Product overview
EK110x, EK15xx
16
Version: 3.6
2.2.1.2
EK1100 - Technical data
Technical data
EK1100
Task within the EtherCAT system
Coupling of EtherCAT Terminals (ELxxxx) to
100BASE-TX EtherCAT networks
Number of EtherCAT Terminals
Up to 65535 in the overall system
Number of peripheral signals
max. 4.2 GB addressable IO points
Transmission medium
at least Ethernet CAT-5 cable
Cable length between two Bus Couplers
max. 100 m (100BASE-TX)
Protocol / Baud rate
EtherCAT Device Protocol / 100 MBaud
HotConnect
no
Delay
typical 1 µs
Bus connection
2 x RJ45
Power supply
24 V
DC
(-15%/+20%)
Current consumption
70 mA + (E-bus current)/4
E-bus power supply (5 V)
(at higher current consumption the
EL9410
power
feed terminal can be used in addition)
max. 2000 mA (-25°C ... +55°C)
max. 1000 mA (> +55°C)
Power contacts
max. 24 V
DC
, max. 10 A
Electrical isolation
500 V (power contact/supply voltage/EtherCAT)
Dimensions (W x H x D)
approx. 44 mm x 100 mm x 68 mm
Weight
approx. 105 g
Permissible ambient temperature range during
operation
-25°C ... +60°C
Permissible ambient temperature range during
storage
-40°C ... + 85°C
Permissible relative humidity
95%, no condensation
Mounting [
}
37]
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27,
see also
Installation instructions [
}
40]
for terminals
with increased mechanical load capacity
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
CE
ATEX [
}
54]
cULus [
}
52]