RELAY  SETTINGS
SW2  DIP-SWITCH  allows  to  choose  between  various  relay  settings.

COLLECTION  EXCLUSION:
Setting  SW1  it  is  possible  to  enable/disable  the  suppression  of  the  signaling  of  any  umderrange  in  the  input
signal  in  the  corresponding  zone.

Zone 1         Zone  2

(sensor)        (sensor)

page  7

After  making  all  the  connections  and  configurations,  the  system  can  be  powered

Micro-switches  1  Positive  safety

Micro-switches  2  Working  mode  of  the  main  alarm  relay

Zone 1      Zone  2

(sensor)        (sensor)

SW1.1

  ON:  Sensor  1  dead  band  suppression  DISABLED
  OFF:  Sensor  dead  band  suppression  ENABLED

SW1.2

ON:  Sensor  2  dead  band  suppression  DISABLED
OFF:  Sensor  dead  band  suppression  ENABLED

WARNING!

>  This  control  unit  is  NOT  built  for    installation  in  ATEX  classified  areas
>  To  meet  the  requirements  as  a  control  unit  according  to  the  standard  EN  60079-29-1:  2016,  the
DIP  switches  on  the  control  unit  must  be  set  to:  SW2.1:  ON,  SW2.2:  OFF,  SW3.2:  ON,  SW4.2:  ON.
>  All  the  wiring  of  the  remote  sensors  must  be  made  using  wires  with  a  minimum  section  of  1.5
mm2  and  no  longer  than  25  m.  Do  not  use  the  same  conduit  for  signal  and  power  cables.
>  In  case  of  installation  in  the  presence  of  strong  EMC  disturbances,    the  shielded  cables  use  is
strongly  recommended.  The  screen  must  be  connected  to  the  'Gnd'  terminal  of  the  interested
area  only  on  the  side  of  the  control  unit.
>  The  appliance  must  be  connected  to  the  power  supply  by  means  of  a  switch  capable  of
disco nnectin g  the  poles  in  complian ce  with  cu rrent  safety  standards  and  with  a  co ntact
separation  of  at  least  3  mm  in  all  poles.
>  The  installation  and  electrical  connections  of  this  appliance  must  be  carried  out  by  qualified
technicians  and  in  compliance  with  the  current  technical  and  safety  standards.
>  Be  sure  to  turn  off  the  power  before  wiring  the  device.
>  Safety  depends  on  the  installer  (whose  responsibility  is  to  set  up  a  detection  system  in
compliance  with  existing  standards,  both  European  and  national)  to  choose  the  correct  type  of
loads  to  be  connected  to  the  control  unit  and  the  correct  configuration  of  the  system  parameters.
In  case  of  doubt,  please  contact  the  distributor.

Switch  1  –  Selection  of  the  positive  safety
Position  ON:  the  positive  safety  function  is  enabled.
The  relay  is  energized  after  the  warm  up  phase  and  turns  off  when  the  BX280-AX  is  main  alarm
Position  OFF:  the  positive  safety  function  is  disabled.
The  relay  is  energized  only  when  the  BX280-AX  goes  into  the  main  alarm

Switch  2  -  Working  mode,  selection  of  the  main  alarm  relay
Position  OFF:  the  relay  remains  closed  until  the  RESET  button  is  pressed.  (continuous)
Position  ON:  the  relay  remains  closed  for  20  seconds,  and  then  disenergizes.  (impulse)

Содержание BX280-AX

Страница 1: ...ty Select the gas type to be detected toxic or explosive Choose the relay functioning mode pulsed or continuous Choose deadband exclusion mode A TEST button checks the efficiency of both the unit and connected probe to ensure total control of the BX280 AX Thanks to the Omega type format small and large systems can be built by exploiting the modularity of the DIN rail in the previously set electric...

Страница 2: ...the appliance Cleaning Never clean the device with chemical products If necessary wash with a moist cloth Technical Specifications Mains Power 110 230VAC 50 60Hz 10 Secondary Power Through Battery max 1 2 Ah Optional not provided 12 V 10 Battery Charger max 1 2 Ah controlled by the microprocessor The battery does not need maintenance Power Demand 6 W max 230V Power Demand 5 W max 12 VDC Relay Cont...

Страница 3: ...SG895 Pellistor ATEX Zone 1 See catalogue 0 100 LEL 4 20 mA 5 Y e s N O SG580 Catalyt ic I P 6 6 Zone 2 See catalogue 0 100 LEL 4 20 mA 5 Y e s N O SGF100 Catalytic I P 6 4 Zone 2 Methane 0 100 LEL 4 20 mA 5 Y e s Y e s SGF102 Catalytic I P 6 4 Zone 2 L P G 0 100 LEL 4 20 mA 5 Y e s Y e s SGF104 Optical Fluores I P 6 4 Zone 2 Oxyg en In 4 20 mA 5 Y e s Y e s SGF106 SemiCondut I P 6 4 Zone 2 F R E ...

Страница 4: ... by the battery in the absence of mains and flashes when the battery voltage is less than 10 8 V 3 LED SCALE CONCENTRATION GAS These LEDs light up in sequence based on the increase to the gas dispersed in the environment a When the first led turns on the gas concentration level has reached the first pre alarm threshold b When the second led turns on the gas concentration level has reached the seco...

Страница 5: ...rding to current performance standards 12 DIP SWITCH of the deadband suppression of the sensor 1 and 2 Setting these two switches ON or OFF it is possible to enable or disable the suppression of the signaling of any sub range in the input signal in the corresponding input Instead over ranges will always be reported Both conditions are indicated by the flashing of the Explosive Gas LED of the corre...

Страница 6: ...sensors as shown in the figure Power supply 110 230 VAC C NC NO C NC NO C NC NO PH N 4 5 6 7 8 9 10 Fault Pre Alarm Main Alarm ACTIVATION AND DEACTIVATION OF THE SENSORS To enable disable the sensor 1 act on the first switch of SW4 first DIP SWITCH from left To enable disable the sensor 2 act on the first switch of SW3 second DIP SWITCH from left When a sensor is excluded all the memories will be ...

Страница 7: ... screen must be connected to the Gnd terminal of the interested area only on the side of the control unit The appliance must be connected to the power supply by means of a switch capable of disconnecting the poles in compliance with current safety standards and with a contact separation of at least 3 mm in all poles The installation and electrical connections of this appliance must be carried out ...

Страница 8: ...on of gas gradually increasing from the enabled sensors and it is therefore possible to control the switching on and off of the LEDs and that all switch relay enabling the loads connected to them Depending on the input signal of the remote sensors the control units can be found in the following working condition NORMAL MODE the control unit receives a signal from the sensors corresponding to a gas...

Страница 9: ...mA normal operation 21 mA Over range 23 mA fault The following figure shows the conversion between mA and the corresponding gas concentration 0 60 120 200 240 300 337 mA Fault zone Over range area Under range area Fault zone 7 2 0 10 4 16 8 20 14 7 4 3 6 22 ppm Linear 5 0 4 8 13 16 20 22 mA Fault zone Over range area Under range area Fault zone 7 2 0 10 4 16 8 20 14 4 4 3 6 22 LEL Linear 5 3 8 3 8...

Страница 10: ...s and eventual battery Page 10 Example of a label WARNING Before connecting to the mains power ensure the voltage is correct Carefully follow the instructions and the connections according to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables An automatic cut off switch appropriately identified as devicesectioning of the detector should be inc...

Страница 11: ...oid valve Normally Closed with Positive Safety Connections of a solenoid valve Normally Closed without Positive Safety Page 11 110 230 VAC Electrical connection example If a 12Vdc solenoid valve is connected to BX280 AX and it does not work well Direct connection of 12VDC solenoid valves or sirens to BX280 AX is not possible An external power unit must always be used BX280 AX gives a max current o...

Страница 12: ...N 230 VAC 230 VAC If a 12VDC solenoid valve is connected to BX280 AX and it does not work well Direct connection of 12VDC solenoid valves or sirens to the BX280 AX is not possible An external power unit must always be used The BX280 AX gives a max current of 50mA Electrical Connections Connections to Positive Safety disabled and an external power supply for valve control and siren 12VDC ...

Страница 13: ...es of remote probes to this unit Therefore they should be positioned at different heights depending on the type of gas to be detected These heights are 30 cm from the lowest point of the floor in order to detect Heavy gases L P G etc 30 cm from the highest point of the ceiling in order to detect light gases Methane etc 160 cm from the lowest point of the floor in order to detect volatile gases CO ...

Страница 14: ... powered by the battery check that the 12Vdc power is correctly connected If the Fault LED lights up Check that the connecting cables from the BX280 ax to the probes are intact that the probes are properly powered and that the signal cable is correctly connected If the Over Load Probe LED lights up Check that the power polarity has not been inverted that no short circuit is present that the probes...

Страница 15: ...arked by two red parallels To enable maintenance mode based on regulations a manual command must be performed Follow the instructions below Once the manual command has been executed proceed as follows Plant maintenance RESET TEST Maintenance Test The simultaneous and prolonged pressing for 5 seconds of the TEST and RESET keys enables the test on mode in which the control unit does not switch the g...

Страница 16: ...xample sales points in case you buy a new and similar product local collection points waste collection center local recycling center etc By ensuring this product is disposed of correctly you will help prevent potential negative consequence for the environment and human health which could otherwise be caused by inappropriate waste handing of this product The recycling of materials will help to cons...

Отзывы: