background image

Product Description 

 

 

2.3 LED-Diagnostic 

 

LED  Allocation 

State 

Meaning 

off 

no supply voltage 

P10 Power 

supply 

shining green  5 V

DC

 for downstream ports is provided 

shining green  the total current of all 4 downstream ports is less than 2.5 A 

P11 Current 

control 

shining red 

the total current of all 4 downstream ports is bigger than 2.5 A 

off 

port not operational 

shining green  port fully operational 
blinking green   software attention  
shining red 

Error condition e.g. overcurrent (port current > 1 A or short circuit) 

P31 

USB Port 1 

blinking red 

hardware attention 

off 

port not operational 

shining green  port fully operational 
blinking green   software attention  
shining red 

Error condition e.g. overcurrent (port current > 1 A or short circuit) 

P32 

USB Port 2 

blinking red 

hardware attention 

off 

port not operational 

shining green  port fully operational 
blinking green   software attention  
shining red 

Error condition e.g. overcurrent (port current > 1 A or short circuit) 

P33 

USB Port 3 

blinking red 

hardware attention 

off 

port not operational 

shining green  port fully operational 
blinking green   software attention  
shining red 

Error condition e.g. overcurrent (port current > 1 A or short circuit) 

P34 

USB Port 4 

blinking red 

hardware attention 

 

 

8

 

CU8005-0000 

Содержание CU8005-0000

Страница 1: ...Installation and Operating instructions for CU8005 0000 4 Port USB 2 0 Hub Version 1 3 Date 2018 04 27 ...

Страница 2: ......

Страница 3: ...symbols 4 2 Product Description 5 2 1 Product Overview 5 2 2 Connections 6 2 2 1 Power Supply 6 2 2 2 Data Connections 7 2 3 LED Diagnostic 8 3 Installation 9 3 1 Transport and Unpacking 9 3 1 1 Transport 9 3 1 2 Unpacking 9 3 2 Mounting Demounting 10 3 3 Connecting devices 11 3 3 1 Mounting power supply connector 11 3 3 2 Connecting cables 11 4 Operation 12 4 1 Maintenance 12 4 1 1 Cleaning 12 4 ...

Страница 4: ...of contents 7 1 1 Beckhoff branches and partner companies 15 7 1 2 Beckhoff company headquarters 15 7 2 Approvals for USA and Canada 16 7 3 FCC Approval for USA 16 7 4 FCC Approval for Canada 16 2 CU8005 0000 ...

Страница 5: ...f Automation GmbH Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owners 1 1 3 Patent Pending The EtherCAT Technology is covered including but not limited to the following patent applications and patents EP1590927 EP1789857 DE102004044764 DE102007017835 with corresponding applications or registrations i...

Страница 6: ...tained herein the operation manual is in good condition and complete and always available for reference at the location of the product none of the safety and warning notes attached to product are removed and that all notes remain legible 1 3 Description of safety symbols The following safety symbols are used in this operating manual They are intended to alert the reader to the associated safety in...

Страница 7: ...ments of industrial applications through several outstanding features User friendly installation via integrated top hat rail adapter 24 VDC supply voltage the standard in industrial environments Delivers up to 1 A supply current from each USB downstream port 480 Mbit 12 Mbit and 1 5 Mbit support for compatibility to all USB standards Compact industrial design Clear quick diagnostic by separate LED...

Страница 8: ...nal X10 labeled 24 V This supply feeds the hub electronics and over the USB downstream ports the connected USB devices 5 VDC It is protected against polarity reversal UL Requirements Attention To meet the UL requirements the device must not be connected to unlimited power sources Pin Assignment Power Supply Connector Pin Assignment 1 PE 2 GND 3 24 V DC 6 CU8005 0000 ...

Страница 9: ...ctors USB Port type B USB type A input The pins are described below USB Typ B Port X20 standard cable Pin Assignment 1 VCC 2 Data 3 Data 4 GND Shield Shield USB Typ A Port X31 X32 X33 X34 standard cable Pin Assignment 1 VCC 2 Data 3 Data 4 GND shield Shield CU8005 0000 7 ...

Страница 10: ... Port 1 blinking red hardware attention off port not operational shining green port fully operational blinking green software attention shining red Error condition e g overcurrent port current 1 A or short circuit P32 USB Port 2 blinking red hardware attention off port not operational shining green port fully operational blinking green software attention shining red Error condition e g overcurrent...

Страница 11: ...e condensation does not form on or inside the device Prior to operation the unit must be allowed to slowly adjust to room temperature Should condensation occur a delay time of approximately 12 hours must be allowed before the unit is switched on 3 1 2 Unpacking Proceed as follows to unpack the unit 1 Remove packaging 2 Do not discard the original packaging Keep it for future relocation 3 Check the...

Страница 12: ...000 can be snapped onto a 35 mm mounting rail conforms to EN 50022 To release the CU8005 0000 from the mounting rail 1 first pull the lug at the bottom of the hub downwards by using a screw driver 1 2 then pull the hub from the mounting rail 2 10 CU8005 0000 ...

Страница 13: ...will be installed with a screwdriver 2 1 3 4 1 Insert screwdriver into the left hole 2 Plug bared cable into right hole 3 Remove screwdriver 4 The Cable is installed 3 3 2 Connecting cables The connections are documented in the section Product Description When connecting the cables to the CU8005 0000 proceed according to the following sequence Switch off all the devices that are to be connected Di...

Страница 14: ...e The CU8005 0000 USB hub is maintenance free 4 2 Shutting down 4 2 1 Disposal Observe national electronics scrap regulations Note Observe the national electronics scrap regulations when disposing of the device In order to dispose of the device it must be removed and fully dismantled Housing components polycarbonate polyamide PA6 6 are suitable for plastic recycling Metal parts can be sent for met...

Страница 15: ...l overall installed size With a height of 100 mm the module dimensions exactly match those of the Beckhoff Bus Terminals Together with the lowered connector surfaces this means that it can be used in a standard terminal box with a height of 120 mm CU8005 0000 13 ...

Страница 16: ...pply Current consumption from 24 V open circuit operation 80 mA if connected with host 110 mA maximum 1 A with USB devices connected Dimensions w x h x d app 34 mm x 100 mm x 86 mm with power supply terminal and lug for mounting rail release Weight app 120 g Permissible ambient temperature 0 C to 55 C operation 25 C to 70 C transport storage Permissible relative humidity 5 to 95 no condensation EM...

Страница 17: ...o KG Huelshorstweg 20 33415 Verl Germany Phone 49 0 5246 963 0 Fax 49 0 5246 963 198 E mail info beckhoff de Web http www beckhoff de Beckhoff Support Support offers you comprehensive technical assistance helping you not only with the application of individual Beckhoff products but also with other wide ranging services world wide support design programming and commissioning of complex automation s...

Страница 18: ...es and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Technical modifications Note Technical modifications t...