Parameterization and commissioning
CX8095
53
Version: 1.5
Setting for setting (4 bytes + object size (256 bytes))
Byte Offset 0: 0x45
Byte Offset 1: 0x23
Byte Offset 2: ObjIndex LoByte (e.g. 0x8000 for Slave 1 and 0x8010 for Slave 2 and 0xF800 for the Master)
Byte Offset 3: ObjIndex HiByte
Byte Offset 4-260: Data of the object (see object description below)
Setting for resetting (4 bytes)
Byte Offset 0: 0x00
Byte Offset 1: 0x00
Byte Offset 2: ObjIndex LoByte (e.g. 0x8000 for Slave 1 and 0x8010 for Slave 2 and 0xF800 for the Master)
Byte Offset 3: ObjIndex HiByte
Object description
Offset
Name
Data Type
SubIndex
Store Category
1
2
0x00..0x01
Id
UINT16
1
0x02..0x03
Reserved
UINT16
-
0x04..0x23
Product Name
BYTE[32],
STRING(31)
3
X
0x24..0x27
Device Type
UINT32
4
0x28..0x2B
Vendor ID
UINT32
5
0x2C..0x2F
Product Code
UINT32
6
X
0x30..0x33
Revision
UINT32
7
0x34..0x37
Serial Number
UINT32
8
0x38..0x7D
Reserved
BYTE[70]
-
0x7E..0x83
MAC Address
BYTE[6]
32
0x84..0x87
IP Address
UINT32
33
X
0x88..0x8B
Network Mask
UINT32
34
X
0x8C..0x8F
Gateway
Address
UINT32
35
X
0x90..0x91
DHCP Max
Retries
UINT16
36
0x92..0x93
TCP/IP TTL
UINT16
37
0x94..0x95
TCP/IP UDP
Checksum
UINT16
38
0x96..0x97
TCP/IP TCP
Timeout
UINT16
39
0x98..0x99
Multicast TTL
UINT16
40
0x9A..0x9B
Multicast
Checksum
UINT16
41
0x9C..0x9D
Forward Class3
to PLC
UINT16
42
0x9E..0x9F
Flags
UINT16
43
0xA0..0xFF
Reserved
Byte[96]
-
Store Category
The "Store Category" defines, which *.tsm settings should be overwritten with settings from the remanent
memory. To do this, bits 9 & 8 must be set accordingly under "Flags" in the System Manager project. In order
to modify both, both bits must be set.
(Bit9=Cat2, Bit8=Cat1)
Содержание CX8095
Страница 1: ...Manual CX8095 Embedded PC with EtherNet IP Interface 1 5 2018 02 09 Version Date...
Страница 2: ......
Страница 56: ...Parameterization and commissioning CX8095 56 Version 1 5 1 Create a new controller 2 Append a new module...
Страница 65: ...Ethernet X001 Interface CX8095 65 Version 1 5 8 1 2 Topology example CX8095...
Страница 76: ...Error handling and diagnosis CX8095 76 Version 1 5...