The position of the probe is a crucial factor for a gas detection unit correct functioning.
In order to obtain the maximum results from an appliance and minimize the probabilities of false alarms, we recommend
to follow this diagram and to keep in mind the following general rules.
The remote probe must be located at different heights, according to the type of gas.
These heights are:
- 30 cm from the lowest point of the floor in order to detect 

 

Heavy Gases

 

:

 

 

LPG, 

Gasoline vapours, Alcohol.

- 30 cm from the highest point of the ceiling in order to detect  Light gases:

  Methane, Hydrogen, 

Ammonia, Acetylene.

- The probe should not be placed near the appliances to be controlled (boilers, burners, industrial kitchens, etc.) but
  on the opposite wall.
- The probe should not be affected by smoke, vapour, etc. as they could distort their measurement. It must be placed
  away from sources of heat, suction fans, ventilation fans.

Positioning of the Sensor

Detection diagrams data

ppm

0         50      100      150       200      250      300

 

 6,7

        Toxic  Gas  Detection  diagram

0

  

  

  

4

  

5

  

  

 1

0

  

  

  

 1

5

  

  

  

2

0

 

 7,2

 

 20

m A

L in ea r  +/ -5 %

Zona   A va ri a

 

 9,3

 

 12

 

 14,6

 

 17,3

    Explosive  Gas  Detection  diagram

0       4%       8%      12%     16%      20%

0

  

  

  

4

  

5

  

  

 1

0

  

  

  

 1

5

  

  

  

2

0

 

 7,2

 

 10,4

 

 13,6

 

 16,8

 

 20

m A

L in ea r  +/ -5 %

L . I . E .

Zona   A va ri a

Curren t-Vo ltage  Con vers io n   G raph
with  220  Ohm  Load  Resistance

0

  

  

4

  

5

  

  

  

 1

0

  

  

  

1

5

  

  

  

2

0

V.

m A

0,88 1,1      2,2       3,3      4,4

L in ea r  +/ -5 %

O K

NO  !

NO  !

 

30 cm Light Gas

30 cm Heavy Gas

 160 cm Volatil Gas

  INSTALLATION  DISTANCES

Содержание SG580

Страница 1: ...CONFORMITY Installation and user guide Important Assembly maintenance of the appliance must be carried out by qualified personnel and in accordance with applicable laws and regulations The manufacturer assumes no responsibility for the use of products that have to comply with particular environmental and or installation standards Important note Before connecting the equipment it is recommended tha...

Страница 2: ...on of the SG580Sensor its ordinary and extraordinary maintenance every six months and its out of service removal at the end of the functional life guaranteed by the manufacturer must be carried out by authorized or specialized personnel Do not allow it to become wet The control unit can be seriously damaged as it is not waterproof either when immersed in water or exposed to high levels of humidity...

Страница 3: ...unit 1 zone Panel 1 IP42 1 1 YES NO BX180 unit 1 zone Omega bar DIN 1 IP20 1 1 YES NO BX280 unit 1 zone Omega bar DIN 2 IP20 1 1 YES NO BX449F unit 1 zone Omega bar DIN 4 IP20 1 1 YES NO BX308 unit 1 zone Omega bar DIN 8 IP20 1 1 YES YES BX308 Box unit 1 zone Wall 8 IP65 1 1 YES YES BX316 unit 2 zones Barra Omega 16 IP20 1 2 YES YES BX316 Box unit 2 zones Wall 16 IP65 1 2 YES YES TAKITJ8 Data Coll...

Страница 4: ...etylene The probe should not be placed near the appliances to be controlled boilers burners industrial kitchens etc but on the opposite wall The probe should not be affected by smoke vapour etc as they could distort their measurement It must be placed away from sources of heat suction fans ventilation fans Positioning of the Sensor Detectiondiagrams data ppm 0 50 100 150 200 250 300 6 7 Toxic Gas ...

Страница 5: ... the operating range to 100 LEL you need to move the jumper between the central and the top pole Electrical cabling Please read the paragraph Particular Specifications for Use in Explosive Atmospheres NOTE Please remind that if you pierce the FLAMEPROOF container it will completely lose its properties Moreover you should install a FLAMEPROOF cable gland for the connection cables 3 2 1 1 2 3 4 5 6 ...

Страница 6: ...not been pinched Check the voltage at the terminals 1 2 It must be higher than 10 80 Vdc and lesser than 26 4 Vdc Check that the connector of the sensor is correctly inserted If it s connected to control unit Check the voltage at the terminals 2 3 It must be from a minimum of 0 8 Vdc to a maximum of 1 1 Vdc Remark If the probes are connected to the control units BX308 and BX316 the voltage at the ...

Страница 7: ...electrical device or appliance 4 Open windows and doors in order to increase ventilation If the alarm stops its cause must be found and the relevant consequent measures taken If the alarm continues and the cause of gas presence cannot be found or removed abandon the building and call the emergency services when outside fire department distributors etc IMPORTANT The operation test should not be car...

Страница 8: ...l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable collection point for the recycling of electr...

Отзывы: