menu by operating the

or

button.

To enter the function press

P

which will reveal the

existing setting which may be changed using the

or

button. When set as required, press

E

to enter

the selection and return to the ‘FAuLT’ prompt in the
configuration menu.

The typical detection thresholds and approximate
response times are:

Thermocouple

> 5k

   

10 sec

RTD sensor              < 5

  >500

    

  1 sec

RTD sense leads

> 50

             

10 sec

In the time between a fault developing in an RTD
sense lead or a thermocouple and the fault being
detected, the transmitter output and display may drift
from the last correct measured value.  

6.2.7  Configuration of 4/20mA output    ‘CAL’

This function defines the relationship between the
transmitter input and the 4/20mA output current.
‘Zero’ defines the transmitter input at which the
output is 4mA and ‘Span’ defines the input at which
the output is 20mA.   

This function does not affect the transmitter display
which is fixed for thermocouple and resistance
thermometer inputs and adjusted via the ‘in-Lo and
‘in-Hi’ functions for resistance and voltage inputs.

The ‘CAL’ function may be selected from within the
menu by operating the

or

button. To enter the

function press

P

which will display the ‘ZEro’ function

in the sub-menu, pressing

P

again will reveal the

existing transmitter input at which the transmitter
output current is 4mA. Input is shown in units which
depend upon how the transmitter input ‘InPut’ and
display

‘dEG’ have been configured, as shown

below: 

            

Configured                              Input

        transmitter input                     shown as 

Thermocouple  

  

o

C, 

o

F, K or r 

Resistance thermometer

  

o

C, 

o

F, K or r

Voltage

          mV

Resistance

        Ohms

The input, at which the transmitter output current is
4mA, may be changed using the

or

button to

adjust the flashing digit and the

P

button to move

control to the next digit. When the required input has
been selected, press

E

to enter the selection and

return to the ‘ZEro’ prompt in the sub menu.    

The ‘SPAn’ function, which defines the input at which
the transmitter current output is 20mA, may be
selected from within the sub-menu by operating
either the

or

button. To enter the function press

P

which will reveal the existing transmitter input at

which the transmitter output current is 20mA. Again
the input will be shown in units which depend upon
how the transmitter has been configured.

The input, at which the transmitter output current is
20mA, may be changed using the

or

button to

adjust the flashing digit and the

P

button to move

control to the next digit. When the required input has
been selected, press

E

twice to enter the selection

and return to the ‘CAL’ prompt in the configuration
menu.

Note:

When configured for a voltage input, operating

the

P

button when the 0.1mV digit is flashing in the

‘Zero’ or ‘SPAn’ sub-menus increases the input
resolution to 0.01mV which is indicated by the display
colon being activated. When the required input has
been selected, pressing

E

enters the selection and

returns the transmitter to the ‘ZEro’ or ‘SPAn’ prompt
in the sub-menu.    

If, when configured for a voltage or resistance input
the displayed decimal point has been set to
autorange, it may be necessary to manually position
the decimal point before adjusting ‘ZEro’ or ‘SPAn’.
This can be achieved by repeatedly operating the

P

button until the activated decimal point flashes, the
decimal point can then be positioned using either the

or

button.

Pressing the

P

button again will

return control to one of the digits.

11

Содержание BA678C

Страница 1: ...Issue 9 4th July 2019 BA678C Panel mounting indicating temperature transmitter Issue 9...

Страница 2: ...BLANK PAGE 2...

Страница 3: ...ermometer type r tYPE 6 1 13 Decimal point position dP 6 1 14 Lower input display in Lo 6 1 15 Higher input display in Hi 6 3 Configuration defaults 7 Configuration example 8 Maintenance 8 1 Fault fin...

Страница 4: ...diagram of the BA678C Indicating Temperature Transmitter The input which may be from a resistance thermometer thermocouple or a dc voltage or resistance is digitised and transferred to the instrument...

Страница 5: ...the sum of the voltage drops caused by the transmitter load and the cable resistance is less than the minimum supply voltage For the transmitter loop shown in Fig 2 Minimum operating voltage of BA678...

Страница 6: ...at an ambient temperature between 20 C and 70 C Please consult BEKA associates if high vibration is anticipated Fig 3 shows the overall dimensions of the BA678C and the panel cut out To achieve an IP6...

Страница 7: ...tion and custom linearisation to be performed Details of the HART communication are contained in the BA47X 67X Indicating Temperature Transmitter HART Interface Guide which may be downloaded from www...

Страница 8: ...smitter input Selects one of the following inputs Thermocouple tHC 3 wire RTD 3rtd 4 wire RTD 4rtd Differential RTD d_rtd Voltage Volt 3 wire resistance 3rES 4 wire resistance 4rES See section 6 2 1 T...

Страница 9: ...Access code for configuration menu Enters four digit configuration menu access code Default code 0000 disables this function See section 6 2 9 For Voltage and Resistance Inputs see Fig 7 Transmitter...

Страница 10: ...e has been selected press E to enter the selection and return to the t tYPE prompt in the configuration menu 6 2 3 Units of digital display dEG The transmitter digital display may be in one of four un...

Страница 11: ...play the ZEro function in the sub menu pressing P again will reveal the existing transmitter input at which the transmitter output current is 4mA Input is shown in units which depend upon how the tran...

Страница 12: ...will return control to one of the digits 6 2 9 Access code for configuration menu CodE Access to the configuration menu may be protected by a four digit security code which must be entered to gain ac...

Страница 13: ...d using either the or button Pressing the P button again will return control to one of the digits 6 2 13 Higher input display in Hi This function which only appears in the menu when the transmitter is...

Страница 14: ...14...

Страница 15: ...15...

Страница 16: ...16...

Страница 17: ...site Function Factory default Transmitter input InPut 3 wire RTD Sensor type t tYPE Pt100 Units of digital display dEG C Display resolution rESn Low Sensor fault FAuLt Off 4 20mA output CAL 0 0 to 10...

Страница 18: ...to enter the selection and return to the InPut prompt in the configuration menu Step 2 Select resistance thermometer type See Fig 6 and section 6 2 10 Using the or button select the r tYPE prompt fro...

Страница 19: ...eveal the existing bargraph justification Using the or button scroll through the options and select LEFt which will start the bargraph on the left hand side of the display Press E to enter the selecti...

Страница 20: ...e digital display Bargraph is over or under range with scale flashing bargraph displaying all or just one segment Input is outside specified range for bargraph Reconfigure bargraph display Digital dis...

Страница 21: ...e fitted with a blank escutcheon around the liquid crystal display If specified when the instrument is ordered this can be supplied printed with units of measurement and a scale for the horizontal bar...

Страница 22: ...ing Temperature Transmitter HART Interface Guide which may be downloaded from www beka co uk manuals for details Alternatively configuration may be performed using the configuration menu which is acce...

Страница 23: ...high or low function See section 9 3 6 no nC Normally open or normally closed output Determines whether the single pole alarm output is open or closed in the non alarm condition See section 9 3 7 HSt...

Страница 24: ...24...

Страница 25: ...al the current setting The function may be changed by pressing the or button pressing the E button will enter the setting and return the display to the Hi Lo prompt in the alarm menu 9 3 7 Alarm outpu...

Страница 26: ...ed 9 3 11 Access Setpoint ACSP This function controls a separate menu that provides direct access to the alarm setpoints when the BA678C transmitter is in the operational mode The function enables an...

Страница 27: ...be displayed Pressing the or button will toggle between the two alarm setpoint prompts SP1 and SP2 If an incorrect security code is entered or a button is not pressed within ten seconds the transmitt...

Отзывы: