Electrical installation
88
───
Version: 1.1
AMP8000 and AMP8500
Installation with protective conductor connection
When installing electrical systems and components, the protective
conductors must be connected first. They must be disconnected
last when uninstalling.
Depending on the magnitude of the leakage currents, observe the
following regulations for the implementation of the protective con-
ductor connection:
• Minimum requirement for protective conductor: KU value of 4.5
• The minimum requirement for leakage currents: I
L
< 10 mA; KU
= 6 for I
L
> 10 mA
Value
Explanation
KU
Variable for the classification of safety-related types of
failure for protection against dangerous shock current
and excessive heating
KU = 4.5
Achieved in relation to interruption:
With permanently connected protective conductor con-
nection
≥ 1.5 mm
2
With protective conductor connections ≥ 2.5 mm
2
via
connector for industrial plants according to IEC 60309-2
KU = 6
Achieved in relation to interruption:
With permanently connected conductors ≥ 10 mm
2
; the
type of connection and routing must comply with the
standards applicable to PE conductors
Содержание AMP8000
Страница 1: ...Operating instructions EN AMP8000 and AMP8500 Distributed servo drives 11 15 2022 Version 1 1 ...
Страница 2: ......
Страница 43: ...Technical data Version 1 1 43 AMP8000 and AMP8500 4 3 1 2AMP8620 2005 0100 4 3 1 2 ...
Страница 44: ...Technical data 44 Version 1 1 AMP8000 and AMP8500 4 3 1 3AMP8620 2005 0200 4 3 1 3 ...
Страница 47: ...Technical data Version 1 1 47 AMP8000 and AMP8500 4 5 1 2AX8832 0000 0000 4 5 1 2 ...
Страница 108: ......