Providing the BA377NE Timer or Clock is correctly
installed in an Ex n panel enclosure located in
Zone 2, the input terminals may be connected to a
certified sensor located in Zone 1 as shown in Fig 4.
The sensor should have Ex e or Ex d certification
permitting installation in Zone 1.

Intrinsically safe

Ex i certified sensors should not be used.

Fig 4  Connection to an Ex d or Ex e sensor in

                Zone 1.

3.2.1  Input switching threshold

For reliable totalisation the Timer or Clock pulse
input must fall below the lower threshold and rise
above the upper thresholds shown in the following
t

able.

Input transducer

Switching thresholds

Lower

Upper

Open collector

2k

10k

Voltage pulse

low

1.0V

3.0V

Voltage pulse

high

3.0V

10.0V

Magnetic pick-off

0mV

40mV peak

Proximity

detector

1.2mA

2.1mA

Switch

100

1000

Switch contact, proximity detector and open
collector sensors require energising which is
achieved by linking BA377NE terminals 3 and 4.

3.2.2  Switch contact input

Any mechanically or magnetically activated switch
contact located in Zone 2 or in the safe area may be
directly connected to the BA377NE pulse input
terminals 5 and 6, providing the sensor and
associated wiring can withstand a 500V rms
insulation test to earth. Most magnetically activated
reed relays comply with these requirements.  

The BA377NE contain a configurable debounce
circuit to prevent false triggering.   See section 6.5.6.

3.2.3  Open collector input

Open collector sensors located in Zone 2 or in the
safe area may be directly connected to input
terminals 5 & 6 providing the sensor and associated
wiring can withstand a 500V rms insulation test to
earth.

The BA377NE contain a configurable debounce
circuit to prevent false triggering.   See section 6.5.6.

3.2.4  2-wire proximity detector input

Most Zone 2 certified NAMUR 2-wire proximity
detectors may be directly connected to a BA377NE
input terminals 5 & 6 providing minimum operating
voltage is greater than 7.5V. The sensor and the
associated wiring should be able to withstand a
500V rms insulation test to earth.

The BA377NE contain a configurable debounce
circuit to prevent false triggering.   See section 6.5.6.

3.2.5  Magnetic pick-off input 

Magnetic pick-offs will usually have a low level ac
voltage output which a BA377NE Timer or Clock can
sense when configured for a

CoiL

input. The Timer

or Clock input terminals 5 and 6 may be connected
to any Zone 2 certified magnetic pick-off sensor
providing the output in normal operation is less than
30V which is the Ui of the BA377NE. The sensor
and associated wiring should be able to withstand a
500V rms insulation test to earth.

The BA377NE contain a configurable debounce
circuit to prevent false triggering.   See section 6.5.6.

3.2.6  Voltage pulse input

Two voltage pulse input ranges are selectable in the
BA377NE Timer or Clock configuration menu,

VoLt5

L

and

VoLt5 H

. The Timer or Clock input terminals

5 and 6 may be connected to any Zone 2 certified
voltage pulse, providing the output in normal
operation is equal to or less than 30V and the
sensor and associated wiring are able to withstand a
500V rms insulation test to earth.

The BA377NE contain a configurable debounce
circuit to prevent false triggering.   See section 6.5.6.

Содержание BA377NE

Страница 1: ...Issue 6 3rd July 2018 BA377NE Rugged one input Ex nA and Ex tc Timer or Clock Issue 6...

Страница 2: ...n functions 6 5 3 Instrument function FunCtion 6 5 4 Input inPut 6 5 5 Input type inP tYPE 6 5 6 debounce debounce 6 5 7 Lower display di5P 2 6 5 8 Starting stopping the Timer 5tAr5toP 6 5 9 Units of...

Страница 3: ...e 5YnC t 9 4 7 Control output 1 Optional oP1 9 4 8 Enable Control output 1 EnbL 9 4 9 On and off times oP 1 on 1 oP 1 off 1 oP 1 on 2 oP 1 off 2 9 4 10 Control output 2 Optional oP2 9 4 11 Enable cont...

Страница 4: ...4...

Страница 5: ...endixes to this manual The Ex nA and Ex tc certification of the instrument is unaffected by whether it is configured as a Timer or as a Clock 2 1 ATEX Ex nA certification Notified Body Intertek Testin...

Страница 6: ...5 Input terminals The BA377NE Timer or Clock has a single pair of pulse input terminals 5 and 6 that may be configured for use with different types of sensor For sensors that require energising to de...

Страница 7: ...equipment In addition to being able to be connected to other equipment in the safe area and in Zone 2 the BA377NE may also be connected to suitably protected and certified equipment located in Zone 1...

Страница 8: ...ng DIN rail mounted terminals incorporating a fuse with easily removable fuses which can be extracted to achieve isolation as shown in Fig 1 Clear identification of and easy access to the means of iso...

Страница 9: ...nnected to input terminals 5 6 providing the sensor and associated wiring can withstand a 500V rms insulation test to earth The BA377NE contain a configurable debounce circuit to prevent false trigger...

Страница 10: ...ngle pole control outputs that may be independently configured with normally open or normally closed outputs CAUTION Control outputs should not be used for critical safety applications such as a shut...

Страница 11: ...in the safe area Fig 6 Typical control output application Shown without recommended screened cables To comply with the requirements of EN 60079 14 Electrical installations design selection and erectio...

Страница 12: ...s 4 2 Installation Procedure a Cut the aperture specified in Fig 7 in the panel enclosure Ensure that the edges of aperture are de burred b Inspect the Timer or Clock s captive gasket and ensure that...

Страница 13: ...equested units of measurement if this information is not supplied when the instrument is ordered a blank card will be fitted A pack of self adhesive scale cards printed with common units of flow measu...

