CALIBRATION

The BA405C output currrent does not require any
calibration, the front panel multi-turn control will
always adjust the output current  between
approximately 3.5 and 21mA.

6.1

Internal display

The internal display requires calibrating so that the
4/20mA loop current is shown in the required
engineering units.

The BA405C will be supplied with the display
calibrated as requested at time of ordering.   If
calibration is not requested, the display will be set
to show 00.0 with 4.000mA loop current and 100.0
with 20.000mA loop current.

The display is calibrated by plug-in links and two
multi-turn potentiometers which are accessible
through holes in the rear panel.    To
gain access to the links the rear panel must be
removed as shown  in Fig 8.

For maximum accuracy the display should be
calibrated using a traceable current measuring
device  with an accuracy greater than 4µA.

Fig 8  Removal of rear panel

6.1.1 Zero adjustment

Zero is defined as the number displayed when the
BA405C output is 4.000mA, and may  adjusted
between  -1000 and 1000.   The zero
potentiometer has two ranges 0 to 500 and 500 to
1000.  Tthe polarity of the zero is defined by the
position of the suppression / elevation links.

Fig 9 shows the position of the zero links and zero
potentiometer.

Suppression / elevation links

Elevation

     Positive zero   0 to 1000

   or

Suppression     Negative zero  0 to -1000

Zero link

0 to 500

   or

500 to 1000

6..1.2 Span adjustment

Span is defined as the difference between the
number displayed at 4.000mA and the number
displayed at 20.000mA output.  The span
potentiometer has four ranges defined by the span
links, and may be adjusted to any number between
0 and 1999.
Fig 9 shows the position of the span links and span
potentiometer.

Span links

000

to

500

or

500

to

1000

or

1000

to

1500

or

1500

to

1999

6.1.3 Decimal point

A dummy decimal point may be displayed between
any of the four digits.  The position or absence of
this decimal  point  is determined by
the position of the decimal point link shown in Fig
9.   When calculating the required span and zero
setting the decimal point should be ignored.

6.1.4 Reverse action

Normally the BA405C display increases as the
loop current increases, but this can be reversed.
Please contact BEKA associates for details.

Содержание BA405C

Страница 1: ...BA405C intrinsically safe 2 wire 4 20mA manual set point station issue 6 Issue 6 17th November 2009 ...

Страница 2: ...n 5 1 Location 5 2 Installation procedure 5 3 EMC 6 Calibration 6 1 Internal display 6 1 1 Zero adjustment 6 1 2 Span adjustment 6 1 3 Decimal point 6 1 4 Reverse action 6 1 5 Calibration example 6 1 6 Over under range 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Customer comments 8 Accessories 8 ...

Страница 3: ...hanges in the supply voltage Caution The 4 20mA output should not be used for critical safety applications The 3 digit internal indicator can easily be calibrated on site to show the loop current in engineering units For example in an application where the BA405C is being used to adjust the set point of a speed controller the internal indicator may be calibrated to display the requested speed in R...

Страница 4: ...alent capacitance and inductance Ci 30nF Li 0 01mH 3 4 Zones Gas Groups and T rating The BA405C and both the optional display backlights have been certified as Group II category 1G apparatus EEx ia IIC T5 When powered via a compatable Zener barrier or galvanic isolator the BA405C manual set point station may be installed in Zone 0 explosive gas air mixture continuously present Zone 1 explosive gas...

Страница 5: ...ish that the maximum voltage drop caused by the manual set point station both Zener barriers the load and cable resistance is always less than the minimum supply voltage Fig 2 Typical application using barriers In this example Minimum operating voltage of BA405C 6 1V Maximum voltage drop caused by 28V 6 8V 93mA 0 65W Zener barrier 340Ω end to end resistance x 20mA Maximum voltage drop caused by 1 ...

Страница 6: ... 30nF Li 0 01mH Any Zener barrier or isolator certified EEx ia IIC by an EEC approved body which has output parameters equal to or less than the maximum input parameters specified above may be used Most installations would use a 28V 93mA 0 65W 28V 300Ω device as shown in Fig 4 The display brilliance depends upon the current flowing through the backlight which is determined by the supply voltage an...

Страница 7: ...lease refer to BEKA associates if high vibration is anticipated Fig 6 shows the enclosure dimensions and the recommended panel cut out sizes 5 2 Installation Procedure a Insert the BA405C set point station into the panel aperture from the front Ensure that the gasket is correctly positioned under the bezel b Fix two panel mounting clips to opposite sides of the instrument and tighten until the ind...

Страница 8: ...ed between 1000 and 1000 The zero potentiometer has two ranges 0 to 500 and 500 to 1000 Tthe polarity of the zero is defined by the position of the suppression elevation links Fig 9 shows the position of the zero links and zero potentiometer Suppression elevation links Elevation Positive zero 0 to 1000 or Suppression Negative zero 0 to 1000 Zero link 0 to 500 or 500 to 1000 6 1 2 Span adjustment S...

Страница 9: ...A dummy decimal point is required between the least two significant digits therefore the decimal point link should be placed in the 00 0 position Step 5 Adjust the BA405C front panel control until the output current measured by external ammeter is 4 000mA The zero potentiometer at the rear of the BA405C should then be adjusted until the BA405C displays 25 0 Step 6 Adjust the BA405C front panel con...

Страница 10: ...as clearance certificate is available If a BA405C fails after it has been functioning correctly the following procedure should be followed Symptom Cause Solution No loop Wiring or power Check wiring current supply fault and power supply Unstable Insufficient Check that voltage loop supply between terminals current voltage 1 3 is greater than 6 1 or 10V between terminals 1 13 if fitted with a loop ...

Страница 11: ...to the shaft Loosen the collet by turning the brass split screwhead anti clockwise and then carefully pull the control knob from the shaft c Pull the electronic assembly from the rear of the enclosure d Remove the blank scale card s and mark with the required legend Replace scale card s taking care to align them within the front panel window e Slide the electronic assembly into the rear of the enc...

Страница 12: ...es Intrinsic Safety Division 1 or 2 Class I Group A B Group C Group D Zone 0 1 or 2 Class 1 Group IIC Group IIB Group IIA The FM entity parameters are similar to the ATEX parameters The intrinsically safe systems shown in this manual may therefore be used for installations in the USA providing the Zener barriers or galvanic isolators are FM Approved All installations must comply with BEKA associat...

Страница 13: ...13 ...

Страница 14: ...14 ...

Страница 15: ...15 ...

Страница 16: ...16 ...

Отзывы: