Electrical Ratings 

Power:

 

Voltage: 120 Vac nominal (102 to 132 Vac)

 

Current: 100 mA nominal (150 mA max at 132 Vac)*

 

Frequency: 60 Hz

    *measured when the motor, valve, and igniter 

are all de-energized

Inputs:

 

Thermostat Anticipator Current: 0.1 A nominal

 

Thermostat Voltage: 24 Vac nominal

 

Combustion Air/Blocked Vent  
(Front side): 10mA @ 24Vac min 
(Underside): 1.9mA @ 120Vac min

Outputs:

 

Motor: 120 Vac, 10 max full load amps (FLA), 
60 max locked rotor amps (LRA)

 

* Note: Reduce motor FLA rating by igniter and 

valve currents

 

Igniter: 120 Vac, 3 A max

 

Solenoid Valve: 120 Vac, 1 A max

Environmental Ratings:

 

Storage and Operating Ambient Temperature: 
-40°F to +150°F (-40°C to +65°C)

 

Moisture: 5 to 95% RH, non-condensing and 
non-crystallizing

 

7585 is rated for condensing environments

Approvals:

 

Underwriters Laboratory Recognition per UL 
60730-1 / 60730-2-5, CSA E60730-1 / C22.2 
NO. 60730-2-5

Installation/Operation/

Maintenance

Do Not Use This 

Control in an 

Application that is Not Within 

the Ratings Listed in This 

Section. Improper Control 

Operation May Result.

Do Not Use This Control 
Above 19.9 GPH

Most codes and standards require additional 
safeguards and features for oil burner inputs 
above 19.9 gph.  Consult the appliance 
manufacturer’s instructions for control selection.

Professional 
Service Required

Incorrect installation or misuse of 
this control could result in severe 
personal injury, death, or 
substantial property damage from 

heavy smoke, explosion or fire.

Please read and understand the manual 
supplied with this control. This control 
must be installed, adjusted and put into 

operation only by a qualified individual or 

service agency that is:

• 

Licensed or certified to install and provide 

technical service to oil heating systems.

• 

Experienced with all applicable codes, 
standards and ordinances.

• 

Responsible for the correct installation 
and commission of this equipment.

• 

Skilled in the adjustment of oil burners 
using combustion test instruments.

The installation must strictly comply with 
all applicable codes, authorities having 
jurisdiction and the latest revision of 
the National Fire Protection Association 
Standard for the Installation of Oil-Burning 
Equipment, NFPA 31 (or CSA-B139 and 

CSA-B140 in Canada).

Regulation by these authorities take 
precedence over the general instructions 
provided in this installation manual.

Frozen Plumbing 
and Water 
Damage Hazard

If the residence is unattended in severely 
cold weather, burner primary control safety 
lockout, heating system component failures, 
power outages or other electrical system 
failures could result in frozen plumbing 
and water damage in a matter of hours. For 
protection, take preventive actions such 
as having a security system installed that 
operates during power outages, senses low 
temperature and initiates an effective action. 
Consult with your heating contractor or a 
home security agency. 

Содержание GENISYS 7565

Страница 1: ...il burners used in boiler furnace and water heater applications having firing rates less than 20 GPH The GeniSys is used with a suitable cad cell flame sensor to control the oil burner motor igniter a...

Страница 2: ...cian App for Apple Devices myTechnician App Note All features in this document apply to both the 7565 and the 7585 unless otherwise noted Content Page Features 2 Definitions 2 MyTechnician 2 Installat...

Страница 3: ...input 24VAC Air switch input 24VAC Asterisk If installed NOTE All front connections are low voltage 24 Vac connections ACTION Button See Table 2 Status Lights See Table 1 Caution if replacing a non Be...

Страница 4: ...l could result in severe personal injury death or substantial property damage from heavy smoke explosion or fire Please read and understand the manual supplied with this control This control must be i...

Страница 5: ...ty controls include but not limited to high temperature or pressure limits low water cutoffs pressure relief valves and blocked flue sensing switches Verify all limit and safety controls are installed...

Страница 6: ...er to the steps for Starting the System and have the system call for heat 2 After flame is established and the burner igniter turns off close the hand valve in the oil supply line 3 At flame loss the...

Страница 7: ...on the oil solenoid valve for the programmed time This feature requires either a Beckett Clean Cut pump or an external valve 4 Trial For Ignition TFI If used the oil solenoid valve is energized A flam...

Страница 8: ...ombustion hot gas puff back and heavy smoke Do not allow oil to spray into a hot combustion chamber while bleeding air from the pump Install a gauge in the nozzle discharge port tubing or fully open t...

Страница 9: ...e correct Replace any control that does not meet listed specifications with an equivalent replacement unit Fire Smoke Fuel Leak Hazard Before starting or resetting the control from restricted lockout...

Страница 10: ...NALS LOCATED ON OPPOSITE SIDE OF CONTROL L1 L2 MOTOR IGNITER CAD CELL OIL VALVE CAD CAD BV L2 MTR L2 IGN VLV MTR L2 VLV IGN L2 3 L1 1 LIM 2 Connector Pins THERMOSTAT RED WHITE TR TW Terminals Located...

Страница 11: ...llation and Operation Manual Figure 9 3 Wire Thermostat Figure 11 24Vac Blocked Vent Wiring Figure 13 120Vac Blocked Vent Wiring Figure 10 Thermostat Wiring with External Transformer For example an ai...

Страница 12: ...duct specifications To review the complete warranty policy and duration of coverage for a specific product or obtain a written copy of warranty form 61545 please choose one of the following options 1...

Отзывы: