926000127
Figure 2. Wiring Diagram
CHARGER BOARD
AC INPUT:
LED
INDICATORS
TRANSFORMER
RED - 347V
ORANGE - 277V
BLACK - 120V
WHITE - NEUTRAL
GREEN - GROUND
TEST
BUTTON
DC OUT
FUSE(S)
TO
BATTERY
* Each pair matches rated DC output voltage.
**Transformer may be separate from
board in some modules.
Representation may vary from actual.
+
1 or 2
pairs
LAMP OUT
1 or 2
pairs
Problem
Possible Reason
Solution
Emergency lamps do not turn
ON in emergency mode
DC output fuse has blown, due to overload
or short-circuit fault in lamp circuit
Locate and clear fault
Replace fuse
Lamp(s) are faulty
Replace lamp(s)
Circuit board is defective
Replace circuit board
Battery is faulty
Replace battery
Emergency lamps do not stay
ON for required minimum
duration
Battery is not fully charged
Recharge battery for up to 24 hours
Battery is faulty
Replace battery
Emergency lamps turn ON
when AC is present
Circuit board is faulty
Replace circuit board
BASIC TROUBLE SHOOTING:
SAVE THESE INSTRUCTIONS