9.6.2  Configuration

When  a  Tachometer  is  supplied  with  an  optional
4/20mA output the configuration menu is extended as
shown in Fig 20.   The 4/20mA output sub-menu is
accessed  via  the  

4-20 oP

  function  that  is  located

before the 

Clr

 

.

 

Gtot

 function.  

The  4/20mA output is controlled by  the  Tachometer
speed  display,  the  speeds  corresponding  to  4  and
20mA output are defined in the sub-menu.

Fig 20   4/20mA output configuration sub-menu

9.6.3  Access 4/20mA output sub-menu:  

4-20 oP

Access  the  Tachometer  configuration  menu  as
described in section 6.2.  Using the  

&

 and 

*

 push

buttons  scroll  though  the  menu  until  

4-20 oP

 is

displayed, pressing  

(  

will then access the 4/20mA

output sub-menu which is shown in Fig 20.

9.6.4  Enable 4/20mA output:  

EnbL

This  function  allows  the  4/20mA  output  to  be
disabled  or  enabled  without  altering  any  of  the
4/20mA output  parameters.    Using  the  

&

 or  

*

push  button  select  

EnbL

 in the  

4-20  oP

 sub-menu

and press 

(

 to reveal the existing setting 

on

 or 

oFF

.

The function can be changed by pressing the 

&

 or

*

 push button followed by the 

)

 button to return

to 

EnbL

 prompt.

    Note:  

When  the  4/20mA output  is  disabled  by
selecting  

oFF

,  the  output  is  a  constant

3.5mA  irrespective  of  the  instrument
display.

9.6.5  Display which corresponds to 4mA
          output:  

4

 

.

 

000

The Tachometer speed display which corresponds to
a 4.000mA output current is defined by this function.
Using the  

&

 or 

*

 push button select  

4

 

.

 

000

 in the

4/20mA output sub-menu and press 

to reveal the

existing speed display with one digit flashing.  The
required display can be entered using the 

&

 or 

*

push button to adjust the flashing digit and the  

(

button to transfer control to the next digit.   When set
as required, press 

to enter the value and return

to the 

4

 

.

 

000

 prompt in the 4/20mA output sub-menu.

9.6.6  Display which corresponds to 20mA
          output:  

20

 

.

 

000

The Tachometer speed display which corresponds to
a  20.000mA  output  current  is  defined  by  this
function.    Using  the  

&

 or 

*

  push  button  select

20

 

.

 

000

 in the 4/20mA output sub-menu and press 

(

to reveal the existing speed display with one digit
flashing.  The required display can be entered using
the 

&

 or 

*

 push button to adjust the flashing digit

and the 

button to transfer control to the next digit.

When set as required, press  

)  

to enter the value

and return to the 

20

 

.

 

000

 prompt in the 4/20mA output

sub-menu.

Notes:

1.

If  the  Tachometer  calibration  is  changed
the 4/20mA output will automatically be set
to 3.5mA irrespective of the speed display.
The  4/20mA  output  should  always  be
reconfigured  following  changes  to  the
Tachometer configuration.

2.

If the Tachometer and the 4/20mA current
sink  output  are  powered  from  separate
supplies,  the  4/20mA  output  current  will
continue  to  flow  when  the  Tachometer
supply fails or is turned off.  Powering both
from  a  common  supply  eliminates  this
effect.

37

Содержание BA317NE

Страница 1: ...Issue 7 9th July 2019 BA317NE Rugged one input Ex nA and Ex tc Tachometer Issue 7...

Страница 2: ...tion functions 6 4 Input inPut 6 5 Input type inP tYPE 6 6 Debounce dEbouncE 6 7 Display update interval uPdAtE 6 8 Run time display di5P 2 6 9 Position of the decimal points dP 6 10 Speed scale facto...

Страница 3: ...Adjusting alarm setpoints from display mode 9 5 Pulse Output 9 5 1 Ex nA certification 9 5 2 Pulse output configuration 9 5 3 Enable pulse output EnbL 9 5 4 Source of output pulse 5ourCE 9 5 5 Divide...

Страница 4: ...4...

Страница 5: ...n Appendix 2 For applications in the USA and Canada the BA317NE has ETL and cETL certification which is described in Appendix 3 2 OPERATION Fig 1 shows a simplified block diagram of the BA317NE Tachom...

Страница 6: ...displays and associated annunciators plus a pulse input indicator as shown on front cover of this manual Speed On upper eight digit display display Run time On lower six digit display display Shows t...

Страница 7: ...or an external Zener barrier or galvanic isolator as shown on the Type Examination Certificate This allows the Tachometer to be adjusted and configured live when installed in a Ex n panel enclosure lo...

Страница 8: ...BA317NE Certification information label 4 SYSTEM DESIGN FOR HAZARDOUS AREAS When correctly installed in Zone 2 the BA317NE Totaliser may be connected to almost any apparatus in the safe area and to Ex...

Страница 9: ...ation is essential for their effective use It is also necessary to ensure that the maintenance procedure makes sure that unauthorised re closure of the switches does not occur It is not considered nec...

Страница 10: ...A317NE contains a configurable debounce circuit to prevent false triggering See section 6 7 4 2 5 Magnetic pick off input Magnetic pick off speed sensors usually have a low level ac voltage output whi...

Страница 11: ...osure Ensure that the edges of aperture are de burred b Inspect the Tachometer s captive gasket and ensure that it is not damaged before inserting it into the panel enclosure aperture c If the enclosu...

Страница 12: ...showing the requested units of measurement if this information is not supplied when the instrument is ordered a blank card will be fitted A pack of self adhesive scale cards printed with common units...

Страница 13: ...factor that determines whether the Tachometer displays speed per second per minute or per hour The Tachometer incorporates a run time clock that displays the time in hours that the speed of the monito...

Страница 14: ...on or oFF See section 6 8 Display Summary of function dP Decimal points Defines the position of the decimal point in the Tachometer speed display See section 6 9 5CALE 5 Speed scale factor 5CALE 5 is...

Страница 15: ...6 Display Summary of function CLr Gtot Resets grand total run time to zero This function resets the grand total run time to zero from within the configuration menu when CLr YE5 is selected and 5urE is...

Страница 16: ...16...

Страница 17: ...17...

Страница 18: ...ch as those resulting from a mechanical contact closing and bouncing Three levels of protection may be selected and the amount of debounce applied depends upon the type of Tachometer input that has be...

Страница 19: ...g shaft generates 18 pulses per revolution to produce a Tachometer speed display in revolutions 5CALE 5 should be set to 18 0 The units of the Tachometer speed display are pulses per unit of time The...

Страница 20: ...sed it is not necessary to enter a clip off value see 6 8 To check or change the clip off threshold select CLP oFF from the configuration menu and press which will reveal the current setting The thres...

Страница 21: ...is displayed and then press which will result in a 0000 prompt being displayed with the first digit flashing This is a request for the instruction to be confirmed by entering 5urE using the or button...

Страница 22: ...al between display updates Using the or button select uPdAtE in the configuration menu and press to reveal how frequently the Tachometer display is updated Using the or push button select 0 5 0 5 seco...

Страница 23: ...h buttons The button will transfer control to the second digit which controls the step response and should be set to 0 in the same way Finally enter the selection and return to the FiLtEr prompt in th...

Страница 24: ...s unauthorised access to the configuration menu Using the or button select CodE from the configuration menu and press which will reveal 0000 with the first digit flashing This example requires the sec...

Страница 25: ...ng calibration change Re enable both alarms 8 2 Fault finding after commissioning BS EN 60079 17 Electrical installations inspection and maintenance permits live maintenance in Zone 2 if a risk analys...

Страница 26: ...output 2 or Isolated dual alarms 2 Notes 1 Internally powered 2 Only one of the three output options can be fitted to a BA317NE Tachometer 9 1 Scale card The BA317NE has a window on the right hand sid...

Страница 27: ...ons such as a shut down system When the BA317NE Tachometer power supply is turned off or disconnected the alarm outputs will open irrespective of whether normally open or normally closed outputs have...

Страница 28: ...ve use It is also necessary to ensure that the maintenance procedure makes sure that unauthorised re closure of the switches does not occur It is not considered necessary to have a means of isolation...

Страница 29: ...ust therefore be reconfigured before use 9 4 6 Setpoint adjustment 5P1 x 5P2 x The speed alarm setpoints 5P1 5peed and 5P2 5peed may be positioned anywhere between 0000000 and 9999999 and the run time...

Страница 30: ...30...

Страница 31: ...the configured alarm silence time When an alarm is silenced the alarm annunciator will flash until the silence time expires To adjust the alarm silence time select 5iL using the or push button in the...

Страница 32: ...digit using the or buttons to adjust the flashing digit and the push button to move control to the next digit If the correct code is entered pressing will then cause alarm setpoint prompt 5P1 5peed o...

Страница 33: ...ned The retransmitted RTx annunciator on the instrument display shows the status of the retransmitted pulse output Annunciator activation depends upon the setting of 5ource in the pulse output configu...

Страница 34: ...e standard 9 5 2 Pulse output configuration PuL5E oP When the BA317NE Tachometer is supplied with a factory fitted pulse output the configuration menu is extended as shown in Fig 18 to include the pul...

Страница 35: ...changed by pressing the or push button followed by the button to return to 5ourCE prompt 9 5 5 Divide output pulse frequency diVidE When 5CALEd is selected in the 5ourCE function described in section...

Страница 36: ...20mA output to be connected to any dc circuit providing that in normal operation the maximum supply voltage is not greater than 30V dc Providing that the BA317NE Tachometer is correctly installed in a...

Страница 37: ...ponds to a 4 000mA output current is defined by this function Using the or push button select 4 000 in the 4 20mA output sub menu and press to reveal the existing speed display with one digit flashing...

Страница 38: ...afe use in dust atmospheres The BA317NE ATEX Type Examination Certificate has an X suffix to show that special conditions for safe use are specified by the BA317NE Ex ic tc certificate indicated by th...

Страница 39: ...for an external Zener barrier or galvanic isolator as shown on the IECEx Certificate This allows the Tachometer to be adjusted and configured live when installed in a Ex n panel enclosure located in...

Страница 40: ...parameters the systems shown in sections 3 4 and 5 of this manual may therefore also be used for US and Canadian installations subject to complying with local codes of practice ETL and cETL codes CL...

Отзывы: