Product Description
Installation of the supply cables
Wiring according to the
wiring diagram
Install the cables for the power supply of the Industrial PC, the connection
of the battery pack and the connection of the illuminated toggle switch
according to the wiring diagram using the connector assembly material
provided.
Connector assembly is described using the example of the 5-pole female
plug connector:
Materials for assembly of
the connector
Female plug connector, 5-pole
Strain relief housing
A
B
C
D
Connector installation
Fitting the connector to the
cable
The plug is fitted to the cable as follows:
1. Remove the insulation from the cable ends (8 - 9 mm).
2. Push the cable into the holders, applying slight pressure according
to the pin assignment label and the wiring diagram.
3. Push the lower part (part
A
) of the strain relief housing onto the top
of the female plug connector until it snaps into place.
4. Relieve the strain on the supply cable by fixing it in place with the
cable clamp (part
C
) and fixing screws (part
D
) (see photograph
below).
Applying the strain relief
Fix the upper part (part
B
) of the strain relief housing by snapping it onto
the lower part.
Cable cross-sections
Avoid voltage drop
Use cables with a cross-section of 2.5 mm
2
(AWG 14) for the supply lines
to the Industrial PC. The distance between power supply and PC should
not exceed 10 m in order to avoid excessive voltage drop in the cable.