Chapter 1
1
Bedrock UPS.500 User Manual - BRDOC120_008
9/2/21
Bedrock UPS.500 Overview
The Bedrock UPS.500 is an Ethernet enabled, 24 V 12 Ah lithium
-
ion uninter
-
ruptible power supply (UPS) designed for use in industrial automation applica
-
tions. Product specifications, installation instructions, and operating information
are included in this manual.
NOTE:
To avoid depleting UPS.500 batteries, the UPS.500
must not be stored without being powered on for
more than ten years. Power up the UPS.500 for at least
four hours within a ten year period to avoid depletion
of the UPS.500 batteries.
NOTE:
Remove the enable connector while storing the
UPS.500.
The Bedrock UPS.500 supports 10/100 Mbit Ethernet IPv4 and IPv6
communication. Network clock synchronization is provided using the IEEE
1588 Precision Time Protocol (PTP) for devices that support the protocol.
A real
-
time clock (RTC) provides up to 21 days of hold up time in the event of a
loss of UPS.500 battery power (product revision D or later).
An OPC UA compliant server provides access to diagnostic and status
information and configuration parameters. OPC UA tags are available using an
OPC UA client or the Bedrock IDE.
The UPS.500 can be installed in either panel or pipe mount configurations. The
enclosure is compliant with IP66/67 (dust tight and protection against water jets
and immersion) and NEMA ratings 4, 5, and 6 (water tight, dust tight, and
immersible).
Bedrock Automation has received several certifications for FCC, CE, IEC, and
EMP testing as well as UL approval for Industrial Control Equipment (UL 508).
See Appendix C, Certifications, Approvals, and Testing for a complete list.
Additional features include:
• tri
-
colored status LED and network activity LEDs
• an enable connector that can be removed to protect against
inadvertent power up
• two type C relay outputs.