Features

Table of Contents

Definitions

myTechnician™

 

Diagnostics and programming through the 
myTechnician™ app

 

Last 50 cycles and last 15 faults

 

Compatible with burners running #2 Fuel 
oil, up to 100% biodiesel, and up to 100% 
renewable diesel.

 

Interrupted or Intermittent Duty Ignition

 

Limited Recycle

 

Limited Reset

 

8 Status Lights

 

Valve-On Delay (also known as “Pre-Purge”)

 

Motor-Off Delay (also known as “Post-Purge”)

 

Blocked Vent and/or Combustion Air Inputs

 

Technician Pump Priming Mode

 

Disable Function

 

Water Resistant Case

 

Encapsulated electronics (7585 only)

 

Thermostat “C” terminal (for enhanced 
compatibility)

 

Intermittent - ignition remains on during the 
entire cycle

 

Interrupted - ignition turns off after flame is proven

 

Recycle - if flame is lost after Trial for Ignition 

(TFI), then burner resets for 60 seconds and 
retries automatically if it has not exceeded the 
allowable number of retries.

 

Relight - if flame is lost after Trial for Ignition 

(TFI), then ignition automatically turns back on

For displaying status information, programming 

control timings, and viewing the history log, the 7565 

and 7585 are compatible with the myTechnician

 

app available from your device’s app store. 

for Android Devices

myTechnician App

for Apple Devices

myTechnician App

Note: All features in this document apply to both 
the 7565 and the 7585 unless otherwise noted.

Content

Page

Features

2

Definitions

2

MyTechnician

2

Installation/Operation/Maintenance

4

Startup / Checkout

6

Sequence of Operation

7

Maintenance

9

Appendix A - Typical Boiler Wiring

10

Appendix B - Typical Furnace Wiring

10

Appendix C - Typical Thermostat Wiring

11

Appendix D - Typical Air Input Wiring

11

 

Blocked Vent (BV) - The control will not start a 
heat cycle unless the switch is closed. The control 
will Recycle if the switch opens after a successful 
ignition trial period. It must be closed during burner 
cycles. Use this setting with a blocked vent switch.

 

Combustion Air Proving (CAP) - The control will 
not start a heat cycle unless the switch is open. 
The control will Recycle if the switch does not 
close after the motor is turned on and remain 
closed throughout the rest of the heat cycle. Use 
this setting with a power venter.

Green

Red

Yellow

TT

On = TT 

Closed

n/a

n/a

LIM

On = Limit 

closed

n/a

n/a

MTR

On = Running On = Fault

n/a

IGN

On = Running On = Fault

n/a

VLV *

On = Running On = Fault

n/a

FLM

On = Flame 

Present

On = no flame 

detected

On = Flame out of 

sequence or cad 

cell shorted

AIR *

On = All 

installed 

switches ok

On = Blocked 

flue

On = Inlet air fault

SYS

On = Power

On = Hard 

Lockout Flashing 

= Soft Lockout

On = Pump prime  

Flashing = Recycle

Asterisk = If installed

Table 1 - Status Lights

Содержание GENISYS 7565

Страница 1: ...il burners used in boiler furnace and water heater applications having firing rates less than 20 GPH The GeniSys is used with a suitable cad cell flame sensor to control the oil burner motor igniter a...

Страница 2: ...cian App for Apple Devices myTechnician App Note All features in this document apply to both the 7565 and the 7585 unless otherwise noted Content Page Features 2 Definitions 2 MyTechnician 2 Installat...

Страница 3: ...input 24VAC Air switch input 24VAC Asterisk If installed NOTE All front connections are low voltage 24 Vac connections ACTION Button See Table 2 Status Lights See Table 1 Caution if replacing a non Be...

Страница 4: ...l could result in severe personal injury death or substantial property damage from heavy smoke explosion or fire Please read and understand the manual supplied with this control This control must be i...

Страница 5: ...ty controls include but not limited to high temperature or pressure limits low water cutoffs pressure relief valves and blocked flue sensing switches Verify all limit and safety controls are installed...

Страница 6: ...er to the steps for Starting the System and have the system call for heat 2 After flame is established and the burner igniter turns off close the hand valve in the oil supply line 3 At flame loss the...

Страница 7: ...on the oil solenoid valve for the programmed time This feature requires either a Beckett Clean Cut pump or an external valve 4 Trial For Ignition TFI If used the oil solenoid valve is energized A flam...

Страница 8: ...ombustion hot gas puff back and heavy smoke Do not allow oil to spray into a hot combustion chamber while bleeding air from the pump Install a gauge in the nozzle discharge port tubing or fully open t...

Страница 9: ...e correct Replace any control that does not meet listed specifications with an equivalent replacement unit Fire Smoke Fuel Leak Hazard Before starting or resetting the control from restricted lockout...

Страница 10: ...NALS LOCATED ON OPPOSITE SIDE OF CONTROL L1 L2 MOTOR IGNITER CAD CELL OIL VALVE CAD CAD BV L2 MTR L2 IGN VLV MTR L2 VLV IGN L2 3 L1 1 LIM 2 Connector Pins THERMOSTAT RED WHITE TR TW Terminals Located...

Страница 11: ...llation and Operation Manual Figure 9 3 Wire Thermostat Figure 11 24Vac Blocked Vent Wiring Figure 13 120Vac Blocked Vent Wiring Figure 10 Thermostat Wiring with External Transformer For example an ai...

Страница 12: ...duct specifications To review the complete warranty policy and duration of coverage for a specific product or obtain a written copy of warranty form 61545 please choose one of the following options 1...

Отзывы: