Bryan Steam
DR
Series Boiler
Boiler
Burner
Chassis
Spec.
Air Tube
Combination
High
Fire
Rate
Nozzle
Head
Setting
Blue -
Low Fire
Air or
Shutter
Red -
High Fire
Air or
Band
Low Fire
Pump
Press.
High Fire
Pump
Press.
Pressure
Firing
Flange
Insertion
250
CF375
BCF3907
CF56KZ
1.79
1.50x60ES
1
10
1/2
N/A
140
51311
5.00"
350
CF375
BCF3907
C100KZ
2.50
2.00x60P
3
10
2
N/A
190
51311
5.00"
450
CF500
BCF809
CF100KK
3.21
2.50x45P
4
4
0
N/A
150
51311
5.00"
650
CF800
BCF403
CF100KH
4.64
4.00x60B (D)
3
7
0
N/A
140
51311
5.50"
850
CF800
BCF403
CF100KJ
6.07
5.00x45B (D)
2
8
8
N/A
150
51311
5.50"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.