39
9.4.8
Enable Control output 1:
EnbL
This is a sub-function in the Control output 1 function
oP1
which allows output 1 to be enabled or disabled
without changing any of the
on
or
off
times and also
determines whether output 1 turns
on
and
off
once
or twice in each twenty four hour period.
Select
oP1
in the configuration menu and press
(
which will result in the
EnbL
prompt being displayed.
Pressing
(
again will enter the sub-function from
which one of the three options may be selected
using the
*
or
&
button:
Display
Control output 1
oFF
Control output 1 disabled
on : 1
Turns
on
&
off
once per 24 hours
on : 2
Turns
on
&
off
twice per 24 hours
When the required option is displayed operating
)
will enter the selection and return to the
EnbL
prompt
from which another sub-function may be selected if
control output 1 has not been disabled.
9.4.9
On
and
off
times:
oP 1 : on 1
;
oP 1 : off 1
oP 1 : on 2
;
oP 1 : off 2
The control output will have one or two
on
and
off
times depending upon whether control output 1 has
been configured to turn
on
and
off
once or twice in
each 24 hour period. - see 9.4.8.
All of the times are adjusted in the same way. To
adjust any of them select
oP1
from the configuration
menu and press
(
which will result in the
EnbL
prompt being displayed. The
*
or
&
button will
scroll through the sub-functions. Only
oP 1 : on 1
and
oP1 : oFF1
will be present if control output 1 has been
configured to switch
on
and
off
once in a 24 hour
period in the
EnbL
sub-function.
Select the required sub-function
oP1
:
on1
Time oP1 turns
on
first time
oP1
:
oFF1
Time oP1 turns
off
first time
oP1
:
on2
Time oP1 turns
on
second time
oP1
:
oFF2
Time oP1 turns
off
second time
When selected, pressing
(
will show the existing
time with the hours flashing.
Using the
*
or
&
button adjust the hours and then press
(
to
transfer control to the minutes display, pressing
(
again will transfer control to the seconds display.
When the time has been set as required press
)
to
return to the sub-menu from which another
on
and
off
times may be selected for adjustment. When all
the
on
and
off
times have been entered, return to the
configuration menu by pressing the
)
button twice.
9.4.10 Control output 2 (Optional): oP2
Control output 2 is an optional factory fitted output
which can be configured to turn
on
(output closed)
and
off
(output open) twice in each twenty-four hour
period. The control output status is shown by the 2
control output display annunciator.
Function
oP2
contains a sub-menu with five sub-
functions:
EnbL
Number of times output 2
turns
on
&
off
in 24 hours.
oP 2
:
on 1
First time when oP 2 turns
on
(closes)
oP 2
:
oFF 1
First time when oP 2 turns
off
(opens)
oP 2
:
on 2
Second time when oP 2 turns
on
(closes)
oP 2
:
oFF 2
Second time when oP 2 turns
off
(opens)
To check or change the function of Control output 2
select
oP2
from the configuration menu and press
(
which will reveal the first sub-funtion
EnbL.
9.4.11 Enable control output 2:
EnbL
This is a sub-function in the Control output 2 function
oP2
which allows output 2 to be enabled or disabled
without changing any of the
on
or
off
times and also
determines whether output 2 turns
on
and
off
once
or twice in each twenty four hour period.Select
oP2
in the configuration menu and press
(
which will
result in the
EnbL
prompt being displayed. Pressing
(
again will enter the sub-function from which one
of the three options may be selected using the
*
or
&
button:
Display
Control output 2
oFF
Control output 2 disabled
on : 1
Turns
on
&
off
once per 24 hours
on : 2
Turns
on
&
off
twice per 24 hours
When the required option is displayed operating
)
will enter the selection and return to the
EnbL
prompt
from which another sub-function may be selected if
control output 2 has not been disabled.
9.4.12
On
and
off
times:
oP2 : on 1
;
oP2 : off 1
oP2 : on 2
;
oP2 : off 2
The control output will have one or two
on
and
off
times depending upon whether control output 2 has
been configured to turn
on
and
off
once or twice in
each 24 hour period. - see 9.4.11.
All of the times are adjusted in the same way. To
adjust any of them select
oP2
from the configuration
menu and press
(
which will result in the EnbL
prompt being displayed. The
*
or
&
button will
scroll through the sub-functions. Only
oP2 : on1
and
oP2 : oFF1
will be present if control output 2 has been
configured to switch
on
and
off
once in a 24 hour
period in the
EnbL
sub-function.