Страница 14: ...asurement specified when the instrument was ordered if the units are not specified a blank scale card will be fitted A pack of scale cards pre printed with common units of measurement is available as...

Страница 15: ...be accomplished via the front panel push buttons or by a remote contact A grand total time is maintained which can be viewed by operating the front panel push buttons It may be reset to zero from wit...

Страница 16: ...15 Shows in succession firmware version number instrument function elap5e and any output accessories that are fitted A Dual Control Outputs Access to configuration menu 6 3 Displays when configured as...

Страница 17: ...nning state to the Pause state by a stop event which could be an input or operation of the button Reset In this state the Timer is readied for operation The Timer is stopped and loaded with zero for t...

Страница 18: ...ughout this manual front panel push buttons are shown as and and legends displayed by the instrument are shown in a seven segment font just as they appear on the instrument e g inPut and Clr Gtot Acce...

Страница 19: ...ContACt Switch contact Energise input by linking terminals 3 4 See section 6 5 5 dEbounCE Defines the level of debounce applied to the input to prevent false functioning dEFAuLt HEAVY LiGHt See secti...

Страница 20: ...the display mode to 5Et t and r5t dela See section 6 5 15 Display Summary of function uP or dn Direction of count Defines whether the Timer times down from 5Et t to zero or times up from zero to the...

Страница 21: ...control output 1 See section 6 5 26 Display Summary of function CLr Gtot Resets grand total to zero This function resets the grand total which represents the total Timer run time from within the confi...

Страница 22: ...ice to return to the configuration menu or repeatedly press the or button until the required type of input is displayed and then press twice to return to the configuration menu One of following six ty...

Страница 23: ...at start of each period 02 11 Current Number of cycles cycle requested not shown number when cycle is continuously repeated LabEL Exactly the same as 5td but timer status i e CYCLE or dELAY is shown...

Страница 24: ...24...

Страница 25: ...25...

Страница 26: ...transfer control to the next digit When set as required enter the selection and return to the cycl cnt prompt in the sub menu by operating the button 6 5 14 Restart delay r5t dela This sub function d...

Страница 27: ...ming will start immediately Continue When power is restored the Timer will continue from where it stopped without any manual intervention To check or change the function select P fail from the configu...

Страница 28: ...guration example in section 7 2 of this manual illustrates the use of the control outputs Further examples can be found in Application Guide AG374 which is available on the BEKA website 6 5 22 Control...

Страница 29: ...A from the control output 1 sub menu and press which will reveal the existing delay time with one digit flashing The flashing digit can be adjusted using the or button and the button to move to the ne...

Страница 30: ...git which should be set to u When 5urE has been entered pressing the button will reset all the configuration functions and return the instrument to the display mode Note r5Et dEF does not reset the gr...

Страница 31: ...ch it stopped when the start button is operated Fig 15 Control of Ex nA solenoid valve in a hazardous area The required instrument configuration for this example are shown below Function Display Setti...

Страница 32: ...d Contact BEKA if code is lost 8 2 Fault finding after commissioning EN 60079 17 Electrical installations inspection and maintenance permits live maintenance in Zone 2 if a risk analysis demonstrates...

Страница 33: ...sociates or to our local agent for repair It is helpful if a brief description of the fault symptoms is provided 8 4 Routine maintenance The mechanical and electrical condition of the instrument shoul...

Страница 34: ...nt memory Following initialisation the instrument will display a flashing display which is a request for the local time to be entered The clock will not start to function until a display time has been...

Страница 35: ...ghout this manual push buttons are shown as and and legends displayed by the Clock are shown in a seven segment font as they appear on the instrument e g di5PLAY and CodE Access to the configuration m...

Страница 36: ...36...

Страница 37: ...rol output 1 Optional Control output 1 can turn on output closed and off output open twice in each twenty four hour period This function contains five sub function EnbL Enables output 1 and defines if...

Страница 38: ...time is entered the Clock will display a flashing 00 00 00 or 00 00 for 24 hour formats or A12 00 00 or A12 00 for 12 hour formats To adjust the clock set time select 5Et from the configuration menu...

Страница 39: ...n entered return to the configuration menu by pressing the button twice 9 4 10 Control output 2 Optional oP2 Control output 2 is an optional factory fitted output which can be configured to turn on ou...

Страница 40: ...the display mode may be protected by a four digit alphanumeric security code which must be entered to gain access Default security code 0000 allows unrestricted access With ACCd displayed press to en...

Страница 41: ...will then change the instrument to a Clock and return the display to FunCtion in the configuration menu Step 3 Select display format Using the or button select di5PLAY in the configuration menu and p...

Страница 42: ...cess to the configuration menu Using the and buttons select CodE from the configuration menu and press which will reveal 0000 with the first digit flashing This example requires the security code to b...

Страница 43: ...Zone 2 if a risk analysis demonstrates that this does not introduce an unacceptable risk The removal of covers opening of Ex n enclosure is permitted if this can be done without contaminating the int...

Страница 44: ...ncy should be chosen to suit the environmental conditions 11 5 Guarantee Instruments which fail within the guarantee period should be returned to BEKA associates or our local agent It is helpful if a...

Страница 45: ...A1 2 Special conditions for safe use in dust atmospheres The BA377NE ATEX Type Examination Certificate has an X suffix to show that special conditions for safe use are specified by the BA377NE Ex ic t...

Страница 46: ...nd both refer to equivalent standards Therefore the ATEX installation requirements specified in the main sections and in Appendix 1 of this manual also apply for IECEx installations but the local code...

Страница 47: ...fety parameters are the same as the ATEX and IECEx parameters the systems shown in sections 2 3 4 of this manual may therefore also be used for US and Canadian installations subject to compliance with...

Отзывы: