Safety Precautions

Warning:

Battery may explode if mistreated. Do not recharge, disassemble or dispose
of in fire.

LA BATTERIE PEUT EXPLOSER EN CAS DE MAUVAISE MANIPULATION.
NE LA RECHARGEZ PAS, NE LA DÉMONTEZ PAS ET NE LA JETEZ
PAS DANS LE FEU.

This product contains a battery; this must only be changed in an area known
to be non-hazardous.

Replace the battery with a BR 2032 battery. Use of another type of battery
may present a risk of fire or explosion.

For use on a flat surface of a type 4X enclosure indoor use only.

Use minimum 75°C copper conductors only.

To make wiring connections to the power supply connector, follow the table
with cable and torque specifications below:

Terminal Block Connector

Wire Size AWG

Torque (Lb.In.)

X1/X100 Phoenix connectors

AWG 30 – 12

5 – 7

X1/X100 Anytek connectors

AWG 24 – 12

3.5

X1/X100 DECA connectors

AWG 24 – 12

7

These devices are Class 2 supplied programmable controllers (industrial PCs)
for the use in industrial control equipment and are intended to be (front)
panel mounted (Type 12 and 4x for indoor use only).

Caution:

The enclosure provides a degree of protection of at least IP20, but when installed in an
apparatus, it should meet IP65..

LE BOÎTIER OFFRE UN DEGRÉ DE PROTECTION D'AU MOINS IP20, MAIS
LORSQU'IL EST INSTALLÉ DANS UN APPAREIL, IL DOIT ÊTRE DE CLASSE IP65.

1.5 During Installation

The operator panel is designed for stationary installation on a planar surface,
where the following conditions are fulfilled:

no high explosive risks

no strong magnetic fields

no direct sunlight

no large, sudden temperature changes

Install the operator panel according to the accompanying installation
instructions.

Ground the operator panel according to the accompanying installation
instructions.

Only qualified personnel may install the operator panel.

Separate the high voltage, signal, and supply cables.

Make sure that the voltage and polarity of the power source is correct before
connecting the operator panel to the power outlet.

Beijer Electronics, MAEN275

9

Содержание BoX2 pro

Страница 1: ...BoX2 pro Installation Manual English MAEN275 2018 03...

Страница 2: ......

Страница 3: ...ts group companies assumes no responsibility for any errors that may appear in this document Read the entire installation manual prior to installing and using this equipment Only quali ed personnel ma...

Страница 4: ...Foreword Beijer Electronics MAEN275...

Страница 5: ...ctions to the Controller 12 2 1 2 Other Connections and Peripherals 13 3 TechnicalData 15 4 ChemicalResistance 17 4 1 MetalCasing 17 5 Operator Panel Drawings 19 5 1 Connectors 19 5 1 1 Communication...

Страница 6: ...Contents Beijer Electronics MAEN275...

Страница 7: ...ier cannot assume responsibility for actual use based onthe gures The supplierneither guarantees thatthe operator panel is suitable foryour particularapplication nor assumesresponsibilityforyour produ...

Страница 8: ...tion All deviceshave tobe supplied bya Class 2 powersupply Warning Only UL and cUL approved expansion units are allowed to be connected to the port designated EXPANSION At the moment there are no such...

Страница 9: ...blecontrollers industrialPCs forthe use in industrial controlequipment and are intended to be front panel mounted Type 12 and4x forindoor use only Caution The enclosure provides a degree of protection...

Страница 10: ...intenance operations disconnect the equipment from the electrical supply Replacingthe battery incorrectly mayresultin explosion Only use batteries recommended by the supplier Duringthe warrantyperiod...

Страница 11: ...e the connection to a side The mount canbe removed for access to all the mounting points shownabove The followingis needed Notools required standard usage A Phillips screwdriver formovement orremoval...

Страница 12: ...and polarity of the powersource is correct Separate high voltage cables from signal and supply cables Shielded communication cables are recommended 24V DC RS232 RS422 RS485 24V DC A D Controller Powe...

Страница 13: ...er Connections and Peripherals Cables peripheral equipment and accessories must be suitable forthe application and itsenvironment Forfurtherdetailsor recommendations please refertothe supplier Beijer...

Страница 14: ...Installation 14 Beijer Electronics MAEN275...

Страница 15: ...5 GB SSD eMMC Memory RAM 1 GB DDR3 NVRAM 128 kB Real time clock Yes Battery BR 2032 lithium battery replaceable Power consumption at rated voltage 5 W Fuse Internal DC fuse 3 14 AT 5 20 mm Power suppl...

Страница 16: ...Technical Data Parameter BoX2 pro UL approval Yes information available at UL com Marine certificates Information is available on www beijerelectronics com 16 Beijer Electronics MAEN275...

Страница 17: ...llowing chemicals at room temperature Butanol Nitric acid 3 Hydrochloric acid 5 Nitric acid 10 Isopropyl alcohol Phosphoric acid 43 Sodium hypochlorite 10 Turpentine Note If exposure to any of the abo...

Страница 18: ...Chemical Resistance 18 Beijer Electronics MAEN275...

Страница 19: ...ort 9 pin female Pin COM 1 COM 2 COM 3 1 RS 422 Tx RS 485 Tx Rx 2 RS 232 RxD 3 RS 232 TxD 4 RS 422 Rx RS 485 Tx Rx 5 GND GND 6 RS 422 Tx RS 485 Tx Rx 7 RS 232 RTS 8 RS 232 CTS 9 RS 422 Rx RS 485 Tx Rx...

Страница 20: ...Operator PanelDrawings 5 2 BoX2 pro Outline 128 86 78 14 39 Note A Step CAD file is available on the web site www beijerelectronics com 20 Beijer Electronics MAEN275...

Страница 21: ...terminalconnectoron the operatorpanel and the chassis of the panel see 2 in drawing above 2 Connect awire orgroundingbraid that is sized correctlyaccording to local electrical codes betweenthe chassi...

Страница 22: ...RJ45 RJ45 RJ45 Industrial Ethernet Operator panel Operator panel Operator panel Operator panel Shielded Short and unshielded 0 1 F 250 V 1 1 3 3 8 8 2 2 In some industrialunits forEthernet the RJ45 c...

Страница 23: ...withfoil and abraided shield D sub covers shouldbe shielded andthe shield shouldbe connected to the cover 360 where the cable enters Connect the shield at both ends Shielded cable Not same potential G...

Страница 24: ...e are anumberofheat generatingdevices the temperature at the top ofthe cabinet is considerably higherthan the temperature increase that would be expected All electronics are sensitive to heat The life...

Страница 25: ...tion against electric shock and UL 950 Note Here is an example that explains why a secure 24 V DC powersupply can be ruined by mixing 24 V relay contacts with 230 V AC relay contacts in a smaller cont...

Страница 26: ...forexample a USB memory stick keyboard orsimilar device is plugged in If anumberofunitsare connectedthat have a0 Vand a groundconnection and these are connected to various groundingpoints there is a...

Страница 27: ...e shield mustbe grounded at one end The other end is usuallygrounded but with longerdistances or whenthere is adifference in the ground potential the shield should be connected tothe ground via 0 1 F...

Страница 28: ...Head office Beijer Electronics AB Box 426 201 24 Malm Sweden www beijerelectronics com 46 40 358600...

Отзывы: