background image

Step 7

Enter the speed timebase

The  speed  timebase  determines  if  the
Tachometer  displays  speed  per  second,
per minute or per hour.   In this example
revolutions per minute are required.
Using  the  

&

 or  

*

  push  button  select

t-bA5E

  from  the  configuration  menu  and

press 

(

.  Again using the 

&

 or 

*

 push

button select 

tb-60

 from the three options

which will multiply the speed display by 60.
Enter  the  selection  and  return  to  the

t-bA5E

 prompt in the configuration menu

by pressing 

)

.

See 6.11

Step 8

Adjust the display filter

The  digital  display  filter  has  two
independent  adjustable  parameters
enabling  the   rate   display   response   to  be
tailored  for  optimum  performance.    The
filter  parameters  are  controlled  by  a  two
digit  number.    The  first  digit  defines  the
amount of filtering applied to the  display,
for initial configuration it is recommended it
is set to 2 which is a time constant of 4.3
seconds.
The second digit defines the deviation from
the displayed speed at which the filtering,
defined by the first digit, will be overridden
and  the  Tachometer  speed  display  will
move  rapidly  to  the  new  value.    It  is
recommended  that  the  second  digit  is
initially set to 0.

After  configuration  both  parameters  may
require  further  adjustment  to  provide  a
stable  display  with  an  acceptable  step
response.

To allow the effect of filter changes to be
seen immediately, the live speed display is
shown on the lower display in place of run-
time while the filter parameters are shown
and being adjusted on the upper display.

Using  the  

&

 or  

*

  push  button  select

FiLtEr

  from  the  configuration  menu  and

press 

(

.   The  first  digit,  which  controls

the filter time constant, will be flashing and
should be set to 

2

 using the 

&

 or 

*

 push

buttons.  The 

button will transfer control

to the second digit, which controls the step
response  and  should  be  set  to  

0

 in  the

same way.  Finally, enter the selection and
return  to  the  

FiLtEr

 prompt  in  the

configuration menu by pressing 

)

.

See 6.12

Step 9

Define clip-off

In  this  example  the  run-time  clock  is
required  to  operate  when  the  display
speed equals or exceeds 5 RPM.   The
clip-off threshold should therefore be set
to 5.

Using the  

&

 or  

*

 push button select

Clp  oFF

 from  the  configuration  menu.

Press  

(  

which  will  reveal  the  current

clip-off  threshold  in  RPM  i.e.  the  same
units  already  selected  for  the  speed
display. Adjust the display to 

00005

 using

the 

&

 or 

*

 push buttons to adjust the

flashing  digit  and  the  

(  

button  to

transfer control to the next digit.  Finally,
enter   the   new   clip-off   threshold   and
return  to  the  

CLp-oFF

 prompt  in  the

configuration menu by pressing 

)

.

See 6.13

Step 13 Local reset of total and grand total

Two  separate  functions  in  the  

LoC  clr

sub-menu  may  be  individually  activated
to allow the operator to reset the run-time
display and grand total run-time from the
display  mode  without  entering  the
configuration menu.

In this example the operator is required
to  reset the run-time display but not the
grand total run-time when the BA317NE
Tachometer is in the display mode.
Using the 

&

 or 

*

 button select 

LoC clr

in the configuration menu and press  

(

which will reveal the sub-menu.   Again
using the 

&

 or 

*

 button select the local

total reset function 

clr tot

 and press 

(

.

This is required therefore using the 

&

 or

*

 button  select  

on

 followed  by  

)  

to

return to the  

clr tot

 prompt in the sub-

menu.

Using  the  

&

 or  

*

 button  select  the

local grand total  run-time reset function

clr  gtot

 and  press  

(

.    This  is  not

required  therefore  using  the  

&

 or  

*

button  select  

oFF

.    Enter  the  selection

and return  to  the   

Loc clr

  prompt  in

the configuration menu  by pressing the

)

 button twice.

See 6.15 and 6.16

23

Содержание BA317NE

Страница 1: ...Issue 7 9th July 2019 BA317NE Rugged one input Ex nA and Ex tc Tachometer Issue 7...

Страница 2: ...tion functions 6 4 Input inPut 6 5 Input type inP tYPE 6 6 Debounce dEbouncE 6 7 Display update interval uPdAtE 6 8 Run time display di5P 2 6 9 Position of the decimal points dP 6 10 Speed scale facto...

Страница 3: ...Adjusting alarm setpoints from display mode 9 5 Pulse Output 9 5 1 Ex nA certification 9 5 2 Pulse output configuration 9 5 3 Enable pulse output EnbL 9 5 4 Source of output pulse 5ourCE 9 5 5 Divide...

Страница 4: ...4...

Страница 5: ...n Appendix 2 For applications in the USA and Canada the BA317NE has ETL and cETL certification which is described in Appendix 3 2 OPERATION Fig 1 shows a simplified block diagram of the BA317NE Tachom...

Страница 6: ...displays and associated annunciators plus a pulse input indicator as shown on front cover of this manual Speed On upper eight digit display display Run time On lower six digit display display Shows t...

Страница 7: ...or an external Zener barrier or galvanic isolator as shown on the Type Examination Certificate This allows the Tachometer to be adjusted and configured live when installed in a Ex n panel enclosure lo...

Страница 8: ...BA317NE Certification information label 4 SYSTEM DESIGN FOR HAZARDOUS AREAS When correctly installed in Zone 2 the BA317NE Totaliser may be connected to almost any apparatus in the safe area and to Ex...

Страница 9: ...ation is essential for their effective use It is also necessary to ensure that the maintenance procedure makes sure that unauthorised re closure of the switches does not occur It is not considered nec...

Страница 10: ...A317NE contains a configurable debounce circuit to prevent false triggering See section 6 7 4 2 5 Magnetic pick off input Magnetic pick off speed sensors usually have a low level ac voltage output whi...

Страница 11: ...osure Ensure that the edges of aperture are de burred b Inspect the Tachometer s captive gasket and ensure that it is not damaged before inserting it into the panel enclosure aperture c If the enclosu...

Страница 12: ...showing the requested units of measurement if this information is not supplied when the instrument is ordered a blank card will be fitted A pack of self adhesive scale cards printed with common units...

Страница 13: ...factor that determines whether the Tachometer displays speed per second per minute or per hour The Tachometer incorporates a run time clock that displays the time in hours that the speed of the monito...

Страница 14: ...on or oFF See section 6 8 Display Summary of function dP Decimal points Defines the position of the decimal point in the Tachometer speed display See section 6 9 5CALE 5 Speed scale factor 5CALE 5 is...

Страница 15: ...6 Display Summary of function CLr Gtot Resets grand total run time to zero This function resets the grand total run time to zero from within the configuration menu when CLr YE5 is selected and 5urE is...

Страница 16: ...16...

Страница 17: ...17...

Страница 18: ...ch as those resulting from a mechanical contact closing and bouncing Three levels of protection may be selected and the amount of debounce applied depends upon the type of Tachometer input that has be...

Страница 19: ...g shaft generates 18 pulses per revolution to produce a Tachometer speed display in revolutions 5CALE 5 should be set to 18 0 The units of the Tachometer speed display are pulses per unit of time The...

Страница 20: ...sed it is not necessary to enter a clip off value see 6 8 To check or change the clip off threshold select CLP oFF from the configuration menu and press which will reveal the current setting The thres...

Страница 21: ...is displayed and then press which will result in a 0000 prompt being displayed with the first digit flashing This is a request for the instruction to be confirmed by entering 5urE using the or button...

Страница 22: ...al between display updates Using the or button select uPdAtE in the configuration menu and press to reveal how frequently the Tachometer display is updated Using the or push button select 0 5 0 5 seco...

Страница 23: ...h buttons The button will transfer control to the second digit which controls the step response and should be set to 0 in the same way Finally enter the selection and return to the FiLtEr prompt in th...

Страница 24: ...s unauthorised access to the configuration menu Using the or button select CodE from the configuration menu and press which will reveal 0000 with the first digit flashing This example requires the sec...

Страница 25: ...ng calibration change Re enable both alarms 8 2 Fault finding after commissioning BS EN 60079 17 Electrical installations inspection and maintenance permits live maintenance in Zone 2 if a risk analys...

Страница 26: ...output 2 or Isolated dual alarms 2 Notes 1 Internally powered 2 Only one of the three output options can be fitted to a BA317NE Tachometer 9 1 Scale card The BA317NE has a window on the right hand sid...

Страница 27: ...ons such as a shut down system When the BA317NE Tachometer power supply is turned off or disconnected the alarm outputs will open irrespective of whether normally open or normally closed outputs have...

Страница 28: ...ve use It is also necessary to ensure that the maintenance procedure makes sure that unauthorised re closure of the switches does not occur It is not considered necessary to have a means of isolation...

Страница 29: ...ust therefore be reconfigured before use 9 4 6 Setpoint adjustment 5P1 x 5P2 x The speed alarm setpoints 5P1 5peed and 5P2 5peed may be positioned anywhere between 0000000 and 9999999 and the run time...

Страница 30: ...30...

Страница 31: ...the configured alarm silence time When an alarm is silenced the alarm annunciator will flash until the silence time expires To adjust the alarm silence time select 5iL using the or push button in the...

Страница 32: ...digit using the or buttons to adjust the flashing digit and the push button to move control to the next digit If the correct code is entered pressing will then cause alarm setpoint prompt 5P1 5peed o...

Страница 33: ...ned The retransmitted RTx annunciator on the instrument display shows the status of the retransmitted pulse output Annunciator activation depends upon the setting of 5ource in the pulse output configu...

Страница 34: ...e standard 9 5 2 Pulse output configuration PuL5E oP When the BA317NE Tachometer is supplied with a factory fitted pulse output the configuration menu is extended as shown in Fig 18 to include the pul...

Страница 35: ...changed by pressing the or push button followed by the button to return to 5ourCE prompt 9 5 5 Divide output pulse frequency diVidE When 5CALEd is selected in the 5ourCE function described in section...

Страница 36: ...20mA output to be connected to any dc circuit providing that in normal operation the maximum supply voltage is not greater than 30V dc Providing that the BA317NE Tachometer is correctly installed in a...

Страница 37: ...ponds to a 4 000mA output current is defined by this function Using the or push button select 4 000 in the 4 20mA output sub menu and press to reveal the existing speed display with one digit flashing...

Страница 38: ...afe use in dust atmospheres The BA317NE ATEX Type Examination Certificate has an X suffix to show that special conditions for safe use are specified by the BA317NE Ex ic tc certificate indicated by th...

Страница 39: ...for an external Zener barrier or galvanic isolator as shown on the IECEx Certificate This allows the Tachometer to be adjusted and configured live when installed in a Ex n panel enclosure located in...

Страница 40: ...parameters the systems shown in sections 3 4 and 5 of this manual may therefore also be used for US and Canadian installations subject to complying with local codes of practice ETL and cETL codes CL...

Отзывы: