Parameterization and commissioning
CX8095
26
Version: 1.5
6
Parameterization and commissioning
6.1
DIP switch
CAUTION
DIP switches as ignition source in potentially explosive atmospheres
Gases or dusts can be ignited by a spark discharge when DIP switches are used.
Switch off the power supply and wait until the 1-second UPS has discharged. Ensure that
there is no explosive atmosphere before you use DIP switches.
10-pole DIP switch S101
The DIP switch has only one meaning for the Ethernet interfaces X101 and X102 which are switched.
Left off "0", right on "1".
DIP switch S101
Meaning
10 on and 9 off
DHCP active
10 off and 9 off
Fixed IP address 192.168.1.xxx; xxx stands for DIP
switches 1 to 8, subnet mask is 255.255.255.0. The
"basic IP address" can be modified in the operating
system. The last byte of the IP address is then
specified once again by the DIP switches.
10 off and 9 off
DIP 1 to 8 all on
The complete IP address is taken from the operating
system.
2-pole DIP switch (under the flap between the battery and the SD card slot)
DIP switch (red)
Meaning
1 off and 2 off
normal mode, TwinCAT is started
1 on and 2 off
The CX mode starts in Config Mode; the flash
memory or, in the case of the CX80xx the SD card, is
reachable via the USB interface (for example for an
image update).
1 off and 2 on
Restore the registry
1 on and 2 on
No function so far
Содержание CX8095
Страница 1: ...Manual CX8095 Embedded PC with EtherNet IP Interface 1 5 2018 02 09 Version Date...
Страница 2: ......
Страница 56: ...Parameterization and commissioning CX8095 56 Version 1 5 1 Create a new controller 2 Append a new module...
Страница 65: ...Ethernet X001 Interface CX8095 65 Version 1 5 8 1 2 Topology example CX8095...
Страница 76: ...Error handling and diagnosis CX8095 76 Version 1 5...