Any galvanic isolator certified EEx ia IIC by an
EEC approved body with output parameters equal
to or less than the maximum BA405C certified
input parameters may be used.

The maximum permitted cable parameters for the
loop should be calculated by subtracting Ci & Li for
the BA405C from the cable parameters specified
on the galvanic isolator certificate.

When designing the loop it is necessary to
establish that the supply voltage between terminals
1 & 3 of the BA405C set point station always
exceeds the minimum operating voltage shown in
section 4.1

4.3

Optional Backlights

The BA405C set point station can be supplied with
two different backlights. The loop powered
backlight produces green background illumination
enabling the display to be read at night or in poor
lighting conditions.  No additional power supply, IS
interface or field wiring are required, but the
minimum operating voltage drop of the set point
station is increased to 11.1V.

Alternatively, the separately powered backlight has
a bright orange output which enhances daylight
viewing, but it requires an additional IS interface
and field wiring.

4.3.1  Separately powered backlight

This backlight is segregated from the measuring
circuit and has been certified as a separate
intrinsically safe circuit

.

The maximum input safety parameters are

Maximum input

Ui

=

   28V dc

Ii

=

 159mA dc

Pi

=

 0.8W

Equivalent capacitance and inductance

Ci

=

   30nF

Li

=

0.01mH

Any Zener barrier or isolator certified EEx ia IIC by
an EEC approved body which has output
parameters equal to, or less than, the maximum
input parameters specified above may be used.
Most installations would use a 28V, 93mA 0.65W
(28V 300

) device as shown in Fig 4.

The display brilliance depends upon the current
flowing through the backlight which is determined
by the supply voltage and the end-to-end
resistance of the Zener barrier or output resistance
of the galvanic isolator.  Brilliance will not be
significantly reduced until the current falls below
20mA.

Fig 4 Separately powered backlight

The separately powered backlight requires a
minimum supply voltage of 14V, The backlight
current can be calculated from:

Backlight current =               Vsupply –14                

End-to-end resistance of barrier

#

#  Or output resistance of galvanic isolator

Two BA405C separately powered backlights may
be powered in parallel from a single 28V 300

Zener barrier or galvanic isolator, but the display
brilliance will be reduced.

4.3.2  Loop powered backlight

The loop powered backlight is connected in series
with, and powered by, the 4/20mA current from the
set point station This eliminates the need for a
separate Zener barrier or galvanic isolator and for
additional wiring, thus significantly reducing the
installation cost.

Fig 5  Loop powered backlight

Fig 5 shows how the loop powered backlight
should be connected in series with the set point
station. Any Zener barrier or galvanic isolator
certified EEx ia IIC by an EEC approved
certification body may be used providing the output
safety parameters do not exceed:

Содержание BA405C

Страница 1: ...BA405C intrinsically safe 2 wire 4 20mA manual set point station issue 6 Issue 6 17th November 2009 ...

Страница 2: ...n 5 1 Location 5 2 Installation procedure 5 3 EMC 6 Calibration 6 1 Internal display 6 1 1 Zero adjustment 6 1 2 Span adjustment 6 1 3 Decimal point 6 1 4 Reverse action 6 1 5 Calibration example 6 1 6 Over under range 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Customer comments 8 Accessories 8 ...

Страница 3: ...hanges in the supply voltage Caution The 4 20mA output should not be used for critical safety applications The 3 digit internal indicator can easily be calibrated on site to show the loop current in engineering units For example in an application where the BA405C is being used to adjust the set point of a speed controller the internal indicator may be calibrated to display the requested speed in R...

Страница 4: ...alent capacitance and inductance Ci 30nF Li 0 01mH 3 4 Zones Gas Groups and T rating The BA405C and both the optional display backlights have been certified as Group II category 1G apparatus EEx ia IIC T5 When powered via a compatable Zener barrier or galvanic isolator the BA405C manual set point station may be installed in Zone 0 explosive gas air mixture continuously present Zone 1 explosive gas...

Страница 5: ...ish that the maximum voltage drop caused by the manual set point station both Zener barriers the load and cable resistance is always less than the minimum supply voltage Fig 2 Typical application using barriers In this example Minimum operating voltage of BA405C 6 1V Maximum voltage drop caused by 28V 6 8V 93mA 0 65W Zener barrier 340Ω end to end resistance x 20mA Maximum voltage drop caused by 1 ...

Страница 6: ... 30nF Li 0 01mH Any Zener barrier or isolator certified EEx ia IIC by an EEC approved body which has output parameters equal to or less than the maximum input parameters specified above may be used Most installations would use a 28V 93mA 0 65W 28V 300Ω device as shown in Fig 4 The display brilliance depends upon the current flowing through the backlight which is determined by the supply voltage an...

Страница 7: ...lease refer to BEKA associates if high vibration is anticipated Fig 6 shows the enclosure dimensions and the recommended panel cut out sizes 5 2 Installation Procedure a Insert the BA405C set point station into the panel aperture from the front Ensure that the gasket is correctly positioned under the bezel b Fix two panel mounting clips to opposite sides of the instrument and tighten until the ind...

Страница 8: ...ed between 1000 and 1000 The zero potentiometer has two ranges 0 to 500 and 500 to 1000 Tthe polarity of the zero is defined by the position of the suppression elevation links Fig 9 shows the position of the zero links and zero potentiometer Suppression elevation links Elevation Positive zero 0 to 1000 or Suppression Negative zero 0 to 1000 Zero link 0 to 500 or 500 to 1000 6 1 2 Span adjustment S...

Страница 9: ...A dummy decimal point is required between the least two significant digits therefore the decimal point link should be placed in the 00 0 position Step 5 Adjust the BA405C front panel control until the output current measured by external ammeter is 4 000mA The zero potentiometer at the rear of the BA405C should then be adjusted until the BA405C displays 25 0 Step 6 Adjust the BA405C front panel con...

Страница 10: ...as clearance certificate is available If a BA405C fails after it has been functioning correctly the following procedure should be followed Symptom Cause Solution No loop Wiring or power Check wiring current supply fault and power supply Unstable Insufficient Check that voltage loop supply between terminals current voltage 1 3 is greater than 6 1 or 10V between terminals 1 13 if fitted with a loop ...

Страница 11: ...to the shaft Loosen the collet by turning the brass split screwhead anti clockwise and then carefully pull the control knob from the shaft c Pull the electronic assembly from the rear of the enclosure d Remove the blank scale card s and mark with the required legend Replace scale card s taking care to align them within the front panel window e Slide the electronic assembly into the rear of the enc...

Страница 12: ...es Intrinsic Safety Division 1 or 2 Class I Group A B Group C Group D Zone 0 1 or 2 Class 1 Group IIC Group IIB Group IIA The FM entity parameters are similar to the ATEX parameters The intrinsically safe systems shown in this manual may therefore be used for installations in the USA providing the Zener barriers or galvanic isolators are FM Approved All installations must comply with BEKA associat...

Страница 13: ...13 ...

Страница 14: ...14 ...

Страница 15: ...15 ...

Страница 16: ...16 ...

Отзывы: