9.  MAINTENANCE

9.1 Fault finding during commissioning

If  an  Rate  Totaliser  fails  to  function  during
commissioning  the  following  procedure  should  be
followed:

Symptom

Cause

Solution

No display

Incorrect wiring

Check wiring

There should be

0.6 to 1.2V

between terminals

1 & 3 with terminal

1 positive.

With an optional

loop powered

backlight, there

should be 3.4 to

5V between

terminals 1 & 13

with terminal 1

positive.

No display

0V between

terminals 1 & 3.

Incorrect wiring

or no power

supply

Check supply

voltage and

voltage drop

caused by all the

instruments in the

loop.

Rate display

showing 

-99999 or 99999

with all decimal

points flashing

Over-range

The rate display

has been

incorrectly

calibrated & is

trying to display a

number outside

the range

 –99999 to 99999.

Recalibrate rate

display.

Total display

showing 

-9999999 or

99999999 with all

decimal points

flashing

Over-range

Reset total display

to zero.

Unstable display

4/20mA input is

noisy.

Eliminate ripple on

4/20mA power

supply and/or

decrease Rate

Totaliser

resolution.

Unable to enter

configuration

menu.

Incorrect

security code

entered.

Enter correct

security code, or

contact BEKA if

the code has been

lost.

9.2  Fault finding after commissioning

ENSURE PLANT SAFETY BEFORE

STARTING MAINTENANCE

Live  maintenance  within  the  hazardous
area should only be performed when it is
permitted by risk analysis or when there is
no risk of a flammable atmosphere being
present.

If an Rate Totaliser fails after it has been functioning
correctly follow the procedure shown in section 9.1.
If this does not reveal the cause of the fault, it is
recommended that the instrument is replaced.

9.3  Servicing

All  BA354NE  loop  powered  Rate  Totalisers  are
interchangeable  if  the  required  optional  backlight
and  alarms  are  fitted.    A  single  spare  instrument
may  quickly  be  recalibrated  to  replace  any
instrument  that is  damaged  or  fails.     No  attempt
should be made to repair instruments at component
level.
 

We recommend that faulty instruments are
returned  to  BEKA  associates  or  to  your
local BEKA agent for repair.

9.4 Routine maintenance

Routine  maintenance  should  comply  with  the
recommendations  contained  in  BS  EN  6007-17
‘Electrical  Installations  Inspections  and
Maintenance’.    The  mechanical  condition  of  the
instrument  and  electrical  calibration  should  be
regularly checked. The interval between inspections
depends  upon  environmental  conditions.    We
recommend  that  initially  instrument  calibration
should be checked annually.

9.5  Guarantee

Rate  Totalisers  which  fail  within  the  guarantee
period should be returned to BEKA associates or our
local agent.  It is helpful if a brief description of the
fault symptoms is provided.

9.6  Customer comments

BEKA  associates  is  always  pleased  to  receive
comments from customers about our products and
services.    All  communications  are  acknowledged
and  whenever  possible,  suggestions  are
implemented.

27

Содержание BA354NE

Страница 1: ...Issue 3 3rd July 2014 BA354NE Type nA 4 20mA loop powered field mounting Rate Totaliser Issue 3...

Страница 2: ...to a new indicator 7 2 Lineariser calibration using internal reference 7 2 1 Example Adding break points to a new indicator 7 3 Lineariser error message 7 4 Under and over range 7 5 Lineariser default...

Страница 3: ...strument The voltage developed across R1 which is proportional to the 4 20mA input current provides the input signal for the analogue to digital converter Each time a 4 20mA current is applied to the...

Страница 4: ...n clear the grand total and Gt CLrd will be displayed to confirm the operation The instrument will then automatically return to the operating mode Selectable function in the configuration menu See sec...

Страница 5: ...TEX installations in explosive gas atmospheres conforming with EN60079 14 Electrical Installations in Hazardous Areas When designing systems for installation outside the UK the local Code of Practice...

Страница 6: ...uit that defines the voltage developed between the input terminals 1 and 3 therefore the ATEX certificate does not specify a maximum safety input voltage Ui 3 4 Reset terminals The input safety parame...

Страница 7: ...ous area should be individually fused and contain a means of isolation However in practice instrumentation energised by a current limited power supply or instrument that can be switched off is often c...

Страница 8: ...0V rms insulation test for one minute The switch button must comply with the electrostatic requirements specified by Clause 7 of EN60079 0 and material composition defined in Clause 8 If the totaliser...

Страница 9: ...ded GRP enclosure If this enclosure is not bolted to an earthed post or structure the earth terminal should be connected to the plant potential equalising conductor The enclosure is fitted with a bond...

Страница 10: ...rised using the square root extractor or the 16 segment lineariser which are selectable in the instrument s FunC sub menu The rate display may then be calibrated using the CAL or 5Et functions to show...

Страница 11: ...e entered using the and push buttons and the P button to move control to the next digit When the correct four digit code has been entered pressing E will cause the first parameter FunC to be displayed...

Страница 12: ...on or oFF See section 6 8 dP Decimal points Positions the decimal point in the rAtE and totAL displays See section 6 9 Display Summary of function CAL Calibration of the rate display using an external...

Страница 13: ...nd Gt rE5Et t rE5Et enables the total display to be reset to zero when and push buttons are operated simultaneously for more than 2 seconds Gt rE5Et enables the grand total to be reset to zero when E...

Страница 14: ...14...

Страница 15: ...arity with bi directional flow Use of the lineariser is described in section 7 of this instruction manual 6 5 Display resolution rE5n This function defines the resolution of the least significant disp...

Страница 16: ...y and identify the lower display variable but on the larger upper display The position of the decimal point can be positioned in the same way by operating the and push buttons when set as required ent...

Страница 17: ...s been activated see section 6 17 To zero the grand total from within the configuration menu select Clr Gtot and press P which will cause the instrument to display Clr no Press the or button until CLr...

Страница 18: ...low rates which over long periods may result in significant totalisation errors the BA354NE rate display can be conditioned to stop totalisation when the flow rate falls below a specified clip off thr...

Страница 19: ...Rate Totaliser is returned to the display mode Please contact BEKA associates sales department if the security code is lost 6 19 Reset to factory defaults r5Et This function enables the Rate Totaliser...

Страница 20: ...ineariser calibration using an external current source This method allows direct calibration of the lineariser with an external current source and is the preferred method when traceability is required...

Страница 21: ...21...

Страница 22: ...llowing break point 7 1 1 Example Adding break points to a new Rate Totaliser When adding break points to a new Rate Totaliser or to a lineariser following resetting to the factory defaults using the...

Страница 23: ...e E button The corresponding rate display at each of the break points can now be defined using the diSP sub function Using the and buttons select the diSP sub function and press P which will reveal th...

Страница 24: ...ither the root extractor or the lineariser are required The standard linear relationship should therefore be selected With FunC displayed press P which will reveal the existing function Using the or b...

Страница 25: ...the totaliser scaling factor In this example the rate display is in litres per minute but the total display is required in cubic metres 5CALE t Units of rate display Units of total display There are 1...

Страница 26: ...and total flow in cubic metres with a resolution of 0 1 cubic metres Total is to be shown on the upper large display and rate on the lower smaller display Totalisation is to occur for flow rates betw...

Страница 27: ...ed by risk analysis or when there is no risk of a flammable atmosphere being present If an Rate Totaliser fails after it has been functioning correctly follow the procedure shown in section 9 1 If thi...

Страница 28: ...of the existing escutcheon Do not remove the original escutcheon The BA354NE Rate Totaliser can also be supplied with a blank or custom laser engraved stainless steel plate secured by two screws to th...

Страница 29: ...dc Ii 200mA This allows each alarm output to switch any dc circuit providing that in normal operation the maximum supply voltage is not greater than 30V and the switched current is not greater than 2...

Страница 30: ...30...

Страница 31: ...ted when the selected display rate or total equals the setpoint See section 10 3 6 Hi Lo Alarm function Defines the alarm function as High or Low See section 10 3 7 no nC Normally open or normally clo...

Страница 32: ...y pressing the or button followed by the E button to return to the alarm menu 10 3 8 Alarm output status no nC Configures the solid state alarm output to be open no or to be closed nC in the non alarm...

Страница 33: ...rate or total display depending upon which has caused the alarm alternates between the numerical value and the alarm reference ALr1 or ALr2 when the alarm output is activated If both alarm outputs ar...

Страница 34: ...5Px1 or 5Px2 prompt from which the other setpoint may be selected or the Rate Totaliser may be returned to the display mode by pressing E again Notes 1 With the Rate Totaliser in the display mode dire...

Страница 35: ...Separately powered backlight The separately powered backlight is a current sink which will draw a constant 35mA when the supply voltage is equal to or greater than 11V At lower supply voltages the ba...

Страница 36: ...A392D Stainless steel bracket secured by two worm drive hose clips Will clamp to any vertical or horizontal pipe with an outside diameter between 60 and 80mm BA393 Heavy duty stainless steel bracket s...

Страница 37: ...2 flammable gas atmosheres may also be used for Zone 22 combustible dust applications The Rate Totaliser should be located where the minimum amount of dust will accumulate on the enclosure and the in...

Страница 38: ...ified operating temperature of the BA354NE is 20 to 70 C At temperatures below 20 C the instrument will continue to totalise but the display will not function The specified gas and dust safety paramet...

Отзывы: