2–48
M-3520 Instruction Book
2.5
Oscillograph Recorder
The oscillograph recorder provides comprehensive
data recording of all monitored waveforms (voltage,
current, control/status inputs and output contacts) at
16 samples per cycle. Oscillograph data can be
downloaded using the communications ports to any
IBM compatible PC running M-3822 IPScom
®
communications software. Once downloaded, the
waveforms can be examined using M-3801D IPSplot
®
PLUS Oscillograph data analysis software.
The recorder can be triggered manually through serial
communications using IPScom or automatically using
programmed control/status inputs (IN1–6) or
programmed output contact (OUT1–8) operation.
When untriggered, the recorder continually records
waveform data, keeping the most recent data in
memory. The recorders memory may be partitioned
into any one of the following:
•
one 170 cycle record
•
two 112 cycle records
•
three 84 cycle records
•
four 68 cycle records
When configured with a specific post trigger delay,
the oscillographic record will show post-trip data in
addition to pre-trip data, and keeps a snapshot of
waveform data in its memory for downloading using
IPScom.
■
■
■
■
■
NOTE:
If more events or triggers occur before
downloading than the number of
partitions being used, the oldest record
will be overwritten. Records are not
retained if power to the relay is
interrupted.
A post trigger delay of 5% to 95% may be specified.
After triggering, the recorder will continue to store
data for the programmed portion of the total record
before rearming for the next record. For example, a
setting of 80% will result in a record with 20% pre-
trigger and 80% post trigger data.
The
OSC TRIG
LED on the front panel will indicate
when oscillograph data has been recorded and is
available for download.
RECORDER PARTITIONS
4
TRIGGER INPUTS
I6 i5 i4 i3 i2 i1
TRIGGER OUTPUTS
o8 o7 o6 o5 o4 o3 o2 o1
POST TRIGGER DELAY
5%
“Recorder Partitions” designates the number of parti-
tions that the oscillograph recorder will use. Whenever
this number is changed, the post-trigger delay is auto-
matically reset to 5%
The trigger inputs designate the control/status inputs
whose operation will trigger the recorder to record an
event. Operation is “OR”ed if more than one input is
selected.
The trigger outputs are relay output contacts whose
operation will trigger the recorder to record an event.
Operation is “OR”ed if more than one output is selected.
The post trigger delay assigns the amount, in percent, of
the individual data record occurring after the trigger. The
remaining portion consists of pre-trigger data.
The setup of the Oscillograph Recorder includes the following settings:
Содержание M-3520
Страница 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Страница 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Страница 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Страница 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Страница 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Страница 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...