Commissioning

SCT5xxx

34

Version: 1.0

4.6

Description of the User Interface SCT5xxx

The SCT5xxx have three user selectable parameters, for each of which 3-5 different values can be selected.
The simple and intuitive user interface is located on the top of the device and is used to configure the
transformer with three buttons located below the interface. These buttons can only be operated with a tool
that prevents unintentional and unauthorized access in accordance with the applicable product standards.
The interface also has a test button and a status LED for visual indication.

Fig. 23: User interface with input and test button

1. Power-on/ Status LED

The LED lights up green with heartbeat characteristic

*)

 during normal operation with low residual currents. If

the color changes to red with heartbeat characteristic, the measured TRMS residual current is higher than
the rated RC limit.

The LED flashes green during start-up. Continuous red light in combination with several flashing green LEDs
of the "Rated RC limit" group indicates an error state.

*) The light intensity of the status LED changes continuously with a heartbeat characteristic to signal the correct execution of the soft-
ware and to indicate that the SCT is in correct operational mode.

2. Error codes

LEDs (flashing), left group

Diagnosis

2x

Input voltage outside permissible range

3x

Relay activated too often

4x

Overtemperature

5x

Internal error

3. Test button

The test button is used to activate the test sequence for testing the operation of the SCT. If the test is
successful, the relay is activated and the LED lights up red.

If the relay is locked due to too many activations, pressing the button for 3 seconds will reset the state when
the differential current is normal.

Содержание SCT Series

Страница 1: ...Documentation EN SCT5xxx Ring type current transformer for differential current 0 2 A type B B all current sensitive ISO62020 1 conform 2022 09 29 Version 1 0...

Страница 2: ......

Страница 3: ...r 14 3 Technical data 23 3 1 SCT5xxx Ring type current transformer for differential current size 5 23 3 1 1 SCT5564 23 4 Commissioning 26 4 1 Mounting instructions mounting options 27 4 2 Measurement...

Страница 4: ...Table of contents SCT5xxx 4 Version 1 0...

Страница 5: ...rCAT P Safety over EtherCAT TwinSAFE XFC XTS and XPlanar are registered trademarks of and licensed by Beckhoff Automation GmbH Other designations used in this publication may be trademarks whose use b...

Страница 6: ...he components are supplied in particular hardware and software configurations appropriate for the application Modifications to hardware or software configurations other than those described in the doc...

Страница 7: ...ged The devices described are intended for installation by qualified electricians and may only be installed in electrical plant rooms or in closed housings Any other use or the disregard of these appl...

Страница 8: ...mechanical engineering through to solutions for test benches with particularly high requirements for accuracy The choice of the right product category 14 depends on the type of usage Whilst the data...

Страница 9: ...windings on the primary side and a larger number of windings on the secondary side The current to be converted flows through the primary side The windings are usually wound on an alternating magnetic...

Страница 10: ...s According to DIN VDE 0141 01 2000 paragraph 5 3 4 current and voltage transformers for nomi nal voltages from Um 3 6 kV must be grounded on the secondary side For low voltages Um 1 2 kV grounding is...

Страница 11: ...of the continuous current in the primary winding at which the overtemperature does not exceed the value specified in the standard with the secondary winding loaded with the rated load Rated short time...

Страница 12: ...nsformers is fundamentally different Fig 4 Principle fluxgate current measurement technology The measuring principle of the SCT5xxx is based on a differential current measurement of two oppositely exc...

Страница 13: ...ents at frequencies up to 100 kHz This makes this differential current transformer compatible with a wide range of industrial applications loads and power sources With its user selectable settings thi...

Страница 14: ...ct overview SCT5xxx 14 Version 1 0 2 3 Product categories SCTxxxx current transformer Breakdown of the type designation of the SCT current transformer Fig 6 Designation key of the SCT current transfor...

Страница 15: ...current transformers would quickly hit their limits on the basis of this physical principle The SCT0xxx coil current transformers with electrical isolation are specially designed for these low primary...

Страница 16: ...stallation spaces e g directly in the sub distribution unit Two current transformers are attached to the DIN rail while the third current transformer is plugged into the fastened current transformers...

Страница 17: ...The SCT2xxx series offers a large selection of ring type current transformers for primary currents from 60 to 2500 A in six sizes and two accuracy classes The innovative screwless connection technolo...

Страница 18: ...onductor 43 7 mm size 3 SCT2321 Accuracy class 0 5 Primary current 0 800 A AC 1000 A AC Secondary current 1 A AC Max diameter round conductor 43 7 mm size 3 SCT2411 Accuracy class 1 Primary current 0...

Страница 19: ...rmers in accuracy class 0 5 3 phase ring type current transformers SCT3111 Accuracy class 1 Primary current 3 x 0 50 A AC to 3 x 0 150 A AC Secondary current 1 A AC Max diameter round conductor 13 5 m...

Страница 20: ...ere Monitoring residual currents with the SCT5xxx in real time in a power system opens up the possibility of evaluating the condition of the electrical insulation based on the actual measured value so...

Страница 21: ...conductor 18 5 mm size 3 SCT6321 Accuracy class 0 5 Primary current 0 200 A AC 0 250 A AC Secondary current 1 A AC Max diameter round conductor 18 5 mm size 3 SCT6411 Accuracy class 1 Primary current...

Страница 22: ...ize 1 SCT7125 Accuracy class 0 5 Primary current 0 400 A AC Secondary current 5 A AC Max diameter round conductor 20 mm size 1 SCT7215 Accuracy class 1 Primary current 0 500 A AC 0 600 A AC Secondary...

Страница 23: ...0 4 A RMS for I n 30 300 mA 2 A RMS for I n 0 5 1 A Resolution 0 01 mA Update interval 1 ms 1 kHz Measurement uncertainty 2 typ 5 max for 10 400 Hz 3 typ 7 max for DC 10 kHz relative to full scale val...

Страница 24: ...ion Protection rating IP20 Connection secondary DFMC 1 5 3 5 2x5way PN 1790519 or compatible Conductor cross section secondary 0 2 1 5 mm 16 24 AWG Strip length 10 mm Size 5 Dimensions W x H x D 151 3...

Страница 25: ...Technical data SCT5xxx 25 Version 1 0 Fig 15 Side view front view all dimensions in mm...

Страница 26: ...ectric shock and burns Make sure that the details on the name plate and in the Technical data correspond to the operating pa rameters of the system Switch the system off before commencing with the ins...

Страница 27: ...d in the scope of delivery for this Fig 16 Mounting SCT5xxx Fastening the base plate with screws in the four holes Free suspension on the cable with the help of cable ties through the hooks on the bac...

Страница 28: ...Commissioning SCT5xxx 28 Version 1 0 Fig 18 Center conductors...

Страница 29: ...Commissioning SCT5xxx 29 Version 1 0 4 2 Measurement circuit example SCT5xxx Fig 19 Use in single phase as well as 3 and 4 pin three phase systems...

Страница 30: ...3 Connection Fig 20 Connection Connection point Description 1 24 Vdc 2 Relay ground 3 0 Vdc 4 Relay NC contact 5 0 Vdc 6 Relay NO contact 7 0 Vdc 8 External test button contact 1 9 Analog 4 20 mA out...

Страница 31: ...RC limit details in the electrical specifications tables After these intermediate steps the TRMS value of the differential current is ready to be output to the analog 4 20mA output However the behavio...

Страница 32: ...Commissioning SCT5xxx 32 Version 1 0 Fig 21 SCT5xxx block diagram...

Страница 33: ...lso suggests a suitable frequency range and integration time Required steps Activate the auto setting by pressing the Rated RC limit and Integration time buttons simultaneously for more than 3 seconds...

Страница 34: ...olor changes to red with heartbeat characteristic the measured TRMS residual current is higher than the rated RC limit The LED flashes green during start up Continuous red light in combination with se...

Страница 35: ...current levels the user can tolerate in the electrical power system before system testing or maintenance is required 5 Frequency range FR Refers to the measurement bandwidth for the differential curr...

Страница 36: ...explains the standard Where a circuit is permanently monitored by an RCM in accordance with IEC 62020 it is not necessary to measure the insulation resistance if the function of the RCM is correct IE...

Страница 37: ...perfect insulation and cannot be technically separated Also due to inductances e g motor high current peaks can be generated during the switch on processes which can lead to relay tripping at the RCD...

Страница 38: ...Appendix SCT5xxx 38 Version 1 0 6 Appendix 6 1 Documentation issue status Version Comment 1 0 First public issue 0 2 Corrections complements 0 1 Preliminary version...

Страница 39: ...here Beckhoff Support Support offers you comprehensive technical assistance helping you not only with the application of individual Beckhoff products but also with other wide ranging services support...

Страница 40: ......

Страница 41: ...Beckhoff Automation GmbH Co KG H lshorstweg 20 33415 Verl Germany Phone 49 5246 9630 info beckhoff com www beckhoff com More Information www beckhoff com SCT5xxx...

Отзывы: