Beckhoff Automation GmbH & Co. KG
Hülshorstweg 20
33415 Verl
Germany
Phone: +49 5246 9630
[email protected]
www.beckhoff.com

More Information: 

www.beckhoff.com/ps2001-2410-0000

Содержание PS2001-2410-0000

Страница 1: ...Documentation EN PS2001 2410 0000 Power supply 24 V DC 10 A 1 phase 2020 10 08 Version 1 0 ...

Страница 2: ......

Страница 3: ...ide and operating elements 21 3 13 EMC 22 3 14 Environment 23 3 15 Protective functions 24 3 16 Safety features 24 3 17 Dielectric strength 25 3 18 Declaration of conformity and approvals 26 3 19 Dimensions and weight 27 4 Application notes 28 4 1 Peak current capability 28 4 2 Back feeding loads 29 4 3 External input protection 29 4 4 Output circuit breakers 29 4 5 Series connection 30 4 6 Parall...

Страница 4: ...Table of contents PS2001 2410 0000 4 Version 1 0 ...

Страница 5: ...uses with a short peak current The power supply unit is part of the PS2000 family and has a width of 39 mm A DC OK LED and a potential free relay contact monitor the status of the output voltage Thanks to approvals for the process industry ATEX IECEx shipbuilding DNV GL and the semiconductor industry SEMI F47 the power supply unit can be used in a wide range of applications Overview of technical d...

Страница 6: ...r are registered trademarks of and licensed by Beckhoff Automation GmbH Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owners Patent Pending The EtherCAT Technology is covered including but not limited to the following patent applications and patents EP1590927 EP1789857 EP1456722 EP2137893 DE1020151057...

Страница 7: ...s device is designed for installation in a housing and is intended for general professional use for example in industrial control systems or office communication and measuring equipment Do not use this power supply in installations where a malfunction could cause serious injury or danger to human life Exclusion of liability All the components are supplied in particular hardware and software config...

Страница 8: ...can be considered safe For the end product a suitable housing must be provided which has a minimum protection class of IP54 and meets the requirements of EN 60079 0 NOTE Instructions for use in potentially explosive atmospheres The device is suitable for use in the following areas Class I Division 2 Groups A B C D and for use in Group II environments of Category 3 Zone 2 Classification ATEX EPS 15...

Страница 9: ...with tolerances e g AC 230 V 10 The calculated total range then indicates the working range of the device Example DC 12 V refers to a 12 V battery regardless of whether it is fully charged 13 7 Vdc or discharged 10 Vdc 230 Vac A value followed by the unit Vac or Vdc is an instantaneous value that does not contain any additional tolerances 50 Hz vs 60 Hz Unless otherwise specified AC 100 V and AC 2...

Страница 10: ...rent power factor over output current Power factor Typ 0 99 0 99 0 97 At 24 V 10 A see Fig Input current over out put current power factor over output current Peak factor Typ 1 5 1 5 1 65 At 24V 10A Start up delay Typ 300ms 290ms 240ms See Fig Input voltage range switch on behav ior definitions Rise time Typ 30ms 30ms 30ms At 24 V 10 A constant current load 0 mF load capacity see Fig Input voltage...

Страница 11: ...Technical data mounting wiring PS2001 2410 0000 11 Version 1 0 Fig 2 Input current over output current power factor over output current ...

Страница 12: ... Max 375 Vdc Continuous according to IEC 62477 1 Turn on voltage Typ 80 Vdc static Shut down voltage Typ 70 Vdc static Typ 55 Vdc Dynamic value for up to 250ms max Instructions for DC operation Fig 3 Wiring for DC input Use a battery or a comparable DC source Operation on the DC link of frequency converters is not recommended and may lead to defects or malfunctions Connect the positive pole to L a...

Страница 13: ...first few microseconds after switching on is not taken into account AC 100V AC 120V AC 230V Input inrush current Max 11Apeak 7Apeak 11Apeak At 40 C cold start Typ 9Apeak 6Apeak 6Apeak At 25 C cold start Typ 9Apeak 6Apeak 9Apeak At 40 C cold start Inrush energy Max 0 1A s 0 1A s 0 4A s At 40 C cold start Fig 4 Typical switch on behavior at nominal load 120Vac input voltage and 25 C ambient temperat...

Страница 14: ...ve 20V See chapter on Peak current capability 28 for further peak current mea surements For AC 100V networks the pulse length is shorter than 12ms Overload behavior Continuous cur rent Output voltage 13Vdc see Fig Output voltage over output current typ Hiccup mode2 Output voltage 13Vdc see Fig Output voltage over output current typ Short circuit current Min 12 5A3 Load impedance 45mOhm see Fig Sho...

Страница 15: ...time AC 100V AC 120V AC 230V Power failure Hold up time Typ 73ms 73ms 73ms At 24V 5A see Fig Hold up time over input voltage Min 55ms 55ms 55ms At 24V 5A see Fig Hold up time over input voltage Typ 37ms 37ms 37ms At 24V 10A see Fig Hold up time over input voltage Min 28ms 28ms 28ms At 24V 10A see Fig Hold up time over input voltage Fig 8 Hold up time over input voltage switch off behavior definiti...

Страница 16: ... voltage The contact opens when the output voltage drops more than 10 below the set output voltage Short drops are extended to a signal length of 100ms Drops that are shorter than 1ms are ignored Switching hysteresis 1 V Contact load capacity Maximum 60Vdc 0 3A 30Vdc 1A 30Vac 0 5A ohmic load Minimum permissible load 1mA at 5Vdc Insulation voltage See the dielectric strength table in the chapter on...

Страница 17: ...W 7 1W At 24V 5A Typ 18 3W 16 4W 12 1W At 24V 10A Typ 23 4W 21 7W 14 8W At 24V 12A Extra Power The average efficiency is based on assumptions for a typical application with the power supply unit operating at 25 of the nominal load during 25 of the time 50 of the nominal load during 25 of the time 75 of the nominal load during 25 of the time and 100 of the nominal load during the remaining time Fig...

Страница 18: ...TBF MTBF stands for Mean Time Between Failure which is calculated from the statistical failure rate of the components and indicates the reliability of a device It is a statistical representation of the probability of equipment failure and does not necessarily represent the service life of a product The MTBF number is a statistical representation of the probability of equipment failure An MTBF numb...

Страница 19: ...tions Use suitable copper cables that are designed for at least the following operating temperatures 60 C for ambient temperatures up to 45 C 75 C for ambient temperatures up to 60 C and 90 C for ambient temperatures up to 70 C Observe the national installation rules and regulations Make sure that all single wires of a strand are connected to the terminal Unused terminals should be tightened firml...

Страница 20: ...Technical data mounting wiring PS2001 2410 0000 20 Version 1 0 3 11 Functional wiring diagram Fig 13 Functional wiring diagram ...

Страница 21: ... poles positive output three identical negative poles negative output Potentiometer for the output voltage Designation C Description Potentiometer cover Open the flap to adjust the output voltage Factory setting 24 1 V DC OK LED Designation D Description LED green Lights up when the output voltage is within the expected range and the DC OK contact is closed DC OK relay contact Designation E Descri...

Страница 22: ... 2 1 Limit values for the DC current connection according to EN 61000 6 3 are met Interference emission EN 55011 EN 55022 Class B Harmonic input current EN 61000 3 2 Class A met between 0A and 12A load Class C met between 6A and 12A load Class A met between 0A and 12A load Class C met between 6A and 12A load Voltage fluctuations flicker EN 61000 3 3 Requirements met 1 This device complies with FCC...

Страница 23: ...n altitude 15W 1000m or 5 C 1000m Above 2000m see Fig Output current over installation altitude Overvoltage category III According to IEC 62477 1 installation altitudes up to 2000m II According to IEC 62477 1 installation altitudes between 2000m and 6000m Degree of pollution 2 According to IEC 62477 1 non conductive LABS free The device does not release any silicones or other paint wetting impairm...

Страница 24: ...olt age the load and the installation type Protection against input transients MOV metal oxide varis tor For further information see EMC chapter 22 Input fuse Included Non replaceable slow blow fuse with high load capacity 3 16 Safety features Safety features Input output isolation Double or reinforced electrical isolation SELV IEC EN 60950 1 PELV IEC EN 60204 1 EN 62477 1 IEC 60364 4 41 Protectio...

Страница 25: ...ngth B When checking the input to DC OK make sure that the maximum voltage between DC OK and the output is not exceeded column D When performing the test we recommend connecting the DC OK contact pins and the output contact pins A B C D Type test 60s 2500Vac 4000Vac 1000Vac 500Vac Component test 5s 2500Vac 2500Vac 500Vac 500Vac Field test 5s 2000Vac 2000Vac 500Vac 500Vac Setting the cut off curren...

Страница 26: ...ation of conformity UL Certificate UL 508 Applicable for US and Canada UL Certificate Class I Division 2 Groups A B C D location and for use in Group II Category 3 Zone 2 environments Applicable for US and Canada Classification ATEX EPS 15 ATEX 1 101 X II 3G EX ec nC IIC T4 Gc Classification IECEx EPS 20 0046X DNV GL ...

Страница 27: ...o the depth of the device to calculate the total installation depth required DIN rail Use 35 mm DIN rails according to EN 60715 or EN 50022 with a height of 7 5 or 15mm Weight 600 g Housing material Housing Aluminum alloy Cover Galvanized steel Installation clearances See chapter on Safety instructions and installation requirements 8 Fig 17 Front side view PS2001 2410 0000 all specifications in mm...

Страница 28: ...acitive load The peak current capability also ensures safe operation of downstream circuit breakers of load circuits The load circuits are often individually fused with circuit breakers or fuses In the event of a short circuit or overload in a circuit the fuse or circuit breaker needs a certain amount of overcurrent to open in time This prevents a voltage drop in adjacent circuits The additional c...

Страница 29: ... off the output voltage The absorbing energy can be calculated according to the large built in output capacitor indicated in the output data 4 3 External input protection The device is tested and approved for circuits that are fused up to 30A UL and 32A IEC External protection is only required if the supply line has a protection that is higher than this Also check the local regulations and require...

Страница 30: ... 9 m B 13A 2 m 2 m 3 m 6 m Don t forget to double the distance to the load or the cable length when calculating the total cable length plus and minus cable 4 5 Series connection Power supplies of the same type can be connected in series to increase the output voltages As many devices can be connected in series as necessary as long as the sum of the output voltages does not exceed 150Vdc Voltages w...

Страница 31: ...rated current of 15A or 16A is required at each output Alternatively a diode can be used Energize all devices at the same time to avoid overload hiccup mode It may also be necessary to ramp up and shut down the input power turn off for at least five seconds if the output was in hiccup mode due to overload or short circuit and the required output current is higher than the current of a device Restr...

Страница 32: ...ecoupling diode between the power supply and the battery Make sure that the output current of the power supply is below the permissible charging current of the battery Only use matching batteries when connecting 12V types in series Make sure that the ambient temperature of the power supply remains below 40 C The reverse current to the power supply battery discharge current is typically 3 5mA when ...

Страница 33: ...230Vac 230Vac Load 24V 8A 80 24V 10A 100 24V 8A 80 24V 10A 100 Temperature inside the housing 48 6 C 53 8 C 42 0 C 48 1 C Temperature outside the housing 26 3 C 26 6 C 25 8 C 26 2 C Temperature increase 22 3K 27 3K 16 2K 21 9K 4 11 Installation positions Mounting positions that deviate from the standard mounting position require a reduction of the continuous output power or a limitation of the max...

Страница 34: ...Application notes PS2001 2410 0000 34 Version 1 0 Fig 27 Mounting position C table mounting Fig 28 Mounting position D horizontal clockwise Fig 29 Mounting position E horizontal counterclockwise ...

Страница 35: ...duct PS2001 2405 0000 Fig 31 Wall mounting Front view side view hole pattern with example product PS2001 2405 0000 ZS5301 0005 Bracket for side mounting This bracket is used to mount the power supply unit laterally with or without a DIN rail The two aluminum brackets and the black plastic slider of the device must be removed to allow the steel brackets to be mounted For lateral DIN rail mounting t...

Страница 36: ...Appendix PS2001 2410 0000 36 Version 1 0 Fig 32 Lateral mounting with and without DIN rail brackets Fig 33 Installation dimensions Angle for side mounting ...

Страница 37: ... PS2001 2410 0000 37 Version 1 0 5 2 Documentation issue status Version Comment 1 0 First public issue 0 3 Complements corrections 0 2 Complements corrections 0 1 Preliminary documentation for PS2001 2410 0000 ...

Страница 38: ...ckhoff components there Beckhoff Support Support offers you comprehensive technical assistance helping you not only with the application of individual Beckhoff products but also with other wide ranging services support design programming and commissioning of complex automation systems and extensive training program for Beckhoff system components Hotline 49 5246 963 157 Fax 49 5246 963 9157 e mail ...

Страница 39: ......

Страница 40: ...Beckhoff Automation GmbH Co KG Hülshorstweg 20 33415 Verl Germany Phone 49 5246 9630 info beckhoff com www beckhoff com More Information www beckhoff com ps2001 2410 0000 ...