2. Removal of Old Panel
2.1 Remove Ohmeda Front Panel
1. Prior to removal and installation of control
panels, verify zone valve is shut o
ff
and line
to control panel is not pressurized.
2. Loosen set screws of on-o
ff
valve handle and
remove handle.
3. Remove regulator adjusting screw and knob
by unscrewing from regulator.
4. Unscrew lens covers from gauges and
remove.
5. Remove screws from cover plate. Remove
cover plate. Discard
6. Disconnect both tubing connections at top of
box.
7. Remove screws in mounting brackets and
remove control panel manifold from box.
Discard.
Figure 1
CAUTION:
Prior to removal and installation of control
panels, verify zone valve is shut o
ff
and line to
control panel is not pressurized.
Cover Plate
Regulator
Adjusting Screw
and Knob
Tubing
Connections
On-Off Valve Handle
Gauge Lens
Covers
Regulator
Mounting
Bracket
3. Installing New Panel
3.1 Installing
Retro
fi
t Kit
1. Remove
fl
are nut assembly (supplied with
retro
fi
t kit) from polyethylene bag and install
to
fi
ttings at top of rough-in box.
2. Remove protective dust caps from hose
ends. Insert hose assembly end into left inlet
connector inside mounting box. Push hose
adapter through collet into connector until it
bottoms out. Pull back on the hose assembly
to verify proper attachment.
Figure 2
Figure 3
Figure 4
Wall Mount Gas Control Panel
4107 9027 47.00
2
Содержание 4107 9027 47.00
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 11: ...5 4107 9027 47 00 Wall Mount Gas Control Panels Notes...
Страница 12: ...1059 Paragon Way Rock Hill SC 29730 888 4 MEDGAS 888 463 3427 Fax 803 817 5750 www beaconmedaes com...