KL401x and KL402x
3
Technical data
Technical data
KL4011
KL4021
KL4012
KL4022
Number of outputs
1
1
2
2
Power supply
24 V
DC
via the power contacts
(alternatively 15 V
DC
with power supply unit terminal KL9515)
Signal voltage
0 ... 20 mA
4 ... 20 mA
0 ... 20 mA
4 ... 20 mA
Load
< 500
Ω
(short-circuit-proof)
Accuracy
± 0.5 LSB linearity error, ± 0.5 LSB offset error
±0.1% of the full scale value
Resolution
12 bits
Electrical isolation
500 V
rms
(K-Bus/signal voltage)
Conversion time
~ 1.5 ms
Current consumption from K-
Bus
typically 60 mA
Bits width in process image
Output: 1 x 16 bits of data
(1 x 8 bit control/status optional)
Input: 2 x 16 bits of data
(2 x 8 bit control/status optional)
Configuration
no address or configuration settings
Weight
approx. 80 g
Operating temperature
0°C ... +55°C
Storage temperature
-25°C ... +85°C
Relative humidity
95 % no condensation
Vibration / shock resistance
according to EN 60068-2-6 / EN 60068-2-27, EN 60068-2-29
EMC resistance burst / ESD
according to EN 61000-6-2 (EN 50082) / EN 61000-6-4 (EN 50081)
Installation position
any
Protection class
IP20