Indeed,  the  most  essential  factor  for  the  proper  functioning  of  the  GSH900  is  its  correct  installation.
By following the  instructions in this paragraph, high precision can be obtained together with the absence of false
alarms.

Install  the  GSH900  on  the  wall  opposite  the  possible  source  of  danger,  example:  kitchens,  boilers,  or  else.

Do  not  install:  behind  barriers  that  prevent  the  prompt  detection  of  gas,  near  vents  or  fans,  and  in  rooms
where  temperature  falls  below  -10°C  or  over  +40°C.

It  must  be  placed:

-  30  cm 

from  the  lowest  point  of  the  floor  in  order  to  detect

heavy  gases  (L.P.G.  etc.)

-  30  cm

  from  the  highest  point  of  the  ceiling  in  order  to  detect

light  gases  (Methane,  etc.)

Turn on and testing

After  turning  on,  the  GSH900  performs  a  test  of  the  sensor’s  efficiency  status,  and  gets  it  to  the  functioning
temperature.
This phase lasts about 60 seconds. At the end, the detector will issue a “BEEP”. Then it is ready for detection.
Note. during the test period, the GSH900 does not detect the gas.

FUNCTIONING TEST

Using a pointed tool, or a toothpick, press the button under the hole indicated by number “4” (see drawing above).
The ALARM and FAULT LEDs will light up, and the relay will shift its functioning mode after 5 seconds.
After the alarm, the LEDs will turn off, the buzzer will stop, and the connected appliances will be turned off.

To complete the general test, issue gas from a pre-calibrated aerosol within 20% of LEL.
Performing a test using a common cigarette lighter you could damage the sensor.
This test should be carried out at least once a year.

Installation measures and positioning

N O !

Cau tio n !!  Do   n o t  in s t all  th e
detector  near:  sinks,  air  intakes,
h eati n g  o r  air   co n diti o n in g
s ys tems , 

w in do ws  

an d

ventilation  devices.

Содержание GSH900

Страница 1: ... E L According to the CEI 216 8 Norm of 2005 the detectors are trigged by a specific combustible gas concentration in the environment The detectors should tolerate common vapours and interfering substances usually present in household environments and guarantee a high stability with temperature and humidity variations A series of technical features make this gas detector extremely versatile reliab...

Страница 2: ...1 W Range of relay contact switching free of voltage 10A 250V resistive Types of gas detected Natural Gas for Natural gas LPG for LPG model Detection sensor Catalytic Alarm sensitivity At 10 of L E L Precision of the detector 1 FS Sensor s faults detected by Fault Circuit Interruption short circuit or wear Test Phase Duration 60 seconds Audible and visual signal alarm by LED diode and buzzer 85 dB...

Страница 3: ...ng installation keeping in mind that the detector should be overhauled after 5 years Components and commands The installation of the detector does not exempt from the compliance with all regulations concerning the characteristics installation and use of gas appliances Particularly the ventilation of the spaces and the elimination of combustion products are described in the UNI norms according to A...

Страница 4: ...s efficiency status and gets it to the functioning temperature This phase lasts about 60 seconds At the end the detector will issue a BEEP Then it is ready for detection Note during the test period the GSH900 does not detect the gas FUNCTIONINGTEST Using a pointed tool or a toothpick press the button under the hole indicated by number 4 see drawing above The ALARM and FAULT LEDs will light up and ...

Страница 5: ...The installation of the detector does not exempt from the compliance with all regulations concerning the characteristics installation and use of gas appliances Particularly the ventilation of the spaces and the elimination of combustion products are described in the UNI norms according to ART 3 LAW 1083 71 and relevant legal provisions 1 Put out all free flames 2 Close the main gas tap or the LPG ...

Страница 6: ...g to Regulations in force An automatic disconnetting switch appropriately identified as the detector sectioning device must be incorporated in the electrical system suitably located and easily accessible N Power supply 230 V AC Ph N C C NO Relay Alarm 1 2 3 4 5 Connection Scheme of GSH900 Detector WARNING All relays are free of voltage Jumper for Relay working Mode 1 With the Jumper opened the rel...

Страница 7: ...ection 230V ac 1 2 3 4 5 1 2 3 4 5 WARNING All relays are free of voltage Connection Scheme with a normally open valve 230VAC Power supply 230 V AC One or more detectors with a normally open valve 230VAC One or more detectors with a normally close valve 230VAC WARNING All relays are free of voltage ...

Страница 8: ...ossible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable collection point for the recycling of electrical and electronic e...

Отзывы: