Error handling and diagnosis
CX8095
75
Version: 1.5
K-bus error code
Error code
Error code argument
Description
Remedy
Persistent, continuous
flashing
EMC problems
• Check power supply
for undervoltage or
overvoltage peaks
• Implement EMC
measures
• If a K-bus error is
present, it can be
localized by a restart
of the coupler (by
switching it off and
then on again)
3 pulses
0
K-bus command error
- No Bus Terminal
inserted
- One of the Bus
Terminals is defective;
halve the number of Bus
Terminals attached and
check whether the error is
still present with the
remaining Bus Terminals.
Repeat until the defective
Bus Terminal is located.
4 pulses
0
K-Bus data error, break
behind the Bus Coupler
Check whether the n+1
Bus Terminal is correctly
connected; replace if
necessary.
n
Break behind Bus
Terminal n
Check whether the bus
end terminal 9010 is
connected.
5 pulses
n
K-bus error in register
communication with Bus
Terminal n
Exchange the n
th
bus
terminal
6 pulses
0
Error at initialization
Exchange Bus Coupler
1
Internal data error
Perform a hardware reset
on the Bus Coupler
(switch off and on again)
8
Internal data error
Perform a hardware reset
on the Bus Coupler
(switch off and on again)
7 pulses
0
Process data lengths do
not correspond to the
configuration
Check the Bus Terminals
for the configured Bus
Terminals
1..n
K-bus reset failed
Check the Bus Terminals
9.2
Diagnostic history
The diagnostic history is an aid for monitoring the status of the EtherNet/IP interface, the status of the
terminal and the Ethernet port and to display the diagnostic messages in plain text with a time stamp.
Furthermore, information/errors that occurred in the past or only briefly are also logged in order to also allow
precise fault finding at a later time.
The diagnostic history is a component of the System Manager and can be found there on the "Diag History"
tab.
Содержание CX8095
Страница 1: ...Manual CX8095 Embedded PC with EtherNet IP Interface 1 5 2018 02 09 Version Date...
Страница 2: ......
Страница 56: ...Parameterization and commissioning CX8095 56 Version 1 5 1 Create a new controller 2 Append a new module...
Страница 65: ...Ethernet X001 Interface CX8095 65 Version 1 5 8 1 2 Topology example CX8095...
Страница 76: ...Error handling and diagnosis CX8095 76 Version 1 5...