6000:0
DPO Inputs
Ch.1
Input of the first channel
UINT8
RO
0x10 (16
dec
)
6000:01
Error Us
The current monitoring of Us has tripped. The bit must be
reset by a ‘Global Reset’ (F707:04) or by the corresponding
Reset Us (7000:05). The output cannot be activated as
long as the bit is 1.
boolean
RO
0x00 (0
dec
)
6000:02
Error Up
The current monitoring of Up has tripped.
boolean
RO
0x00 (0
dec
)
6000:03
Warning Us
The monitoring has detected overcurrent; the switching off
of output Us on this channel is imminent if the current con-
sumption of the branch does not decrease.
boolean
RO
0x00 (0
dec
)
6000:04
Warning Up
The monitoring has detected overcurrent; the switching off
of output Us on this channel is imminent if the current con-
sumption of the branch does not decrease.
boolean
RO
0x00 (0
dec
)
6000:05
Status Us
0: The output is switched off
1: The output supplies 24 V
boolean
RO
0x00 (0
dec
)
6000:06
Status Up
0: The output is switched off
1: The output supplies 24 V
boolean
RO
0x00 (0
dec
)
6000:07
Channel Error
6000:01 or 6000:02 are set
boolean
RO
0x00 (0
dec
)
6000:0E
Sync error
boolean
RO
0x00 (0
dec
)
6000:0F
TxPDO State
boolean
RO
0x00 (0
dec
)
6000:10
TxPDO Toggle
boolean
RO
0x00 (0
dec
)
4.5.1.3.2
Index 6010 DPO Inputs Ch.2
Index
Name
Meaning
Data type
Flags
Default
6010:0
DPO Inputs
Ch.2
Input of the first channel
UINT8
RO
0x10 (16
dec
)
6010:01
Error Us
The current monitoring of Us has tripped. The bit must be
reset by a ‘Global Reset’ (F707:04) or by the corresponding
Reset Us (7000:05). The output cannot be activated as
long as the bit is 1.
boolean
RO
0x00 (0
dec
)
6010:02
Error Up
The current monitoring of Up has tripped.
boolean
RO
0x00 (0
dec
)
6010:03
Warning Us
The monitoring has detected overcurrent; the switching off
of output Us on this channel is imminent if the current con-
sumption of the branch does not decrease.
boolean
RO
0x00 (0
dec
)
6010:04
Warning Up
The monitoring has detected overcurrent; the switching off
of output Us on this channel is imminent if the current con-
sumption of the branch does not decrease.
boolean
RO
0x00 (0
dec
)
6010:05
Status Us
0: The output is switched off
1: The output supplies 24 V
boolean
RO
0x00 (0
dec
)
6010:06
Status Up
0: The output is switched off
1: The output supplies 24 V
boolean
RO
0x00 (0
dec
)
6010:07
Channel Error
6010:01 or 6010:02 are set
boolean
RO
0x00 (0
dec
)
6010:0E
Sync error
boolean
RO
0x00 (0
dec
)
6010:0F
TxPDO State
boolean
RO
0x00 (0
dec
)
6010:10
TxPDO Toggle
boolean
RO
0x00 (0
dec
)