Product description
EP1918
14
Version: 1.1.0
3.5
Safe inputs
The safe input modules and corresponding clock outputs have a two-channel design. This has the
advantage that a two-channel safe sensor with an M12 connection can be used, and a fault such as cross-
circuit or external feed results in shutdown of the whole module.
DANGER
Clocked signals inside a sheathed cable
If clocked signals (clock outputs for the safe inputs) of different modules are used within a sheathed cable,
a fault of one module, such as cross-circuit or external feed, must lead to the switch-off of all of these mod-
ules. This is achieved by setting the
Module Fault Link active
parameter for all modules involved. This pa-
rameter is set to TRUE by default.
DANGER
Safe inputs in Cat.4 / PL e
If two safe input channels are to be used in a category 4 structure that are not on one M12 connector,
please make sure to combine always an even and an odd channel number.