background image

12

i.e. 

A span of 1400 ignoring the decimal
point A decimal point in position 00.0

The following adjustments are required:

Step 1

Put the suppression / elevation links
in the elevation position.

Step 2

Put the zero link in the 0 to 500
position.

Step 3

The required span is 1400, therefore
the span links should be placed in the
1000 to 1500 position.

Step 4

The decimal point is required between
the two least significant digits,
therefore the decimal point link should
be placed in the 00.0 position.

Step 5

With 4.160mA input current adjust the
zero potentiometer until the indicator
displays 14.0 (10% of flow). If there is
insufficient adjustment to achieve this,
put the elevation/suppression links in
the suppression position and repeat
step 5.

Step 6

With 20.000mA input current adjust
the span potentiometer until the
indicator displays 140.0

Step 

7

Repeat steps 5 and 6 until both
calibration points are correct.

8.4  Display backlights

The BA304ND may be supplied with two different
backlights. The loop powered backlight produces
green background illumination enabling the display
to be read at night and in poor lighting conditions.
No additional power supply or field wiring are
required, but the indicator voltage drop is
increased. Alternatively, the separatly powered
backlight has a bright orange output which
enhances daylight viewing, but additional field
wiring and a power supply are required.

8.4.1  Separately powered backlight

The separately powered backlight is electrically
segregated from the measuring circuit, and has
been certified as a separate Ex nL Group II,
Category 3G circuit.

The Type nL input safety parameters are:

Ui

=

30V dc

Ii

=

100mA dc

Pi

=

1.3W

This allows the backlight to be powered from a
safe area 18 to 30V dc supply as shown in Fig 8.
Providing the supply voltage is less than 30V dc,
the backlight safety components will ensure that
the maximum input current and power are within
the safety limits.

Reducing the supply voltage below 18V, or fitting a
current limiting resistor in series with the supply will
reduce the display brilliance.

Fig 8 Separately powered backlight

8.4.2  Loop powered backlight

This backlight is connected in series with the
4/20mA measuring circuit as shown in Fig 9. In
normal operation the voltage and current applied to
terminals 1 and 13 of the BA304ND must not
exceed:

Ui

=

6V dc

Ii

=

30 mA dc

Providing the maximum input current in normal
operation is less than 30mA, the maximum voltage
between the indicator terminals will automatically
be limited by the internal safety components.

Содержание BA304ND

Страница 1: ...issue 8 4th March 2014 BA304ND Type nL certified loop powered 3 digit field mounting indicator issue 8 Only for replacement use after May 2013 Use BA304NE for new applications...

Страница 2: ...on example 6 6 Over and under range 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Customer comments...

Страница 3: ...wer the analogue to digital converter and liquid crystal display The voltage developed across R1 which is proportional to the 4 20mA input current provides the input signal for the analogue to digital...

Страница 4: ...mperatures between 20 and 60 C Used with gases in groups Group A propane Group B ethylene Group C hydrogen Used with gases having a temperature classification of T1 450 C T2 300 C T3 200 C T4 135 C or...

Страница 5: ...alyser drives a BA304ND Again it is necessary to ensure that the loop complies with the two design requirements listed in section 4 1 Fig 3 Remote indication 5 INSTALLATION 5 1 Location The BA304ND in...

Страница 6: ...re 5 3 EMC The BA304ND complies with the requirements of the European EMC Directive 2004 108 EC For specified immunity all wiring should be in screened twisted pairs Fig 5 Dimensions and terminal conn...

Страница 7: ...plug in link shown in Fig 6 When calculating the required span and zero settings the decimal point should be ignored 6 4 Reverse action Normally the BA304ND display increases as the input current inc...

Страница 8: ...8 Fig 6 Position of plug in links and potentiometers shown with control cover removed...

Страница 9: ...n not enter the enclosure Before replacing control terminal covers ensure that the sealing gaskets are undamaged and free from dirt and foreign bodies If a BA304ND fails after it has been functioning...

Страница 10: ...dirt and foreign bodies To gain access to the display label remove the terminal cover by unscrewing the two A screws which will reveal two concealed D screws Unscrew the four D screws and carefully l...

Страница 11: ...ely clip off can be selected which will force the display to zero at flows below 5 4 04mA The location of the clip off link is shown in Fig 7 Access to the link is gained by carefully removing the ind...

Страница 12: ...d wiring are required but the indicator voltage drop is increased Alternatively the separatly powered backlight has a bright orange output which enhances daylight viewing but additional field wiring a...

Страница 13: ...t secured by two worm drive hose clips Will clamp to any pipe with an outside diameter between 60 and 80mm BA393D Heavy duty stainless steel bracket secured by a V bolt Will clamp to any pipe with an...

Отзывы: