Installation Manual – Rx100 Interface Edition 1.5
March 2001
Page 7
CABLE CONNECTION METHOD
Fig. 1: Wago connectors
The WAGO PCB terminal block is a simple-to-use method of
attaching cables to PCBs quickly and easily. Prepare cables
as follows:
•
Use only cable between 0.08 and 2.5 mm²
•
Strip the cable to a length of 5 to 6 mm (0.23 in)
The correct method of attachment is as follows:
1. Press down the relevant terminal block lever with a
suitable screwdriver;
2. Insert wire;
3. Remove screwdriver.
The procedure for detaching wires is the reverse of the 3
attachment steps, ensuring that
power is disconnected
before starting.
CABLING RECOMMENDATIONS FOR THE Rx100 INTERFACE.
Although BBV do not specify any particular type, manufacturer or supplier of cables, the following
ESD Electronic Services (01279 626777) cables have been used successfully for production and
testing:
ESD Part Number:
Description:
0222586G
Co-Ax Cable (Minimum Specification)
(100 m)
RG59B/U ESD radio frequency coax cable to BS2316 and MIL-C-17
1/0.58mm copper-covered steel wire conductor with solid polythene
dielectric, bare copper wire braid and PVC sheath
Characteristic impedance: 75 Ohm
Capacitance: 22pF/ft
020966D
Orange-Coloured Lighting Output Power Cable (1000 w)
(100 m)
3183Y PVC-insulated, 3-core cable
1.25mm
²
40/0.2mm annealed copper conductor
Current rating: 13 amp
0140467H
20mA Twisted Pair Cable (Minimum Specification)
(100 m)
British Telecom spec CW 1308
2-core 1/0.5mm PVC-insulated
Maximum conductor resistance at 20 degrees Celsius: 97.8 ohms/km