background image

Page  2

Technical  Specifications

Precautions

CHECK  the  integrity  of  the  probe  after  having  removed  it  from  the  box.
Check  that  the  data  written  on  the  box  correspond  to  the  type  of  gas  used.
When  doing  the  electrical  connections,  follow  the  drawing  closely.
Any  use  of  the  detector  for  purposes  other  than  the  intended  one  is  considered  improper,  and  as  a
result  of  which  BEINAT  S.r.l.    therefore  disclaims  any  responsibility  for  possible  damages  caused  to
people,  animals  or  objects.

INSTALLATION
When performing  the  installation, please remind that if  you pierce the GS911K  container, it  will lose
its  properties  and  its  conformity  to  REGULATIONS.

TERMS and EXPECTATIONS: The installation of the GS911K detector, its ordinary and extraordinary
maintenance,  and  its  out  of  service  removal  at  the  end  of  the  functional  life  guaranteed  by  the
manufacturer, must be carried out by authorized and/or  specialized personnel.

Do not allow it to become wet.
The  detector  can  be  seriously  damaged  when  immersed  in  water.

Do not drop it.
Heavy  knocks  or  falls  during  transportation  or  installation  can  damage  the  appliance.

Avoid abrupt temperature fluctuations.
Sudden  temperature  variations  can  cause  condensation  and  the  probe  could  work  poorly.

Cleaning
Never  clean  the  device  with  chemical  products.  If  necessary,  wash  with  a  moist  cloth.
Absolutely  avoid  using  any  cloth  dipped  in  thinners,  alcohol  and  chemical  detergents.

Power supply .............................................................................................. 230Vac 50 Hz +/- 10%
Power consumption ...................................................................................................... 1W @ 230V
Range  of relay contact switching  .........................................10A 250V resistive - 5A 30Vdc  resistive
Explosive gas sensor  ....................................................................................................... Catalytic
Explosion Alarm Threshold  .................................................................................... At 10% of L.E.L.
Explosive gas detector alarm  threshold ......................................................................... Immediate
Sensor’s  faults  detected  by  Fault  Circuit  ...................................  Interruption,  short  circuit,  or  wear
Audible and  visual  signal  alarm by ............................................................... LED  diode and  buzzer
Test Phase Duration ..................................................................................................... 60 seconds
Functioning Temperature ....................................................................................    -10°C to +40°C
Functioning Humidity ............................................................................. 0÷90% RH non condensed
Electromagnetic  Compatibility “CE Reference Norms  “ ..................................................... EN 50270
External degree of protection ................................................................................................... IP42
Mounting  ..................................................................... External wall mount, or embedded box 503
Body material  .............................................................................................. ABS self-extinguishing
Dimensions  ................................................................................................................. 115x150x50
Warranty ............................................................................................................................. 3 years

The  installation  of  the  GS911K  detector,  its  ordinary  and  extraordinary  maintenance,  and  its  out
of  service  removal  at  the  end  of  the  functional  life  guaranteed  by  the  manufacturer,  must  be
carried  out  by  authorized  and/or  specialized  personnel.
The  CATALYTIC  technology  sensor  duration  is  guaranteed  for  6  years  (in  clean  air).
The  detector’s  functioning  temperature  ranges  from  -10°C  to  +  40°C.

WARNING!

The  CATALYTIC  probe  does  not  tolerate  a  gas  detection  exceeding  100%  of  L.E.L.,  with  consequent
natural  death  of  the  sensor.
Each  immediate  puff of  gas  that  exceeds  100%  of L.E.L.  takes  away  months  of  life  from  the  sensor.
The  detector  must  be  tested  by  simulating  the  presence  of  gas  by  issuing  it  from  a  pre-calibrated
testing  aerosol.
A  common  cigarette  lighter  near  the  sensor  does  not  guarantee  excellent  functioning.

Содержание GS911K

Страница 1: ...l reset solenoid valves or the continuous functioning to activate class A solenoid valves and sirens The relay free of voltage allows installation of multiple detectors on a single solenoid valve ensuring control of multiple dangerous environments The detector is complete with a special circuit that controls the catalytic sensor s efficiency level and signals any possible fault The external contai...

Страница 2: ...inners alcohol and chemical detergents Power supply 230Vac 50 Hz 10 Power consumption 1W 230V Range of relay contact switching 10A 250V resistive 5A 30Vdc resistive Explosive gas sensor Catalytic Explosion Alarm Threshold At 10 of L E L Explosive gas detector alarm threshold Immediate Sensor s faults detected by Fault Circuit Interruption short circuit or wear Audible and visual signal alarm by LE...

Страница 3: ...oles the relay will be set to impulse functioning That is when the alarm is triggered the relay will close the C and NA contacts for about 90 seconds and then will reopen them This is needed to prevent damaging some types of manual reset solenoid valve coils By opening the two poles the relay will be set to continuous functioning 5 Catalytic sensor for Methane or LPG explosive gas detection 6 TEST...

Страница 4: ... appliances will be turned off To complete the general test issue gas from a pre calibrated aerosol within 20 of L E L Testing using a common cigarette lighter could damage the sensor Installation measuresandpositioning The position of the detector is a crucial factor for its correct functioning during gas detection In order to obtain the maximum results from a device and minimize the probability ...

Страница 5: ...e alarm signal and the FAULT indicator light turn on together proceed as in the previous paragraph If the detector is issuing an alarm and does not shut off the devices connected to it Check that the wiring is correct and that the jumper that carries power to the relay has been set properly All relays are free from electrical power Check the drawing of the connections WARNING Actions to be taken i...

Страница 6: ...N C C NO 1 2 3 4 5 Electricalconnections WARNING Before connecting to the mains power ensure the voltage is correct Carefully follow the instructions and the connections according to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables Jumper for Relay working Mode 1 With the Jumper opened the relay works in continuos Mode 2 With the Jumper clos...

Страница 7: ...oltage One detector with 230V normally open valve WARNING All relays are free of voltage One or more detectors with 230V normally closed valve N Power Supply 230V ca Ph Electrovalve N C C NO 1 2 3 4 5 Ph N Power Supply 230V ca 1 2 3 4 5 1 2 3 4 5 Ph N Power Supply 230V ca 1 2 3 4 5 1 2 3 4 5 ...

Страница 8: ... 3 years from manufacturing date in agreement with the following conditions The components acknowledged as faulty will be replaced free of charge excluding the replacement of plastic or aluminium cases bags packing batteries and technical reports The device must arrive free of shipment charges to BEINAT S r l Defects caused by unauthorized personnel tampering incorrect installation and negligence ...

Отзывы: