Operation
EL2912
41
Version: 1.0.0
Index
Name
Meaning
Flags
Default
F984:01
Voltage C2
Voltage µC2
RO
0
dec
F984:02
Temperature C1
Temperature µC1
RO
0
dec
F984:03
Firmware CRC C1
CRC of the firmware on µC1
RO
-
F984:04
Vendor data CRC C1 CRC of the vendor data on µC1
RO
-
Index F985
hex
: Device Info Data C2
CoE object F985
hex
currently displays internal temperature and voltage values for the TwinSAFE component.
Index
Name
Meaning
Flags
Default
F985:01
Voltage C1
Voltage µC1
RO
0
dec
F985:02
Temperature C2
Temperature µC2
RO
0
dec
F985:03
Firmware CRC C2
CRC of the firmware on µC2
RO
-
F985:04
Vendor data CRC C2 CRC of the vendor data on µC2
RO
-
Diagnostics history
Any errors, which occur during operation of the TwinSAFE component, such as overtemperature or
undervoltage, are entered in the diagnostics history with a corresponding timestamp.
Index F100
hex
: FSLOGIC status
The CoE object F100
hex
shows the current status of the TwinSAFE component.
Index
Name
Meaning
Flags
Default
F100:01
Safe Logic State
Status of the internal logic:
0: OFFLINE
1: RUN
3: SAFE
6: START
8: PREPARE
10: RESTORE
11: PROJECT-CRC-OK
RO
0
bin
F100:02
Cycle Counter
Life cycle counter, which is incremented with each TwinSAFE logic
cycle.
RO
0
bin
The following table contains a description of all values of the index F100
hex
SubIndex 01
.