Product overview
KL2819
10
Version: 1.1.0
2.2
Technical data
Technical data
KL2819
Connection technology
1-wire
Number of Outputs
16
Rated load voltage
24 V
DC
(-15 %/+20 %)
Current consumption from K-bus
typ. 30 mA
Load type
ohmic, inductive, lamp load
Max. output current
0.5 A (short-circuit-proof) per channel
Short circuit current
< typ. 1.1 A
Breaking energy
< 300 mJ/channel
Reverse voltage protection
yes
Current consumption power contacts
typ. 50 mA + load
Electrical isolation
500 V (K-bus/field potential)
Output stage
push (high-side switch)
Bit width in the process image
16 bit output and diagnostics (2 x 8 Bit-control/status
optional)
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
Weight
approx. 70 g
Mounting
on 35 mm mounting rail according to EN 60715
Permissible ambient temperature range during
operation
0°C ... +55°C
Permissible ambient temperature range during
storage
-25°C ... +85°C
Permissible relative humidity
95 %, no condensation
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Installation position
of
chapter Mounting and wiring
Protection class
IP20
Approvals/markings*
CE, UKCA, EAC
*) Real applicable approvals/markings see type plate on the side (product marking).
2.3
Overload protection
The maximum continuous output current per output is around 0.5 A.
When switching on lamp loads, high starting currents occur that are limited by the output circuit of the
terminals. This ensures that the upstream circuit breaker does not trip (see fig. Overload current limitation).