background image

 

Appendix 

 

C9900-P209 

13 

Appendix 

 

Technical data 

Electrical data 

Input voltage:

 

21-30V DC/ 16A 

Power output:

 250W 

(max.) 

Output voltages:

 

see section Product Description  

 

 

Dimensions 

Dimensions (W x H x D):

   97.0 x 44.0 x 203.9 mm

 

Weight:

 0.85 

kg 

 

Do not use the power 
supply unit in areas of 
explosive hazard 

The power supply unit must not be used where there is a risk of 
explosion. 

 

 

The following conditions must be observed during operation: 

Environmental conditions 

Ambient temperature:

  

0 to 55°C 

Atmospheric humidity:

 

Maximum 95%, non-condensing 

 

Shock resistance 

Sinusoidal vibration 
(EN 60068-2-6):

 

10 to 58 Hz:

 

0.035 mm 

 

58 to 500 Hz:  0.5 G (~ 5 m/ s

2

Impact 
(EN 60068-2-27/ -29):

 

5 G (~ 50 m/ s²), duration: 30 ms 

EMC compatibility  

Resistance to interference:

 according to EN 61000-6-2 

 

Emission of interference:

  according to EN 61000-6-4 

Transport and storage 

The same values for atmospheric humidity and shock resistance are to be 
observed during transport and storage as in operation. The shock 
resistance during transport can be improved by appropriate packaging of 
the power supply unit. The ambient temperature during storage and 
transport must be between -20°C and +65°C. 

 

 

Approvals 

 

FCC: Federal Communications Commission 
Radio Frequency Interference Statement 

FCC Approval for USA 

This equipment has been tested and found to comply with the limits for a 
Class A digital device, pursuant to Part 15 of the FCC Rules. These limits 
are designed to provide reasonable protection against harmful interference 
when the equipment is operated in a commercial environment. This 
equipment generates, uses, and can radiate radio frequency energy and, if 
not installed and used in accordance with the instruction manual, may 
cause harmful interference to radio communications. Operation of this 
equipment in a residential area is likely to cause harmful interference in 
which case the user will be required to correct the interference at his own 
expense. 

 

FCC: Canadian Notice 

FCC Approval for Canada 

This equipment does not exceed the Class A limits for radiated emissions 
as described in the Radio Interference Regulations of the Canadian 
Department of Communications. 

 

Содержание C9900-P209

Страница 1: ...Operating instructions for C9900 P209 power supply unit Version 1 1 Date 2006 01 26...

Страница 2: ......

Страница 3: ...rial PC 6 Preparing the cable harness 6 External wiring 7 Power supply of the Industrial PC 7 On Off switch 7 Wiring 7 Installation of the supply cables 8 Connector installation 8 Cable cross sections...

Страница 4: ...out in 443 of the German Civil Code or a statement about the assumed use according to the contract as set out in 434 para 1 clause 1 no 1 of the German Civil Code In the event that it contains techni...

Страница 5: ...r supply unit and the Industrial PC Items of equipment that have been switched off must be secured against being switched on again Danger Do not open the power supply unit while voltage is applied The...

Страница 6: ...er battery packs are used Electrical data Input voltage 22 30V DC 15A Power output 250W max Output voltages 5V 14A 12V 12A 3 3V 12A 5V 0 3A 12V 0 5A 5VSB 1 5A Configuration and installation C9900 P209...

Страница 7: ...ns of the board 5 12V supply Pin assignment of the pin strips Pin Function Pin Function 1 3 3V 11 3 3V 2 3 3V 12 12V 3 GND 13 GND 4 5V 14 PS ON 5 GND 15 GND 6 5V 16 GND 7 GND 17 GND 8 PWR OK 18 5V 9 5...

Страница 8: ...for connecting the power supply unit with the connection sockets in the Industrial PC Due to different cable lengths the harness is produced individually for each type of computer The wiring diagram s...

Страница 9: ...onnecting the power supply and the battery pack Pin Function 1 Power supply 24 V 2 Power supply GND 3 Protective conductor 4 Battery pack 24 V 5 Battery pack GND Pin assignment for connecting power su...

Страница 10: ...move the insulation from the cable ends 8 9 mm 2 Push the cable into the holders applying slight pressure according to the pin assignment label and the wiring diagram 3 Push the lower part part A of t...

Страница 11: ...rol panel After successful installation of the software an additional Beckhoff UPS configuration tab will appear under Start Settings Control Panel Power Options This is used for configuring the devic...

Страница 12: ...Support offers you comprehensive technical assistance helping you not only with the application of individual Beckhoff products but also with other wide ranging services world wide support design prog...

Страница 13: ...Assembly dimensions Assembly dimensions Device dimensions and mounting points Dimensional notation in mm C9900 P209 11...

Страница 14: ...Wiring diagram Wiring diagram C9900 P209 power supply unit in conjunction with C9900 U330 battery pack 12 C9900 P209...

Страница 15: ...ck resistance during transport can be improved by appropriate packaging of the power supply unit The ambient temperature during storage and transport must be between 20 C and 65 C Approvals FCC Federa...

Отзывы: