Additional Installation Tips
Note:
The grounding wires should be short and the conductor should have a large area.
A long, thin grounding wire has a very high impedance (resistance) at high frequencies
and does not guide disturbances to the ground.
Multi-wire conductors are better than single wire conductors with the same area.
A braided conductor wire with the same area is even better. The best is a short, thick
grounding braid.
6.2 Ethernet Connection in the
Operator Panel
1
2
3
4
5
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
Industrial Ethernet
Operator panel
Operator panel
Operator panel
Operator panel
Shielded
Short and
unshielded
0.1
μ
F
250 V
1-1
3-3
8-8
2-2
In some industrial units for Ethernet, the RJ45 contact’s shield is connected to the
chassis via a capacitor, see 1 in drawing above.
The operator panel’s Ethernet shield is directly connected to the chassis, see 2 in
drawing above.
1. Check whether the other Ethernet unit has its shield directly grounded or
grounded via a capacitor.
Note:
In many cases, connecting the shielded Ethernet cabling to the chassis at both ends is
inappropriate. Hum or grounding loops can occur. Unshielded cabling may even result
in fewer communication errors.
22
Beijer Electronics, MAEN275
Содержание BoX2 pro
Страница 1: ...BoX2 pro Installation Manual English MAEN275 2018 03...
Страница 2: ......
Страница 4: ...Foreword Beijer Electronics MAEN275...
Страница 6: ...Contents Beijer Electronics MAEN275...
Страница 14: ...Installation 14 Beijer Electronics MAEN275...
Страница 18: ...Chemical Resistance 18 Beijer Electronics MAEN275...
Страница 28: ...Head office Beijer Electronics AB Box 426 201 24 Malm Sweden www beijerelectronics com 46 40 358600...