Manual Tests will not change the time intervals and durations set for automatic tests.
Use the MANUAL TEST menu to perform operations described in the following table:
EMERGENCY
Note:
Commands in the EMERGENCY menu will only affect luminaires that are not powered from
the mains, i.e. they are lit in a state of emergency.
When power from the mains to a luminaire is cut off, the luminaire will turn on and run on bat-
tery supply. As long as its battery still has energy stored, a luminaire can be sent the following
commands:
- Disable the state of emergency: the luminaire turns off; it can be turned back on by enabling
the state of emergency.
- Enable the state of emergency: the luminaire turns on
- Turn off: the luminaire is turned off permanently; it cannot be turned back on unless the lumi-
naire itself detects power being fed from the mains. This feature can be useful to preserve
battery power when, for instance, the power supply to the system needs to be cut off for a
long period.
To:
go to (menu):
run a Functional Test
FUNCTION
run an unlimited time test that will stop when
the battery is completely discharged
ON INDEFINITELY
an Autonomy Test of 1 hour
1 h AUTONOMY TEST
stop any test
STOP TEST
To:
go to (menu):
disable the state of emergency
EM. OFF
enable the state of emergency
EM. ON
permanently turn off the luminaire
TO TURN THEM OFF