Parameterizing and commissioning
CX8093
41
Version: 1.6
• Name by the System Manager
• Name by the PLC program and System Manager
Device settings
MAC address, VendorID and DeviceID are available to you for information and are not editable.
Generate Station Name from Control
With this an extension of the name can be assigned via the PLC program. The extension consists of a three-
digit numerical value. To do this, link the PnIoBoxCtrl with the PLC program. The value must be registered
as a constant value and must be available when starting the PLC *program. For example, the address of the
switch can be read and thus the name of the device formed with the function F_CX80xx_Address.
Example (ST):
Address:=16#FF AND INT_TO_WORD(F_CX80xx_Address(8093));
PnIoBoxCtrl:=Address;
Get Station Name from Tree
This means that the name of the Profinet device will be taken from the System Manager tree.
Register PN IP settings not at the OS
For the CCAT ports the PROFINET IP address is registered in the operating system on delivery. If TwinCAT
is in RUN, the device can be accessed in this way via normal TCP/IP mechanisms. If no registered
PROFINET IP address is desired in the operating system, this feature can be disabled via the System
Manager.