Product overview
KL3356
10
Version: 2.3.0
2.2
Technical data
Technical data
KL3356/KS3356
Inputs
2, for one resistor bridge
Signal voltage U
D
-20 mV ... +20 mV
Input resistance (U
D
)
>1 MΩ
Supply voltage for the measuring bridge (U
V
)
5 V ... 12 V (recommended)
Reference voltage U
Ref
max. 12 V
Input resistance (U
ref
)
> 200 kΩ
Resolution
16 bits
Conversion time
< 250 ms, configurable
Measuring error (total measuring range)
±0.01% of the full scale value, self-calibration
Bit width in the K-bus I/O
2 x 16 bit user data, 2 x 8 bit control/status
Bit width in the input process image
2 data words, 2 status byte
Bit width in the output process image
2 data words, 2 control byte
Power supply for the electronics
via the K-bus
Current consumption from K-bus
typically 85 mA
Weight
approx. 75 g
Dimensions (W x H x D)
approx. 15 mm x 100mm x 70mm
on 35 mm mounting rail conforms to EN 60715
at all KSxxxx series terminals
Permissible ambient temperature range during
operation
0 °C ... + 55 °C
Permissible ambient temperature range during
storage
-25 °C ... + 85 °C
Permissible relative air humidity
95 %, no condensation
Vibration / shock resistance
conforms to EN 60068-2-6/EN 60068-2-27, see also
load capacity
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
2.3
Basic function principles
The KL3356 Analog Input Terminal is used to acquire the supply voltage to a load cell as a reference
voltage, and simultaneously the differential voltage that is proportional to the force acting on the cell. The
reference and the differential voltages are measured alternately by the same converter. The quotient of the
differential and the reference voltages corresponds to the force that is acting on the load cell. Deviations in
the analog input stages (temperature drift, long-term drift etc.) are checked by regular calibration, and
compensated to bring the measurement within the permitted tolerance range.
Strain gauge measuring signal
The strain gauge measuring signal is acquired at fixed intervals with a resolution of 16 bits (+ sign). This
value is saved as a data word, without sign, in register
. The sign is represented in bit
of the status word.
The length of the sampling interval is directly determined by the filter constant in register
.