e.g.  An Rate Totaliser with a high alarm set at 9000
and an alarm delay of 30 seconds will perform as
follows:

The alarm annunciator will start to flash when an
increasing rate display equals 9000, but the alarm
output will not be activated until the alarm condition
has existed continuously for 30 seconds.  When the
alarm output is activated, the alarm annunciator will
stop flashing and become permanently activated.

If  the  ‘FL5H’  function,  which  flashes  the  Rate
Totaliser display when an alarm occurs, has been
enabled, it will not start to function until the alarm
output is activated.  
See section 10.3.12

10.3.11  Alarm silence time:   5iL

This function is primarily intended for use in small
installations where the alarm output directly operates
an alarm annunciator such as a sounder or beacon.
When  the  alarm  silence  time,  which  is  adjustable
between   0   and   3600   seconds   in   1   second
increments, is set to any figure other than zero, the

P

  push-button  becomes  an  alarm  accept  button.

After an alarm has occurred, operating the 

P

 button

will cause the alarm output to revert to the non-alarm
condition for the programmed alarm silence time.  If
the  alarm  condition  still  exists  at  the  end  of  the
silence  time,  the  alarm  output  will  be  reactivated.
During  the  silence  time  the  Rate  Totaliser  alarm
annunciator will flash until the silence time expires or
the alarm is cleared. 

If  the  ‘FL5H’  function,  which  flashes  the  Rate
Totaliser display when an alarm occurs has been
enabled, it will only function when the alarm output
is  activated,  not  during  the  silence  time.    See
section 10.3.12

To adjust the alarm silence time select '5iL' from the
alarm  configuration  menu  and  press  

P

 which  will

reveal the existing silence time.  The flashing digit of
the silence time can be adjusted using the 

 and 

push buttons, and the  

P

 button to move control to

the other digits.  When the required silence time has
been entered press 

E

 

to return to the alarm menu.

10.3.12 Flash display when alarm occurs

 

‘FL5H’

In  addition  to  the  two  alarm  annunciators  on  the
Rate Totaliser display which show the status of both
alarms,  this  function  provides  an  even  more
conspicuous indication that an alarm condition has
occurred.    

When enabled, the rate or total display depending
upon  which  has  caused  the  alarm,  alternates
between   the   numerical   value   and   the   alarm
reference, ‘ALr1’ or ‘ALr2’ when the alarm output is
activated.  If both alarm outputs are activated by one

variable,  the  display  alternates  between  the
numerical value and ‘Alr1-2’.

To enable or disable the function select 'FL5H' from
the alarm menu and press  

P

 which will reveal the

current  setting.    The  function  can  be  changed  by
pressing the 

 or 

 button followed by the 

E

 button

to return to the alarm menu.

10.3.13  Access setpoint in display mode:  

         AC5P

This  function  enables  a  separate  menu  providing
access to the alarm setpoints from the display mode
by  simultaneously  operating  the  

P

 and  

 push

buttons.  An operator can therefore adjust the alarm
setpoints without having access to the Rate Totaliser
configuration  menu.    Protection  against  accidental
adjustment of the setpoints when the Rate Totaliser
is  in  the  display  mode  is  provided  by  a  separate
security code.

This direct setpoint access menu is enabled and the
separate  security  code  entered  from  the  'AC5P'
function in the alarm configuration menu as shown in
Fig  14.    To  change  the  menu  parameters  select
'AC5P'  from  the  configuration  menu  and  press  

P

which will display the enable prompt 'EnbL'.  Press 

P

again to reveal if the direct access menu is 'on' or
'oFF'.  The 

 or  

 button  will  toggle  the display

between the two conditions.  

If 'oFF' is selected, the operator will not have access
to the setpoints from the display mode.  Return to
the 'AC5P' prompt in the main menu by pressing

 

E

twice.  

If   'on'   is   selected,   the   operator   will   have   direct
access to the alarm setpoints from the display mode
via a separate optional security code.   To define this
four digit security code press 

P

 to return to the 'Enbl'

prompt followed by the 

 or 

 button to select the

access code prompt 'ACCd'.   Pressing 

P

 

will reveal

the current security code.   Each digit of the code
may be changed by operating the 

 and 

 push

buttons, and the 

P

 

button to move control to the next

digit.  When the required code has been entered,
press  

E

 twice to return to the 'AC5P' prompt in the

configuration menu.

Default  code  0000  will  disable  the  security  code
allowing direct access to the setpoints in the display
mode  by  pressing  the

 

P

 

and  

 buttons

simultaneously.    Unless  otherwise  requested  new
instruments  with  alarms  are  supplied  with  this
function disabled and the security code set to 0000.

33

Содержание BA354NE

Страница 1: ...Issue 3 3rd July 2014 BA354NE Type nA 4 20mA loop powered field mounting Rate Totaliser Issue 3...

Страница 2: ...to a new indicator 7 2 Lineariser calibration using internal reference 7 2 1 Example Adding break points to a new indicator 7 3 Lineariser error message 7 4 Under and over range 7 5 Lineariser default...

Страница 3: ...strument The voltage developed across R1 which is proportional to the 4 20mA input current provides the input signal for the analogue to digital converter Each time a 4 20mA current is applied to the...

Страница 4: ...n clear the grand total and Gt CLrd will be displayed to confirm the operation The instrument will then automatically return to the operating mode Selectable function in the configuration menu See sec...

Страница 5: ...TEX installations in explosive gas atmospheres conforming with EN60079 14 Electrical Installations in Hazardous Areas When designing systems for installation outside the UK the local Code of Practice...

Страница 6: ...uit that defines the voltage developed between the input terminals 1 and 3 therefore the ATEX certificate does not specify a maximum safety input voltage Ui 3 4 Reset terminals The input safety parame...

Страница 7: ...ous area should be individually fused and contain a means of isolation However in practice instrumentation energised by a current limited power supply or instrument that can be switched off is often c...

Страница 8: ...0V rms insulation test for one minute The switch button must comply with the electrostatic requirements specified by Clause 7 of EN60079 0 and material composition defined in Clause 8 If the totaliser...

Страница 9: ...ded GRP enclosure If this enclosure is not bolted to an earthed post or structure the earth terminal should be connected to the plant potential equalising conductor The enclosure is fitted with a bond...

Страница 10: ...rised using the square root extractor or the 16 segment lineariser which are selectable in the instrument s FunC sub menu The rate display may then be calibrated using the CAL or 5Et functions to show...

Страница 11: ...e entered using the and push buttons and the P button to move control to the next digit When the correct four digit code has been entered pressing E will cause the first parameter FunC to be displayed...

Страница 12: ...on or oFF See section 6 8 dP Decimal points Positions the decimal point in the rAtE and totAL displays See section 6 9 Display Summary of function CAL Calibration of the rate display using an external...

Страница 13: ...nd Gt rE5Et t rE5Et enables the total display to be reset to zero when and push buttons are operated simultaneously for more than 2 seconds Gt rE5Et enables the grand total to be reset to zero when E...

Страница 14: ...14...

Страница 15: ...arity with bi directional flow Use of the lineariser is described in section 7 of this instruction manual 6 5 Display resolution rE5n This function defines the resolution of the least significant disp...

Страница 16: ...y and identify the lower display variable but on the larger upper display The position of the decimal point can be positioned in the same way by operating the and push buttons when set as required ent...

Страница 17: ...s been activated see section 6 17 To zero the grand total from within the configuration menu select Clr Gtot and press P which will cause the instrument to display Clr no Press the or button until CLr...

Страница 18: ...low rates which over long periods may result in significant totalisation errors the BA354NE rate display can be conditioned to stop totalisation when the flow rate falls below a specified clip off thr...

Страница 19: ...Rate Totaliser is returned to the display mode Please contact BEKA associates sales department if the security code is lost 6 19 Reset to factory defaults r5Et This function enables the Rate Totaliser...

Страница 20: ...ineariser calibration using an external current source This method allows direct calibration of the lineariser with an external current source and is the preferred method when traceability is required...

Страница 21: ...21...

Страница 22: ...llowing break point 7 1 1 Example Adding break points to a new Rate Totaliser When adding break points to a new Rate Totaliser or to a lineariser following resetting to the factory defaults using the...

Страница 23: ...e E button The corresponding rate display at each of the break points can now be defined using the diSP sub function Using the and buttons select the diSP sub function and press P which will reveal th...

Страница 24: ...ither the root extractor or the lineariser are required The standard linear relationship should therefore be selected With FunC displayed press P which will reveal the existing function Using the or b...

Страница 25: ...the totaliser scaling factor In this example the rate display is in litres per minute but the total display is required in cubic metres 5CALE t Units of rate display Units of total display There are 1...

Страница 26: ...and total flow in cubic metres with a resolution of 0 1 cubic metres Total is to be shown on the upper large display and rate on the lower smaller display Totalisation is to occur for flow rates betw...

Страница 27: ...ed by risk analysis or when there is no risk of a flammable atmosphere being present If an Rate Totaliser fails after it has been functioning correctly follow the procedure shown in section 9 1 If thi...

Страница 28: ...of the existing escutcheon Do not remove the original escutcheon The BA354NE Rate Totaliser can also be supplied with a blank or custom laser engraved stainless steel plate secured by two screws to th...

Страница 29: ...dc Ii 200mA This allows each alarm output to switch any dc circuit providing that in normal operation the maximum supply voltage is not greater than 30V and the switched current is not greater than 2...

Страница 30: ...30...

Страница 31: ...ted when the selected display rate or total equals the setpoint See section 10 3 6 Hi Lo Alarm function Defines the alarm function as High or Low See section 10 3 7 no nC Normally open or normally clo...

Страница 32: ...y pressing the or button followed by the E button to return to the alarm menu 10 3 8 Alarm output status no nC Configures the solid state alarm output to be open no or to be closed nC in the non alarm...

Страница 33: ...rate or total display depending upon which has caused the alarm alternates between the numerical value and the alarm reference ALr1 or ALr2 when the alarm output is activated If both alarm outputs ar...

Страница 34: ...5Px1 or 5Px2 prompt from which the other setpoint may be selected or the Rate Totaliser may be returned to the display mode by pressing E again Notes 1 With the Rate Totaliser in the display mode dire...

Страница 35: ...Separately powered backlight The separately powered backlight is a current sink which will draw a constant 35mA when the supply voltage is equal to or greater than 11V At lower supply voltages the ba...

Страница 36: ...A392D Stainless steel bracket secured by two worm drive hose clips Will clamp to any vertical or horizontal pipe with an outside diameter between 60 and 80mm BA393 Heavy duty stainless steel bracket s...

Страница 37: ...2 flammable gas atmosheres may also be used for Zone 22 combustible dust applications The Rate Totaliser should be located where the minimum amount of dust will accumulate on the enclosure and the in...

Страница 38: ...ified operating temperature of the BA354NE is 20 to 70 C At temperatures below 20 C the instrument will continue to totalise but the display will not function The specified gas and dust safety paramet...

Отзывы: