![Beckhoff EK1100 Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/beckhoff/ek1100/ek1100_documentation_2719363019.webp)
Product overview
EK110x, EK15xx
19
Version: 3.6
2.2.2.3
EK1101, EK1101-0080 - Technical data
Technical data
EK1101
EK1101-0080
Task within the EtherCAT system
Coupling of EtherCAT Terminals
(ELxxxx) to 100BASE-TX
EtherCAT networks
Coupling of EtherCAT Terminals
(ELxxxx) to 100BASE-TX
EtherCAT networks,
Fast Hot Connect technology
Number of EtherCAT Terminals
up to 65535 in the overall system
Number of peripheral signals
max. 4.2 GB addressable IO points
Transmission medium
at least Ethernet CAT-5 cable
Cable length between two Bus
Couplers
max. 100 m (100BASE-TX)
Protocol / Baud rate
EtherCAT Device Protocol / 100 MBaud
HotConnect
max. number of configurable IDs: 4096
Delay
typical 1 µs
Bus connection
2 x RJ45
Power supply
24 V
DC
(-15%/+20%)
Current consumption
70 mA + (E-bus current)/4
E-bus power supply (5 V)
depending on ambient temperature
(at higher current consumption the
EL9410
power feed terminal can be
used in addition)
max. 2000 mA (-25°C ... +55°C)
max. 1000 mA (> +55°C)
Power contacts
max. 24 V
DC
, max. 10 A
Electrical isolation
500 V (power contact/supply voltage/EtherCAT)
Dimensions (W x H x D)
approx. 44 mm x 100 mm x 68 mm
Weight
approx. 105 g
Permissible ambient temperature
range during operation
-25°C ... +60°C
Permissible ambient temperature
range during storage
-40°C ... + 85°C
Permissible relative humidity
95%, no condensation
Mounting [
}
37]
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
CE
ATEX [
}
54]
cULus [
}
52]
2.2.2.4
Notes re. EtherCAT Fast Hot Connect technology
EtherCAT components that support Fast Hot Connect enable a faster fieldbus boot up following the
establishment of a connection. The boot up depends in detail on the number of devices, the topology and
activated Distributed Clocks. Whereas the normal establishment of a connection and communication takes
several seconds, less than 1 second is possible with FHC components.
Properties and system behavior
• Fast Hot Connect is supported from TwinCAT 2.11R3 Build 2221.
• Fast Hot Connect ports are specially marked.