Components and commands

1)  MAINS  connected  indication  LED  (ON).
2) FAULT indication LED.  If  this LED turns on, it means that the gas  detection  catalytic sensor  is not
working  efficiently  and  must  be  replaced  by  an  authorized  service  center.
3) ALARM  indication LED.  This LED  turns on  when room  gas  concentration  exceeds the  danger level.
4)  Jumper  to  select  the  relay  functioning  mode.  By  closing  the  two  poles,  the  relay  will  be  set  to
impulse  functioning.  That  is,  when  the  alarm  is  triggered,  the  relay  will  close  the  C  and  NA  contacts
for  about  90  seconds,  and  then  will  reopen  them.  This  is  needed  to  prevent  damaging  some  types
of  manual  reset  solenoid  valve  coils.  By  opening  the  two  poles,  the  relay  will  be  set  to  continuous
functioning.
5)  Catalytic  sensor  for  Methane  or  LPG  explosive  gas  detection.
6)  TEST  button.  This  button  is  used  to  simulate  a  gas  leak,  after  installation.
7)  Identification  label,  registration  number  and  manufacturing  year,  located  under  the  ABS  small
dome.

8

)  Label  of  the  gas  sensor  expiration  date.

This label must be applied by the technician during the installation 

and remembering that  the gas

sensor must be reviewed after 5 Years.

Dimensions

Содержание GS911K

Страница 1: ...l reset solenoid valves or the continuous functioning to activate class A solenoid valves and sirens The relay free of voltage allows installation of multiple detectors on a single solenoid valve ensuring control of multiple dangerous environments The detector is complete with a special circuit that controls the catalytic sensor s efficiency level and signals any possible fault The external contai...

Страница 2: ...inners alcohol and chemical detergents Power supply 230Vac 50 Hz 10 Power consumption 1W 230V Range of relay contact switching 10A 250V resistive 5A 30Vdc resistive Explosive gas sensor Catalytic Explosion Alarm Threshold At 10 of L E L Explosive gas detector alarm threshold Immediate Sensor s faults detected by Fault Circuit Interruption short circuit or wear Audible and visual signal alarm by LE...

Страница 3: ...oles the relay will be set to impulse functioning That is when the alarm is triggered the relay will close the C and NA contacts for about 90 seconds and then will reopen them This is needed to prevent damaging some types of manual reset solenoid valve coils By opening the two poles the relay will be set to continuous functioning 5 Catalytic sensor for Methane or LPG explosive gas detection 6 TEST...

Страница 4: ... appliances will be turned off To complete the general test issue gas from a pre calibrated aerosol within 20 of L E L Testing using a common cigarette lighter could damage the sensor Installation measuresandpositioning The position of the detector is a crucial factor for its correct functioning during gas detection In order to obtain the maximum results from a device and minimize the probability ...

Страница 5: ...e alarm signal and the FAULT indicator light turn on together proceed as in the previous paragraph If the detector is issuing an alarm and does not shut off the devices connected to it Check that the wiring is correct and that the jumper that carries power to the relay has been set properly All relays are free from electrical power Check the drawing of the connections WARNING Actions to be taken i...

Страница 6: ...N C C NO 1 2 3 4 5 Electricalconnections WARNING Before connecting to the mains power ensure the voltage is correct Carefully follow the instructions and the connections according to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables Jumper for Relay working Mode 1 With the Jumper opened the relay works in continuos Mode 2 With the Jumper clos...

Страница 7: ...oltage One detector with 230V normally open valve WARNING All relays are free of voltage One or more detectors with 230V normally closed valve N Power Supply 230V ca Ph Electrovalve N C C NO 1 2 3 4 5 Ph N Power Supply 230V ca 1 2 3 4 5 1 2 3 4 5 Ph N Power Supply 230V ca 1 2 3 4 5 1 2 3 4 5 ...

Страница 8: ... 3 years from manufacturing date in agreement with the following conditions The components acknowledged as faulty will be replaced free of charge excluding the replacement of plastic or aluminium cases bags packing batteries and technical reports The device must arrive free of shipment charges to BEINAT S r l Defects caused by unauthorized personnel tampering incorrect installation and negligence ...

Отзывы: