Product Description
2.4 Interfaces CP29xx-0000
X104
USB in
X102,
X103
USB out
Ground
X101
Power
X106
DVI-E Input
X105
USB-E
Input
2.4.1 DVI-E Input (Digital Visual Interface-Extended) (X106)
X106
DVI-D 3 X 8-pole digital PCB installation (MOLEX 74320-9000 / 74320-9004)
The DVI-E connection
(X 106)
is used for transferring the video signal from the Industrial PC to the
Control Panel.
The graphics signal is transferred directly via a DVI cable over a distance of 50 m max. Such a cable
length leads to strong distortion of the graphics signal on arrival at the Control Panel. The CP29xx Control
Panel features a signal processor that restores the DVI signal. The PC requires a conventional DVI
output.
Pin
Signal
Pin
Signal
1 Rx2-
13 Rx3+
2
Rx2-
14
+ 5V DVI
3 GND
15 GND
4 Rx4-
16 HPD
5 Rx4+
17 Rx0-
6 DDC
CLK
18 Rx0+
7 DDC
DAT
19 GND
8 AV
SYNC
20 Rx5-
9 Rx1-
21 Rx5+
10 Rx1+
22 GND
11 GND
23 RxC+
12 Rx3-
24 RxC-
2.4.2 USB-Extended Input (X 105)
X105
Connection via standard-RJ45-cabel, not crossed
The Control Panel is connected with the CU8801 USB to USB extended converter box via the USB-
Extended input (
X 105
).
In order to realize a distance of 50 m without hubs, with USB extended the USB signal is converted so
that it can be transferred via 50 m CAT5 cables commonly used for Ethernet wiring. In the Control Panel
the signal is converted back to USB.
10
CP29xx
Содержание CP29xx-0000 Series