6.4  Input:  

inPut

The  Input  function  contains  two  sub-functions

inP

 

.

 

tYPE

 and  

dEbounCE

 which  configure  the

Tachometer  input  and  define  the  amount  of  input
noise rejection.

6.5  Input type:  

inP

 

.

 

tYPE

inP

 

.

 

tYPE

 is a sub-menu in the  

inPut

 function which

defines the type of input sensor or input pulse with
which  the  Tachometer  will  function.    To  check  or
change  the  type  of  input,  select  

inPut

 in  the  main

configuration menu and press 

(

 which will reveal the

inP

 

.

 

tYPE

 prompt,  pressing  

(

 

again will show the

present  type  of  input

.    

If  set  as  required  press  

)

twice  to  return  to  the  configuration  menu,  or
repeatedly  press  the  

&

 or  

*

  button  until  the

required type of input is displayed and then press 

)

twice to return to the configuration menu.

One of following six types of input may be selected:

                                                                       Switching
                                                                       thresholds
                                                                     Low      High

oP

 

.

 

CoL

Open collector 

2

2

10k

VoLt5L

Voltage pulse low 

1

1

3V

VoLt5H

Voltage pulse high

1

3

10V

CoiL

Magnetic pick-off 

0

40mV

Pr

 

.

 

dEt

Proximity detector 

2

1.2

2.1mA

ContACt

Switch contact 

2

100

1000

Notes:

1

Maximum voltage input +30V.

2

For  sensors  that  require  energising    i.e.
proximity  detectors,  switch  contacts  and
open  collectors,  terminals  3  &  4  of  the
Tachometer should be linked together.

3

To count correctly, the input pulse must fall
below the lower switching threshold and rise
above the higher switching threshold.

4       See section 6.6 for maximum operating 
        frequency.

6.6  Debounce:  

dEbouncE

dEbouncE

  is  an  adjustable  sub-menu  in  the  

inPut

function which prevents the Tachometer miscounting
when the input pulse has noisy edges, such as those
resulting  from  a  mechanical  contact  closing  and
bouncing.      Three  levels  of  protection  may  be
selected  and  the  amount  of  debounce  applied
depends upon the type of Tachometer input that has
been selected in the 

inP

 

.

 

tYPE

 function.

The following table shows the minimum time that the
input pulse must be continuously above the upper
input switching threshold and continuously below the
lower  switching  threshold  to  ensure  that  the
Tachometer  processes  the  input  pulse.    Input
switching thresholds are shown in section 6.5.

De-bounce

level

Min input pulse width

Type of Input

Contact

All others

Default

1600µs

40µs

Heavy

3200µs

350µs

Light

400µs

5µs

The  Tachometer’s  maximum  counting  frequency
depends  upon  the  debounce  level  selected,  the
shape  of  the  input  pulse  and  its  amplitude.    The
following table assumes a square wave input and is
only  for  guidance.    The  maximum  operating
frequency  will  be  lower  if  the  input  pulses  have
sloping edges and the pulse amplitude only slightly
exceeds the input switching thresholds.  

ONLY FOR GUIDANCE

Debounce

level

Max counting frequency

Type of input

Contact

All others

Default

250Hz

12kHz

Heavy

120Hz

2kHz

Light

1000Hz

100kHz

The minimum operating input frequency is 0.01Hz.
Below this frequency the speed display will be forced
to zero.

The 

dEbouncE

 function is a sub-menu located in the

inPut

 function.   Select  

inPut

 in  the  configuration

menu and press  

(

 which will reveal the  

inP

 

.

 

tYPE

prompt,  press  the  

&

 or  

*

  button  to  select

dEbouncE

 followed  by  

(

 

to  reveal  the  existing

setting.  

 

 Pressing the  

&

 or  

*

 button will scroll

through the three levels.  When the required level
has been selected, pressing  

)  

twice will enter the

selection and return the display to the 

inPut

 prompt

in the configuration menu.

18

Содержание BA317NE

Страница 1: ...Issue 7 9th July 2019 BA317NE Rugged one input Ex nA and Ex tc Tachometer Issue 7...

Страница 2: ...tion functions 6 4 Input inPut 6 5 Input type inP tYPE 6 6 Debounce dEbouncE 6 7 Display update interval uPdAtE 6 8 Run time display di5P 2 6 9 Position of the decimal points dP 6 10 Speed scale facto...

Страница 3: ...Adjusting alarm setpoints from display mode 9 5 Pulse Output 9 5 1 Ex nA certification 9 5 2 Pulse output configuration 9 5 3 Enable pulse output EnbL 9 5 4 Source of output pulse 5ourCE 9 5 5 Divide...

Страница 4: ...4...

Страница 5: ...n Appendix 2 For applications in the USA and Canada the BA317NE has ETL and cETL certification which is described in Appendix 3 2 OPERATION Fig 1 shows a simplified block diagram of the BA317NE Tachom...

Страница 6: ...displays and associated annunciators plus a pulse input indicator as shown on front cover of this manual Speed On upper eight digit display display Run time On lower six digit display display Shows t...

Страница 7: ...or an external Zener barrier or galvanic isolator as shown on the Type Examination Certificate This allows the Tachometer to be adjusted and configured live when installed in a Ex n panel enclosure lo...

Страница 8: ...BA317NE Certification information label 4 SYSTEM DESIGN FOR HAZARDOUS AREAS When correctly installed in Zone 2 the BA317NE Totaliser may be connected to almost any apparatus in the safe area and to Ex...

Страница 9: ...ation is essential for their effective use It is also necessary to ensure that the maintenance procedure makes sure that unauthorised re closure of the switches does not occur It is not considered nec...

Страница 10: ...A317NE contains a configurable debounce circuit to prevent false triggering See section 6 7 4 2 5 Magnetic pick off input Magnetic pick off speed sensors usually have a low level ac voltage output whi...

Страница 11: ...osure Ensure that the edges of aperture are de burred b Inspect the Tachometer s captive gasket and ensure that it is not damaged before inserting it into the panel enclosure aperture c If the enclosu...

Страница 12: ...showing the requested units of measurement if this information is not supplied when the instrument is ordered a blank card will be fitted A pack of self adhesive scale cards printed with common units...

Страница 13: ...factor that determines whether the Tachometer displays speed per second per minute or per hour The Tachometer incorporates a run time clock that displays the time in hours that the speed of the monito...

Страница 14: ...on or oFF See section 6 8 Display Summary of function dP Decimal points Defines the position of the decimal point in the Tachometer speed display See section 6 9 5CALE 5 Speed scale factor 5CALE 5 is...

Страница 15: ...6 Display Summary of function CLr Gtot Resets grand total run time to zero This function resets the grand total run time to zero from within the configuration menu when CLr YE5 is selected and 5urE is...

Страница 16: ...16...

Страница 17: ...17...

Страница 18: ...ch as those resulting from a mechanical contact closing and bouncing Three levels of protection may be selected and the amount of debounce applied depends upon the type of Tachometer input that has be...

Страница 19: ...g shaft generates 18 pulses per revolution to produce a Tachometer speed display in revolutions 5CALE 5 should be set to 18 0 The units of the Tachometer speed display are pulses per unit of time The...

Страница 20: ...sed it is not necessary to enter a clip off value see 6 8 To check or change the clip off threshold select CLP oFF from the configuration menu and press which will reveal the current setting The thres...

Страница 21: ...is displayed and then press which will result in a 0000 prompt being displayed with the first digit flashing This is a request for the instruction to be confirmed by entering 5urE using the or button...

Страница 22: ...al between display updates Using the or button select uPdAtE in the configuration menu and press to reveal how frequently the Tachometer display is updated Using the or push button select 0 5 0 5 seco...

Страница 23: ...h buttons The button will transfer control to the second digit which controls the step response and should be set to 0 in the same way Finally enter the selection and return to the FiLtEr prompt in th...

Страница 24: ...s unauthorised access to the configuration menu Using the or button select CodE from the configuration menu and press which will reveal 0000 with the first digit flashing This example requires the sec...

Страница 25: ...ng calibration change Re enable both alarms 8 2 Fault finding after commissioning BS EN 60079 17 Electrical installations inspection and maintenance permits live maintenance in Zone 2 if a risk analys...

Страница 26: ...output 2 or Isolated dual alarms 2 Notes 1 Internally powered 2 Only one of the three output options can be fitted to a BA317NE Tachometer 9 1 Scale card The BA317NE has a window on the right hand sid...

Страница 27: ...ons such as a shut down system When the BA317NE Tachometer power supply is turned off or disconnected the alarm outputs will open irrespective of whether normally open or normally closed outputs have...

Страница 28: ...ve use It is also necessary to ensure that the maintenance procedure makes sure that unauthorised re closure of the switches does not occur It is not considered necessary to have a means of isolation...

Страница 29: ...ust therefore be reconfigured before use 9 4 6 Setpoint adjustment 5P1 x 5P2 x The speed alarm setpoints 5P1 5peed and 5P2 5peed may be positioned anywhere between 0000000 and 9999999 and the run time...

Страница 30: ...30...

Страница 31: ...the configured alarm silence time When an alarm is silenced the alarm annunciator will flash until the silence time expires To adjust the alarm silence time select 5iL using the or push button in the...

Страница 32: ...digit using the or buttons to adjust the flashing digit and the push button to move control to the next digit If the correct code is entered pressing will then cause alarm setpoint prompt 5P1 5peed o...

Страница 33: ...ned The retransmitted RTx annunciator on the instrument display shows the status of the retransmitted pulse output Annunciator activation depends upon the setting of 5ource in the pulse output configu...

Страница 34: ...e standard 9 5 2 Pulse output configuration PuL5E oP When the BA317NE Tachometer is supplied with a factory fitted pulse output the configuration menu is extended as shown in Fig 18 to include the pul...

Страница 35: ...changed by pressing the or push button followed by the button to return to 5ourCE prompt 9 5 5 Divide output pulse frequency diVidE When 5CALEd is selected in the 5ourCE function described in section...

Страница 36: ...20mA output to be connected to any dc circuit providing that in normal operation the maximum supply voltage is not greater than 30V dc Providing that the BA317NE Tachometer is correctly installed in a...

Страница 37: ...ponds to a 4 000mA output current is defined by this function Using the or push button select 4 000 in the 4 20mA output sub menu and press to reveal the existing speed display with one digit flashing...

Страница 38: ...afe use in dust atmospheres The BA317NE ATEX Type Examination Certificate has an X suffix to show that special conditions for safe use are specified by the BA317NE Ex ic tc certificate indicated by th...

Страница 39: ...for an external Zener barrier or galvanic isolator as shown on the IECEx Certificate This allows the Tachometer to be adjusted and configured live when installed in a Ex n panel enclosure located in...

Страница 40: ...parameters the systems shown in sections 3 4 and 5 of this manual may therefore also be used for US and Canadian installations subject to complying with local codes of practice ETL and cETL codes CL...

Отзывы: