Register Description
KL401x and KL402x
11
User parameters
R32: Feature register:
[0x0006]
The feature register specifies the operating modes of the terminal.
Feature bit
no.
Description of the operating mode
Bit 0
1
User scaling (1.2) active [0]
Bit 1
1
Manufacturer scaling (1.1) active [1]
Bit 2
1
Watchdog timer active [1]
In the delivery state, the watchdog timer is switched on.
In the event of a watchdog overflow, either the
manufacturer or the user switch-on value is applied to
the terminal output.
Bit 3
1
Sign / amount representation [0]
Bit 7...4
-
reserved, do not change
Bit 8
0/1
0: Manufacturer switch-on value [0]
1: User switch-on value
Bit 15...9
-
reserved, do not change
R33: User scaling - offset (B_w)
16 bit signed integer [0x0000]
This register contains the offset of the user straight-line equation (4.1). The
straight-line equation is activated via register R32.
R34: User scaling - gain (A_w)
16 bits signed integer * 2
-8
[0x0100]
This register contains the scale factor of the user straight-line equation
(4.1). The straight-line equation is activated via register R32.
R35: User's switch-on value (Y_2)
16 bit signed integer [0x0000]
If the user switch-on value is activated in register R32, this value is applied
to the terminal output after a system reset or a watchdog timer overflow
(terminal has not received any process data for 100 ms).