6.12  Total scale factor:   

5CALE

 

.

 

t

5CALE

 

.

 

 is  a  dividing  factor  adjustable  between

0.0001  and  99999  that  enables  the  total  to  be
displayed  in  engineering  units.    e.g.  if  one  input
pulse  represents  1  centimetre  of  dispensed  cable
and the total display is required in metres,  

5CALE

 

.

 

t

should  be  set  to  100.0  which  is  the  number  of
centimetres  in  a  metre.      If  a  display  of  the  total
number of input pulses is required,  

5CALE

 

.

 

t

 should

be set to 1.0.  The total display is independent of the
rate display.

To  check  or  change  the  total  scale  factor  select

5CALE

 

.

 

t

 from the configuration menu and press 

(

which  will  reveal  the  existing  value  with  one  digit
flashing.    The  value  of  the  flashing  digit  may  be
changed by pressing the  

&

 or  

*

 button.  When

this digit has been adjusted as required, pressing 

(

will transfer control to the next digit.  When all the
digits have been adjusted pressing  

(

 will transfer

control to the decimal point that may be positioned
between  any  of  the  digits,  or  may  be  omitted  by
moving  it  to  the  right of the  least  significant  digit.
When the total scale factor has been entered, press

(

   to  return  to  the   

5CALE

 

.

 

T  

 prompt  in  the

configuration menu. 

Note:

Adjustment  of  

5cale

 

.

 

t

  will  disable  the

following  ouputs  which  must  be  re-enabled
after the adjustment is complete:

Optional Pulse output

Optional Alarm outputs.

Optional 4/20mA output.

6.13 Rate scale factor:   

5CALE

 

.

 

r

5CALE

 

.

 

r

  is  a  dividing  factor  adjustable  between

0.0001 and 99999 that enables the rate display to be
in  engineering  units.    e.g.  if  one  input  pulse
represents 2 pump strokes and the rate display is
required in pump strokes, 

5CALE

 

.

 

r

 should be set to

2.0.      If  just  the  rate  of  input  pulses  is  required,

5CALE

 

.

 

r

  should be set to 1.0.   The rate display is

independent of the total display.

The units of the rate display are counts per unit of
time.    The  unit  of  time  is  the  timebase  of  the
instrument  which  is  determined  by  

t-bA5E

described in section 6.14.

To  check  or  change  the  rate  scale  factor  select

5CALE

 

.

 

r

 from the configuration menu and press 

(

which  will  reveal  the  existing  value  with  one  digit
flashing.    The  value  of  the  flashing  digit  may  be
adjusted by pressing the 

&

 or 

*

 button.

When  this  digit  has  been  adjusted  as  required,
pressing  

(

  will  transfer  control  to  the  next  digit.

When  all  the  digits  have  been  adjusted  pressing

(

 will transfer control to the decimal point that may

be positioned between any of the digits, or may be
omitted  by  moving  it  to  the  right  of  the  least
significant digit.  When the required rate scale factor
has been entered, press 

)

 to return to the 

5CALE

 

.

 

r

prompt in the configuration menu.

Note:

Adjustment   of   

5cale

 

.

 

R  

 will   disable   the

following  outputs  which  must  be  re-enabled
after the adjustment is complete:

Optional Pulse output

Optional Alarm outputs.

Optional 4/20mA output.

6.14  Timebase:  

t-bA5E

The timebase multiplies the rate display by 1, 60 or
3,600  depending  upon  whether  the  BA367NE
Counter is required to display rate per second, per
minute or per hour.    See Fig 10.

To  check  or  change  the  timebase,  select  

t-bA5E

from the configuration menu and press 

(

 

which will

reveal the current setting.   Pressing the  

&

 or  

*

button will scroll through the three options:

tb-1

for pulses / second

tb-60

for pulses / minute

tb-3600

for pulses / hour

When the required multiplier is displayed press  

)

to return to the  

t-bA5E

 prompt in the configuration

menu.

6.15   Display filter:   

FiLtEr

The  digital  display  filter  has  two  independent
adjustable  parameters  enabling  the  rate  display
response  to  be  tailored  for  optimum  performance.
The filter parameters are controlled by a two digit
number.  The first digit defines the amount of filtering
applied to the display as shown below.

First digit

Filter time constant

Seconds

0X

              0

1X

              1.3

2X

              4.3

3X

              6.5

4X

              8.7

5X

            11.3

6X

            15.7

7X

            20.9

8X

            25.2

9X

            31.5

20

Содержание BA364G

Страница 1: ...Issue 7 9th July 2019 BA367NE One input Ex nA and Ex tc Counter Issue 7 ...

Страница 2: ... type inP tYPE 6 6 Input debounce dEbouncE 6 7 Input pulse counting edge Cnt EdgE 6 8 Display update interval uPdAtE 6 9 Upper display di5P 1 6 10 Lower display di5P 2 6 11 Position of the decimal points dP 6 12 Total scale factor 5CALE t 6 13 Rate scale factor 5CALE r 6 14 Timebase t bA5E 6 15 Display filter FiLtEr 6 16 Direction of count uP or dn 6 17 Reset value CLr VAL 6 18 Local reset LoC CLr...

Страница 3: ...play mode 9 4 Pulse Output 9 4 1 Ex nA certification 9 4 2 Pulse output configuration PuL5E oP 9 4 3 Enable pulse output EnbL 9 4 4 Source of pulse output 5ourCE 9 4 5 Divide output pulse frequency diVidE 9 4 6 Output pulse width durAtion 9 4 7 Pulse storage 9 5 4 20mA output 9 5 1 Ex nA certification 9 5 2 Configuration 9 5 3 4 20mA output 4 20 oP 9 5 4 Enable 4 20mA output EnbL 9 5 5 Select rate...

Страница 4: ...ounter initialisation is performed After a short delay the following display sequence occurs All segments of the display are activated Counter starts functioning using the configuration information stored in the instrument s permanent memory Unless total and grand total displays have been reset to zero new pulses will be added to the existing totals 2 2 Controls The BA367NE Counter is controlled a...

Страница 5: ...dicator of the display rotates for two seconds each time an input pulse is received on either input Appears to rotate continuously when combined input frequency on both inputs exceeds 0 5Hz Reset Activated while the total display annunciator is being reset via the front panel push buttons or the external reset terminals Rate Identifies rate display annunciator Total Identifies total display annunc...

Страница 6: ...closure located in Zone 2 When connected to a suitable system and correctly mounted in a panel enclosure complying with the requirements for Type of protection n the panel enclosure containing the BA367NE Counter may be installed in Zone 2 explosive gas air mixture not likely to occur and if it does will only exist for a short time Be used with gases in groups Group A propane Group B ethylene Grou...

Страница 7: ... Ex e Ex p and Ex d protected apparatus located in Zone 2 Because the BA367NE is not certified intrinsically safe it should not be connected to an intrinsically safe system BEKA Application Guide AG310 Guide for Installation of extra low voltage d c Ex nA instrumentation which can be downloaded from www beka co uk contains explanations and recommendations for the installation of Ex nA equipment In...

Страница 8: ...nted terminals incorporating an easily removable fuse which can be extracted to achieve isolation as shown in Fig 2 Clear identification of and easy access to the means of isolation is essential for their effective use It is also necessary to ensure that the maintenance procedure makes sure that unauthorised re closure of the switches does not occur It is not considered necessary to have a means o...

Страница 9: ... 6 providing the minimum operating voltage of the proximity detector is greater than 7 5V The sensor and the associated wiring should be able to withstand a 500V rms insulation test to earth The BA367NE contain a configurable debounce circuit to prevent false triggering See section 6 6 4 2 5 Magnetic pick off input Magnetic pick off sensors usually have a low level ac voltage output which a BA367N...

Страница 10: ... the edges of aperture are de burred b Inspect the Counter s captive gasket and ensure that it is not damaged before inserting it into the panel enclosure aperture c If the enclosure panel is less than 1 0mm thick or is non metallic an optional BEKA stainless steel support plate should be slid over the rear of the indicator before the panel clamps are fitted to evenly distribute the clamping force...

Страница 11: ...scale card showing the requested units of measurement if this information is not supplied when the instrument is ordered a blank card will be fitted A pack of self adhesive scale cards printed with common units of measurement is available as an accessory from BEKA associates Custom printed scale cards can also be supplied To change a scale card unclip the protruding end of the flexible strip by ge...

Страница 12: ...n uP or dn uP Clear value clr val 00000000 Local clear Local total reset Clr tot oFF Local grand total reset Clr Gtot oFF Security code CodE 0000 Note While the instrument is being configured counting continues so that any input pulses occurring during this time are recorded 6 1 Configuration structure Fig 10 shows the calibration structure of the BA367NE Counter The pulse input is passed to the 5...

Страница 13: ... 5AVE while the new information is stored in permanent memory If after accessing the configuration menu the interval between operating any front panel push button exceeds one minute the BA367NE will automatically return to the display mode and any configuration changes will not be stored in permanent memory When making changes to multiple configuration functions it is therefore sensible to occasio...

Страница 14: ...ngineering units 5CALE r may be adjusted between 0 0001 and 99999 e g if one pulse represents 2 pump strokes and the rate display is required in pump strokes 5CALE r should be set to 2 0 The rate display is independent of the total display See section 6 13 Display Summary of function t bA5E Timebase Selectable multiplier allowing rate to be displayed in units per second per minute or per hour Sele...

Страница 15: ...al can not be restored See section 6 20 Clr Gtot Resets grand total to zero from within configuration menu This function resets the grand total to zero from within the configuration menu when CLr YE5 is selected Note Once reset the grand total can not be recovered See section 6 21 Display Summary of function CodE Access code Defines a four digit alphanumeric code that must be entered to gain acces...

Страница 16: ...16 ...

Страница 17: ...17 ...

Страница 18: ...the input miscounting when the input pulse has noisy edges such as those resulting from a mechanical contact closing and bouncing Three levels of protection may be selected The amount of debounce applied depends upon the type of Counter input that has been selected in the inP tYPE function Select inPut in the configuration menu and press which will reveal the inP tYPE prompt press the or button to...

Страница 19: ...eturn to the configuration menu 6 10 Lower display di5P 2 This function turns the lower display on or off When turned off the BA367NE will only have one eight digit display which may be configured in the di5P 1 function to show the total count or rate To check the setting for the lower display select di5P 2 from the configuration menu and press that will reveal if the lower display is on or oFF Th...

Страница 20: ...e counts per unit of time The unit of time is the timebase of the instrument which is determined by t bA5E described in section 6 14 To check or change the rate scale factor select 5CALE r from the configuration menu and press which will reveal the existing value with one digit flashing The value of the flashing digit may be adjusted by pressing the or button When this digit has been adjusted as r...

Страница 21: ...ount uP or dn This function defines whether input pulses increment or decrement the total display i e whether the BA367NE is an up counter or a down counter When configured as a down counter with a non zero number entered for the reset value CLr VAL the BA367NE will count down from the reset value to zero To check or change the count direction select uP or dn from the configuration menu and press ...

Страница 22: ...the LoC CLr prompt in the configuration menu Note Once reset the grand total can not be recovered 6 21 Reset grand total from configuration menu Clr Gtot The grand total is a separate sixteen digit counter which is incremented or decremented in parallel with the total display but is not reset when the total display is reset The grand total may be viewed in the display mode in two eight digit secti...

Страница 23: ...f strokes that a reciprocating pump makes in thousands of strokes on the larger upper display and to show the speed of pumping in strokes per hour on the lower display The stroke sensor is a proximity detector which produces four pulses per stroke The total display is only to be resettable by an external contact not from the BA367NE Counter front panel Similarly the grand total is not to be resett...

Страница 24: ...mple the proximity detector produce four pulses per pump stroke The BA367NE is required to display thousands of pump strokes therefore the total scale factor 5CALE t should be set to 4 x 1000 4000 Select 5CALE t from the configuration menu and press to view the current value with one digit flashing Use the or button to adjust the flashing digit and the button to transfer control to the next digit ...

Страница 25: ...ation menu and press which will reveal the existing security code with the first digit flashing Enter the new code 1209 using the or button to adjust the flashing digit and the button to transfer control to the next digit When the new code has been entered press to return to the configuration menu Step 12 Return to the display mode Following completion of configuration return the BA367NE to the di...

Страница 26: ... Optional alarms do not function Alarms have been disabled following configuration change Re enable both alarms 8 2 Fault finding after commissioning EN 60079 17 Electrical installations inspection and maintenance permits live maintenance in Zone 2 if a risk analysis demonstrates that this does not introduce an unacceptable risk The removal of covers opening of Ex n enclosure is permitted if this ...

Страница 27: ...nmental conditions 8 5 Guarantee Instruments which fail within the guarantee period should be returned to BEKA associates or our local agent It is helpful if a brief description of the fault symptoms is provided 8 6 Customer comments BEKA associates is always pleased to receive comments from customers about our products and services All communications are acknowledged and whenever possible suggest...

Страница 28: ...refore be chosen for the alarm condition Alarm annunciators on the instrument display indicate the status of each alarm If an alarm delay or silence time has been selected the annunciator will flash during the delay or silence period The BA367NE internal counters are up dated and compared with the alarm setpoint twice per second irrespective of the display update time selected This may result in a...

Страница 29: ...o alarm AL1 The following table summarises each of the alarm configuration functions and includes a cross reference to more detailed information Again only the functions on alarm AL1 are listed Display Summary of function EnbL Alarm enable Enables or disables the alarm without changing the alarm parameters See section 9 3 4 tYPE Type of alarm Defines whether the alarm operates on the rate or total...

Страница 30: ... return to the Hi Lo prompt in the alarm sub menu 9 3 8 Alarm output status no nC Each single pole alarm output may be open or closed in the non alarm condition When the BA367NE power supply is turned off or disconnected the alarm output s will open irrespective of whether normally open or normally closed outputs have been selected Therefore when designing an alarm system normally closed nc should...

Страница 31: ...on After an alarm has occurred operating the button will cause the alarm output to revert to the non alarm condition for the programmed alarm silence time When an alarm is silenced by operating the push button the Counter s alarm annunciator will flash until the silence time expires To adjust the alarm silence time select 5iL using the or push button in the selected alarm sub menu and press which ...

Страница 32: ... the AC5P sub menu and press which will cause the Counter to display 0000 with one digit flashing The flashing digit may be adjusted using the or push button when set as required operating the button will transfer control to the next digit When all the digits have been adjusted press twice to return to the AC5p prompt in the configuration menu The revised security code will be activated when the C...

Страница 33: ...e to another BA367NE Counter the pulse output terminals may be directly connected to the input terminals of the second instrument as shown in Fig 16 alternatively the second instrument may be located in the safe area The second Counter should be configured for an open collector input Fig 16 Pulse retransmission to another BEKA E Ex nA instrument A voltage output pulse can be generated as shown in ...

Страница 34: ...unted terminals incorporating a fuse which can easily be removed as shown in Fig 2 to provide isolation Clear identification of and easy access to the means of isolation is essential for their effective use It is also necessary to ensure that the maintenance procedure makes sure that unauthorised re closure of the switches does not occur It is not considered necessary to have a means of isolation ...

Страница 35: ... to followed by the button to return to diVidE prompt in the sub menu Note This function only appears in the pulse output sub menu when 5CALEd is selected in the 5ource sub function See 9 4 4 9 4 6 Output pulse width durAtion When 5CALEd is selected in the 5ource sub function 9 4 4 the output pulse width is defined by this function One of following millisecond pulse widths may be selected 0 1 0 5 ...

Страница 36: ...mply with the requirements of EN 60079 14 Electrical installations design selection and erection each of the wires entering the hazardous area should be individually fused and contain a means of isolation These two requirements may be satisfied by installing DIN rail mounted terminals incorporating a fuse which can easily be opened as shown in Fig 2 to provide isolation Clear identification of and...

Страница 37: ...tput sub menu and press to reveal the existing setting totAL or rAtE The function can be changed by pressing the or push button followed by the button to return to the 4 20tYPE prompt in the sub menu 9 5 6 Display which corresponds to 4mA output 4 000 The Counter display which corresponds to a 4 000mA output current is defined by this function Using the or push button select 4 000 in the 4 20mA ou...

Страница 38: ...d in the main section of this instruction manual all BA367NE Counters have ATEX dust ignition protection by enclosure certification Ex tc permitting installation in combustible dust atmospheres The front panel push button switches are non incendive and have been certified intrinsically safe Ex ic without the need for Zener barriers or galvanic isolators This appendix describes ATEX installations i...

Страница 39: ...nspections depends upon environmental conditions Removal of flammable dust should be performed with care to avoid creating a dust cloud Appendix 2 IECEx certification Appendix 2 IECEx certification A2 0 The IECEx Certification Scheme IECEx is a global certification scheme for explosion protected products which aims to harmonise international certification standards For additional information about...

Страница 40: ...L safety parameters are the same as the ATEX and IECEx parameters the systems shown in sections 3 4 and 5 of this manual may therefore also be used for US and Canadian installations subject to complying with the local codes of practice ETL and cETL codes CL I Zone 2 AEx nA ic IIC T5 Gc US gas Zone cert Zone 22 AEx ic tc IIIC T80ºC Dc US dust Zone cert Ex nA ic IIC T5 Gc Canadian gas Zone cert Ex i...

Отзывы: