background image

Page 7

1)By  providing  the  proper  voltage  with  an  external  switch,  which  must  be  provided  with  safety  fuses,  you  will
see  that  the  POWER  LED,  wait  60  seconds,  after  this  time  the  detector  is  ready  to  detect.

2)Pressing  the  TEST  button,  you  get  the  simulation  of  a  gas  leak  and  the  detector  performs  the  following
actions:  The  LED  ALARM  will  turn  on  and  the  relay  will  change  its  working  state  after  5  seconds.  Ceased  the
alarm,  the  LED  will  turn  off,  it  will  stop  the  buzzer  sound  and  the  connected  devices  will  be  disabled.

*  To  complete  the  general  test,  emit  gas  from  a  calibration  bottle  pre-calibrated  within  20%  of  the  LEL.
Do  a  test  with  a  common  cigarette  lighter  could  cause  damage  to  the  sensor.
We  recommend  that  you  make  this  test  at  least  once  a  year.

Turn  on  and  testing

- If the device does not start up.
Check  that  the  230/240  VAC  power  is  correctly  connected.

When  the  fault  LED  lights  up
Check  the  capsule  detector,  the  RGX100  may  have  failed.
It  may  be  exhausted:  after  5/6  years  should  be  replaced.

If  the  detector  goes  into  alarm  repeatedly.
Check  that  there  are  no  gas  leaks.  Check  that  together  with  the  alarm  does  not  turn  on  even  the  led  FAULT,
in  this  case,  proceed  with  the  inspection  of  the  capsule  detector.

If  the  detector  goes  into  alarm  and  closes  the  connected  equipment.
Check  that  connections  are  correct  and  that  the  jumper  which  leads  to  the  common  voltage  of  the  relay  has
been  carried  out,  all  the  relays  are  voltage  free.    Check  the  scheme  of  connection.

If  RGX100  is  connected  to  a  Solenoid  valves  12  VDC  and  does  not  work.
To RGX100 you can not connect directly solenoid valves, sirens in 12 VDC. It must always to use to an external
supply.

Do  not  tamper  with  the  detector
In  order  not  to  cause  decalibration  of  the  device  and  electric  shock.

If other problems arise, it is necessary to call a specialised and/or authorised technician and/or the Distributor of
BEINAT S.r.l. should be contacted directly.

Before calling a technician ...

1) Put out all free flames.
2) Close the main gas tap or the LPG cylinder tap.
3) Do not turn any lights on or off; do not turn on any electrical device or appliance.
4) Open windows and doors in order to increase ventilation.

If the alarm stops, its cause must be found and the relevant consequent measures taken.
If the alarm continues and the cause of gas presence cannot be found or removed, abandon the building and call
the emergency services when outside (fire department, distributors, etc.)

Warning !!

If you have the following symptoms: vomiting, sleepiness, or else, go to the closest first aid station and
inform the operators that you could have been poisoned by Gas Methane or LPG.

WARNING!  Actions  to  be  taken  in  case  of  alarm

Содержание RGX100

Страница 1: ...ith the concept of home fitness comes the household gas detector RGX100 detects through the catalytic sensor the presence of explosive gas such as Methane LPG Gas detection The detector is tested and calibrated to 10 of L E L The power supply unit allows driving of a manual reset solenoid valve with a 12Vdc coil without any buffer battery If the voltage absorption is too high you can later integra...

Страница 2: ...a specialized technician The disposal of the detector 5 years after installation It must be carried out by qualified technician Mains power 230VAC 50 60 Hz 10 Battery power 12 VDC 1 2 Ah 10 Current consumption 3 1 W 230V Range of relay contact switching 10A 250V resistive 5A 30Vdc resistive Battery charger Max Built in for a 1 2Ah 12VDC battery Insulation Class II Explosive gas sensor Catalytic Ex...

Страница 3: ...ds and then will reopen them This is needed to prevent damaging some types of manual reset solenoid valve coils This features is suitable only when a 12 Vdc electrovalve is connected By opening the two poles the relay will be set to continuous functioning 6 Relay This relay changes its position when the detector trigger the main alarm 7 Catalytic sensor for Methane or LPG explosive gas detection 8...

Страница 4: ...e free Power supply 230 240 VAC Electrical connections WARNING Before connecting to the mains power ensure the voltage is correct Carefully follow the instructions and the connections according to Regulations in force An automatic disconnetting switch appropriately identified as the detector sectioning device must be incorporated in the electrical system suitably located and easily accessible N C ...

Страница 5: ...tery 12VDC 1 2Ah MAX N B The 12VDC voltage can be derived from another source Normaly open solenoid valve 12VDC N C C NO 1 2 3 4 5 6 7 Solenoid valve NA 12 VDC Connection with a normally closed solenoid valve 12 VDC N C C NO N Ph 1 2 3 4 5 6 7 230 240 VAC Solenoid valve NA 12 VDC ATTENTION Relay is voltage free The power supply is 230 240 VAC with a buffer battery 12VDC 1 2Ah MAX N C C NO 1 2 3 4 ...

Страница 6: ...r should not be installed in environments where the temperature drops below 10 C or rises above 40 C The detector is equipped to detect different types of gases and according to these its must to be positioned at different heights These heights are 30 cm from the lowest point of the floor in order to detect heavy gases LPG etc 30 cm from the highest point of the ceiling in order to detect light ga...

Страница 7: ...oes into alarm and closes the connected equipment Check that connections are correct and that the jumper which leads to the common voltage of the relay has been carried out all the relays are voltage free Check the scheme of connection If RGX100 is connected to a Solenoid valves 12 VDC and does not work To RGX100 you can not connect directly solenoid valves sirens in 12 VDC It must always to use t...

Страница 8: ...excluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable collec...

Отзывы: